An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 19200 bps — options: 9600, 19200, 38400 |
| Data · parity · stop | 8 · Even · 1 |
| Max per request | 8 registers |
| Manual address style | Wire address as is (0-based) |
- Addressing: the communication number (hex, e.g. FD00, FA01) is the frame address — read example 01 03 FD 00 00 01 (output frequency, p.26), write example 01 06 FA 01 17 70 (60 Hz, p.31). Parameters use the same hex number, e.g. 0800 (f800).
- Factory protocol is the Toshiba protocol (f829 = 0); set f829 = 1 and reset for Modbus. Defaults 19200 bps (f800 = 4), even parity (f801 = 1), inverter number 0 (f802) (p.4, p.24, p.47). The inverter receives 1 stop bit and sends 2 (p.4).
- FC 03 (normally 1 word; 'direct block read' 2-8 words), 06, 10 (1 word), 17 and 2B (p.25, p.29, p.32). Communication numbers xxxA-xxxF and xxAx-xxFx do not exist and are skipped in block reads, e.g. 0009h is followed by 0010h (p.29, p.68). Missing numbers return 8000h.
Registers (32)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 0800 (f800) | 2048 (0x0800) | HR | Baud rate | U16 | R/W | 03·06·10 | Takes effect after reset or power cycle 3 = 9600 bps · 4 = 19200 bps (default) · 5 = 38400 bps p.47 | |
| 0801 (f801) | 2049 (0x0801) | HR | Parity | U16 | R/W | 03·06·10 | 0 = None · 1 = Even (default) · 2 = Odd p.47 | |
| 0802 (f802) | 2050 (0x0802) | HR | Inverter number (slave ID) | U16 | R/W | 03·06·10 | Default 0. In Modbus 0 is broadcast, so set 1-247 Range 0 ~ 247 p.47, p.49 | |
| 0803 (f803) | 2051 (0x0803) | HR | Communication time-out time | U16 | ×0.1 s | R/W | 03·06·10 | 0.0 = disabled (default) Range 0 ~ 100 s p.47 |
| 0804 (f804) | 2052 (0x0804) | HR | Communication time-out action | U16 | R/W | 03·06·10 | 0 = Alarm only (default) · 1 = Trip (coast stop) · 2 = Trip (deceleration stop) p.47 | |
| 0829 (f829) | 2089 (0x0829) | HR | Communication protocol | U16 | R/W | 03·06·10 | Takes effect after reset 0 = Toshiba inverter protocol (default) · 1 = Modbus RTU p.47, p.24 | |
| FA00 | 64000 (0xFA00) | HR | Communication command 1 | U16 | W | 06·10 | E.g. 8400h = command priority + run (forward), C400h also enables frequency priority. Stored in RAM only b7 DC braking (1 = forced DC braking) · b8 Jog run · b9 Forward/reverse (0 forward, 1 reverse) · b10 Run/stop (1 = run) · b11 Coast stop command (1 = coast stop) · b12 Emergency stop (always enabled, 'E' trip) · b13 Fault reset (the inverter returns no reply) · b14 Frequency priority (1 = communication frequency enabled regardless of fmod) · b15 Command priority (1 = communication commands enabled regardless of cmod) p.52 Table 1, p.69 | |
| FA01 | 64001 (0xFA01) | HR | Frequency command (communication) | U16 | ×0.01 Hz | W | 06·10 | 0 to maximum frequency (fh). Write example 01 06 FA 01 17 70 = 60.00 Hz (p.31) p.54, p.69 |
| FA13 | 64019 (0xFA13) | HR | Motor speed command | U16 | min-1 | W | 06·10 | Range 0 ~ 24000 min-1 p.54, p.69 |
| FA50 | 64080 (0xFA50) | HR | Terminal board output data | U16 | W | 06·10 | b0 Specified data output 1 (output function 92/93) · b1 Specified data output 2 (output function 94/95) p.55 | |
| FB07 | 64263 (0xFB07) | HR | Inverter series type | U16 | R | 03 | 224 for VF-S15 p.70 | |
| FC90 | 64656 (0xFC90) | HR | Trip code (current) | U16 | R | 03 | See the table on p.63 for the other codes 0 = No error (nerr) · 1 = Over-current during acceleration (oc1) · 2 = Over-current during deceleration (oc2) · 3 = Over-current at constant speed (oc3) p.63, p.70 | |
