Power, RS-485, RS-232, 4–20 mA, thermocouple, Ethernet, servo, cable chain: cable type and conditions by use, wire size from voltage drop, length checks.

Calculation

Ampacity is not calculated — it varies widely with installation method, ambient temperature and grouping. Check it separately in IEC 60364-5-52 Annex B, your local code (NEC, …) or the cable maker's data. Have a qualified person confirm the design.

Results update as you type. Everything runs in your browser; nothing you type is sent anywhere.

AC power (single- or three-phase)

Recommended cable

  • Single-phase: L, N, PE (3 cores). Three-phase: L1, L2, L3 (and N) plus PE in the same cable.
  • The size must satisfy both: (1) current-carrying capacity (installation method, ambient temperature, grouping) and (2) voltage drop. This tool calculates (2) only.
  • For drive (VFD) outputs, follow the maker's recommended shielded motor cable and grounding.

What to check when choosing and laying

  • Take IZ from Annex B of IEC 60364-5-52 (KEC 232.5.2 in Korea) and coordinate with protection so that IB ≤ In ≤ IZ.
  • Maximum conductor temperature: PVC 70 °C, XLPE/EPR 90 °C — the same size carries different current.
  • Keep apart from communication and analog cables; cross at right angles.

Sources

  • KEC 212.4.1, 232.5 / IEC 60364-5-52 Annex B (ampacity — values from the original)
  • Voltage drop: IEC 60028 copper resistivity 1/58 Ω·mm²/m

See also

24 V DC power and control

Recommended cable

  • Run +24 V and 0 V in the same size — the drop happens in both conductors.
  • For remote sensors, valves and devices, voltage drop usually decides the size. Compare the voltage at the load with the device's minimum input voltage.
  • Control signals (contacts, NPN/PNP): multi-core control cable, shielded where noise is high.

What to check when choosing and laying

  • Loads with high inrush (solenoids, motor brakes) drop more at switch-on.
  • Raising the supply output to cover the drop only works within the devices' maximum input voltage.

Sources

  • Voltage drop: IEC 60028 resistivity, IEC 60228 nominal sizes

See also

RS-485 / RS-422 communication

Recommended cable

  • Twisted pair with an overall shield. 2-wire RS-485: one pair (A, B) plus a signal ground (SG) wire; 4-wire and RS-422: two pairs plus SG.
  • Use a cable rated for RS-485 with a stated characteristic impedance (commonly 120 Ω) and match the end terminations to it.
  • Modbus serial spec: AWG 26 or thicker, up to 1000 m at 9600 bps, stubs 20 m or less.

What to check when choosing and laying

  • Daisy chain — avoid star wiring and long stubs.
  • Distance and speed trade off: roughly bps × m ≤ 10⁸, at most about 1200 m.
  • Ground the shield (one end or both) as the device or bus installation guide says.

Sources

  • MODBUS over serial line V1.02 §3.4
  • TI SLLA070D — 1200 m, bps × m ≤ 10⁸

See also

RS-232 communication

Recommended cable

  • Keep it short — the spec limits line capacitance (under 2500 pF), not length. About 15 to 20 m with ordinary cable.
  • At least TX, RX and SG (GND); more (RTS, CTS, …) with hardware flow control. Shielded multi-core cable.
  • If both ends are DTE, use a crossover (null-modem) cable.

What to check when choosing and laying

  • For longer runs: low-capacitance cable, lower baud rate, or an RS-485/422 converter.
  • From the datasheet pF/m: rough length = 2500 pF ÷ pF/m (an upper value; device input capacitance not subtracted).

Sources

  • TI SLLA067C §2.13 — TIA-232 2500 pF, about 20 m

See also

4–20 mA and 0–10 V analog

Recommended cable

  • Shielded twisted pair — each signal pair twisted, overall or individual shields.
  • In a 4–20 mA loop the cable resistance eats supply voltage. For long runs, check the transmitter terminal voltage with a loop load calculation.
  • 0–10 V voltage signals are more sensitive to resistance and noise; keep them short.

What to check when choosing and laying

  • The shield is usually grounded at one end (the receiving end) — follow the device guide if it says otherwise.
  • Do not share a duct with power or drive output cables.

