TOSHIBA VF-S15 Modbus register map

Factory protocol is Toshiba's own; set f829 = 1 for Modbus RTU. The hex communication number is the address: commands FA00/FA01, monitors from FD00, parameters from 0800. · Inverter (VFD)

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)19200 bps — options: 9600, 19200, 38400
Data · parity · stop8 · Even · 1
Max per request8 registers
Manual address styleWire address as is (0-based)

Registers (32)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

32

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
0800 (f800)2048 (0x0800)HRBaud rateU16R/W03·06·10
Takes effect after reset or power cycle
3 = 9600 bps · 4 = 19200 bps (default) · 5 = 38400 bps
p.47
0801 (f801)2049 (0x0801)HRParityU16R/W03·06·10
0 = None · 1 = Even (default) · 2 = Odd
p.47
0802 (f802)2050 (0x0802)HRInverter number (slave ID)U16R/W03·06·10
Default 0. In Modbus 0 is broadcast, so set 1-247
Range 0 ~ 247
p.47, p.49
0803 (f803)2051 (0x0803)HRCommunication time-out timeU16×0.1 sR/W03·06·10
0.0 = disabled (default)
Range 0 ~ 100 s
p.47
0804 (f804)2052 (0x0804)HRCommunication time-out actionU16R/W03·06·10
0 = Alarm only (default) · 1 = Trip (coast stop) · 2 = Trip (deceleration stop)
p.47
0829 (f829)2089 (0x0829)HRCommunication protocolU16R/W03·06·10
Takes effect after reset
0 = Toshiba inverter protocol (default) · 1 = Modbus RTU
p.47, p.24
FA0064000 (0xFA00)HRCommunication command 1U16W06·10
E.g. 8400h = command priority + run (forward), C400h also enables frequency priority. Stored in RAM only
b7 DC braking (1 = forced DC braking) · b8 Jog run · b9 Forward/reverse (0 forward, 1 reverse) · b10 Run/stop (1 = run) · b11 Coast stop command (1 = coast stop) · b12 Emergency stop (always enabled, 'E' trip) · b13 Fault reset (the inverter returns no reply) · b14 Frequency priority (1 = communication frequency enabled regardless of fmod) · b15 Command priority (1 = communication commands enabled regardless of cmod)
p.52 Table 1, p.69
FA0164001 (0xFA01)HRFrequency command (communication)U16×0.01 HzW06·10
0 to maximum frequency (fh). Write example 01 06 FA 01 17 70 = 60.00 Hz (p.31)
p.54, p.69
FA1364019 (0xFA13)HRMotor speed commandU16min-1W06·10
Range 0 ~ 24000 min-1
p.54, p.69
FA5064080 (0xFA50)HRTerminal board output dataU16W06·10
b0 Specified data output 1 (output function 92/93) · b1 Specified data output 2 (output function 94/95)
p.55
FB0764263 (0xFB07)HRInverter series typeU16R03
224 for VF-S15
p.70
FC9064656 (0xFC90)HRTrip code (current)U16R03
See the table on p.63 for the other codes
0 = No error (nerr) · 1 = Over-current during acceleration (oc1) · 2 = Over-current during deceleration (oc2) · 3 = Over-current at constant speed (oc3)
p.63, p.70
FC9164657 (0xFC91)HRAlarm information 1U16R03
b0 Over-current alarm · b1 Inverter overload alarm · b2 Motor overload alarm · b3 Overheat alarm · b4 Overvoltage alarm · b5 Undervoltage alarm · b7 Low current alarm · b8 Over-torque alarm · b12 Serial communication alarm
p.61
FD0064768 (0xFD00)HROutput frequencyU16×0.01 HzR03
Read example 01 03 FD 00 00 01 → 17 70 = 60.00 Hz (p.26). Value just before a trip: FE00
p.56, p.70
FD0164769 (0xFD01)HRStatus information 1U16R03
b0 Failure FL (1 = output in progress) · b1 Failure (1 = tripped, incl. retry and trip retention) · b2 Alarm (1 = alarm issued) · b3 Main circuit undervoltage (1 = undervoltage) · b7 DC braking (1 = forced DC braking) · b8 Jog run · b9 Forward/reverse (0 forward, 1 reverse) · b10 Run/stop (1 = run) · b11 Coast stop (1 = ST=OFF) · b12 Emergency stop status · b13 Standby (incl. ST=ON and RUN=ON) · b14 Standby (initialised, not stopped by fault or alarm)
p.59
FD0264770 (0xFD02)HRFrequency command valueU16×0.01 HzR03
p.70
FD0364771 (0xFD03)HROutput current (% of rating)U16×0.01 %R03
p.56, p.70
FD0464772 (0xFD04)HRInput voltage (DC detection, % of rating)U16×0.01 %R03
p.56, p.70
FD0564773 (0xFD05)HROutput voltage (% of rating)U16×0.01 %R03
p.56, p.70
FD0664774 (0xFD06)HRInput terminal statusU16R03
b0 F terminal · b1 R terminal · b2 RES terminal · b3 S1 terminal · b4 S2 terminal · b5 S3 terminal
p.57
FD0764775 (0xFD07)HROutput terminal statusU16R03
b0 RY-RC · b1 OUT · b2 FL
p.58
FD2264802 (0xFD22)HRPID feedback valueU16×0.01 HzR03
p.70
FD2964809 (0xFD29)HRInput powerU16×0.01 kWR03
p.70
FD3064816 (0xFD30)HROutput powerU16×0.01 kWR03
p.70
FD4564837 (0xFD45)HROperating command mode statusU16R03
0 = Terminal block · 1 = Panel keypad · 2 = RS485 communication · 3 = CANopen communication · 4 = Communication option
p.62
FD9064912 (0xFD90)HROutput motor speedU16min-1R03
Number of poles from f856
p.61, p.71
FE1065040 (0xFE10)HRPast trip 1 (latest)U16R03
p.70
FE1465044 (0xFE14)HRCumulative operation timeU16hR03
p.70
FE3565077 (0xFE35)HRTerminal VIA inputU16×0.01 %R03
Range 0 ~ 100 %
p.58
FE3665078 (0xFE36)HRTerminal VIB inputS16×0.01 %R03
Range -100 ~ 100 %
p.58
FE7065136 (0xFE70)HRRated currentU16×0.1 AR03
p.71
FE7165137 (0xFE71)HRRated voltageU16×0.1 VR03
p.71

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).