| FC91 | 64657 (0xFC91) | HR | Alarm information 1 | U16 | R | 03 | b0 Over-current alarm · b1 Inverter overload alarm · b2 Motor overload alarm · b3 Overheat alarm · b4 Overvoltage alarm · b5 Undervoltage alarm · b7 Low current alarm · b8 Over-torque alarm · b12 Serial communication alarm p.61 | |
| FD00 | 64768 (0xFD00) | HR | Output frequency | U16 | ×0.01 Hz | R | 03 | Read example 01 03 FD 00 00 01 → 17 70 = 60.00 Hz (p.26). Value just before a trip: FE00 p.56, p.70 |
| FD01 | 64769 (0xFD01) | HR | Status information 1 | U16 | R | 03 | b0 Failure FL (1 = output in progress) · b1 Failure (1 = tripped, incl. retry and trip retention) · b2 Alarm (1 = alarm issued) · b3 Main circuit undervoltage (1 = undervoltage) · b7 DC braking (1 = forced DC braking) · b8 Jog run · b9 Forward/reverse (0 forward, 1 reverse) · b10 Run/stop (1 = run) · b11 Coast stop (1 = ST=OFF) · b12 Emergency stop status · b13 Standby (incl. ST=ON and RUN=ON) · b14 Standby (initialised, not stopped by fault or alarm) p.59 | |
| FD02 | 64770 (0xFD02) | HR | Frequency command value | U16 | ×0.01 Hz | R | 03 | p.70 |
| FD03 | 64771 (0xFD03) | HR | Output current (% of rating) | U16 | ×0.01 % | R | 03 | p.56, p.70 |
| FD04 | 64772 (0xFD04) | HR | Input voltage (DC detection, % of rating) | U16 | ×0.01 % | R | 03 | p.56, p.70 |
| FD05 | 64773 (0xFD05) | HR | Output voltage (% of rating) | U16 | ×0.01 % | R | 03 | p.56, p.70 |
| FD06 | 64774 (0xFD06) | HR | Input terminal status | U16 | R | 03 | b0 F terminal · b1 R terminal · b2 RES terminal · b3 S1 terminal · b4 S2 terminal · b5 S3 terminal p.57 | |
| FD07 | 64775 (0xFD07) | HR | Output terminal status | U16 | R | 03 | b0 RY-RC · b1 OUT · b2 FL p.58 | |
| FD22 | 64802 (0xFD22) | HR | PID feedback value | U16 | ×0.01 Hz | R | 03 | p.70 |
| FD29 | 64809 (0xFD29) | HR | Input power | U16 | ×0.01 kW | R | 03 | p.70 |
| FD30 | 64816 (0xFD30) | HR | Output power | U16 | ×0.01 kW | R | 03 | p.70 |
| FD45 | 64837 (0xFD45) | HR | Operating command mode status | U16 | R | 03 | 0 = Terminal block · 1 = Panel keypad · 2 = RS485 communication · 3 = CANopen communication · 4 = Communication option p.62 | |
| FD90 | 64912 (0xFD90) | HR | Output motor speed | U16 | min-1 | R | 03 | Number of poles from f856 p.61, p.71 |
| FE10 | 65040 (0xFE10) | HR | Past trip 1 (latest) | U16 | R | 03 | p.70 | |
| FE14 | 65044 (0xFE14) | HR | Cumulative operation time | U16 | h | R | 03 | p.70 |
| FE35 | 65077 (0xFE35) | HR | Terminal VIA input | U16 | ×0.01 % | R | 03 | Range 0 ~ 100 % p.58 |
| FE36 | 65078 (0xFE36) | HR | Terminal VIB input | S16 | ×0.01 % | R | 03 | Range -100 ~ 100 % p.58 |
| FE70 | 65136 (0xFE70) | HR | Rated current | U16 | ×0.1 A | R | 03 | p.71 |
| FE71 | 65137 (0xFE71) | HR | Rated voltage | U16 | ×0.1 V | R | 03 | p.71 |
Notes
- No communication for about 1 s after power-on (p.24). Do not write the same EEPROM parameter more than 10,000 times (p.31).
- Printed page = PDF page − 1.
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- toshiba/vf-s15.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- TOSVERT VF-S15 Series RS485 Communication Function Instruction Manual — Toshiba, E6581913 (PDF created 2019-04, modified 2022-04) · 2 transmission specs printed p.4, 5 Modbus RTU pp.24-32, 7 communication parameters p.47, 8 commands and monitoring pp.52-63, 9 parameter data pp.68-71 · checked 2026-11-01