Sources

  • General practice — the loop calculation is Ohm's law

See also

Thermocouples and RTDs (Pt100)

Recommended cable

  • Thermocouple: extension (X) or compensating (C) cable of the same type — e.g. KX or KCA/KCB for type K. Copper wire in between creates new junctions and error.
  • IEC 60584-3 colours: + core in the type colour (K green, J black, T brown, E violet, N pink, R/S orange), − core white. Older and other national codes differ.
  • RTD (Pt100): for 3-wire use the same length and size on all three wires (so lead resistance cancels); 4-wire for precision. Shielded cable.

What to check when choosing and laying

  • Reversed polarity reads down as it heats (including the compensating cable).
  • Compensating cables have a limited temperature range — use extension cable and heat-resistant insulation in hot zones.

Sources

  • IEC 60584-3 extension and compensating cables, colours

See also

Ethernet (Modbus TCP, cameras, …)

Recommended cable

  • 100 Mbps and 1 Gbps: Cat5e or better; 10 Gbps: Cat6A (Cat6 only for short runs).
  • One copper channel is 100 m — 90 m fixed cabling plus 10 m of patch cords.
  • Factory floor (noise, oil, movement): shielded (S/FTP, SF/UTP) industrial cable, M12 D-coded (100 Mbps) or X-coded (1/10 Gbps) connectors.

What to check when choosing and laying

  • Beyond 100 m add a switch or go to fibre.
  • Use one wiring scheme (T568A or B) for the whole site.
  • Industrial Ethernet fieldbuses (PROFINET, …) have their own cable guidelines.

Sources

  • ANSI/TIA-568 channel 100 m (90 + 10)
  • IEEE 802.3 — 1000BASE-T (Cat5e), 10GBASE-T (Cat6A 100 m)

See also

Encoders and servo motors

Recommended cable

  • Use the maker's dedicated servo power and encoder cables (or cables to the maker's spec) — shielding, pairing and maximum length are matched to the drive.
  • Incremental encoders (line driver A/A̅, B/B̅, Z/Z̅): individually twisted pairs plus shield. Open-collector outputs: keep short.

What to check when choosing and laying

  • Maximum length and encoder supply drop: from the drive manual.
  • Run power and encoder cables apart; terminate the shield as the manual shows.

Sources

  • General practice — lengths and specs from the drive and motor manuals

See also

Moving parts (cable chains, robots)

Recommended cable

  • For continuous flexing use cables rated for cable chains (high-flex) — fine stranding, lay and jacket designed for bending.
  • The minimum bending radius is given in the maker's catalogue as a multiple of the outer diameter — make sure the chain radius is at least that.
  • For torsion (robot axes) use cables with a torsion rating.

What to check when choosing and laying

  • Use separators and clearance so cables do not twist together; spread heavy cables evenly to the outside.
  • Flex life, acceleration and travel: from the maker's data.

Sources

  • General practice — bending radius and life from cable and chain makers

See also

What this does not cover

  • Ampacity and protective device coordination: the other half of cable sizing. This tool calculates voltage drop only.
  • Short-circuit withstand, protective earth (PE) size, earthing systems: follow your local code (IEC 60364, NEC, …).
  • Cable specs for a particular device: the device or drive manual overrides the general rules here.

To convert AWG and mm², use the AWG to mm² table; for how many wires fit in a conduit or duct, the conduit and duct fill calculator; for a detailed voltage drop, the voltage drop calculator.

FAQ

Can I use LAN cable (UTP) for RS-485?

It is twisted pair, so it often works over short runs, but LAN cable is 100 Ω and often unshielded. For long or noisy runs, use shielded twisted-pair cable made for RS-485 and match the terminations to it.

How do I size a 24 V sensor supply cable?

Enter current, one-way length and allowed drop for the minimum cross-section and the next IEC size. Example: 2 A, 50 m, 5 % needs about 2.87 mm² → 4 mm². Also check the voltage at the load against the device's minimum input voltage.

How far can RS-232 go?

The spec (TIA-232) limits line capacitance to under 2500 pF, not length. With ordinary cable that is about 15 to 20 m; low-capacitance cable goes further. Beyond that, converting to RS-485/422 is the sure way.