AWG to mm² Conversion Table
AWG 0000 to 40 diameter and area (ASTM B258 formula), nearest metric mm² size (IEC 60228) and copper Ω/km at 20 °C. Convert either way.
Formulas
- Diameter d = 0.127 mm × 92^((36 − n) ÷ 39) (n: AWG number; 0 = 0, 00 = −1, 000 = −2, 0000 = −3)
- Area A = π ÷ 4 × d²
- Resistance R (Ω/km) = ρ × 1000 ÷ A, ρ = 1/58 ≈ 0.017241 Ω·mm²/m (copper, 20 °C)
The AWG formula is from ASTM B258; copper resistivity is the IEC 60028 annealed copper value. Every 6 gauges the diameter doubles; every 3 gauges the area roughly doubles.
AWG table (0000 to 40)
| AWG | Diameter mm | Area mm² | Ω/km (copper 20 °C) | Nearest mm² (difference) |
|---|---|---|---|---|
| 4/0 (0000) AWG | 11.684 | 107.2 | 0.161 | 120 (+12 %) |
| 3/0 (000) AWG | 10.405 | 85.03 | 0.203 | 95 (+12 %) |
| 2/0 (00) AWG | 9.266 | 67.43 | 0.256 | 70 (+4 %) |
| 1/0 (0) AWG | 8.251 | 53.48 | 0.322 | 50 (−6 %) |
| 1 AWG | 7.348 | 42.41 | 0.407 | 50 (+18 %) |
| 2 AWG | 6.544 | 33.63 | 0.513 | 35 (+4 %) |
| 3 AWG | 5.827 | 26.67 | 0.646 | 25 (−6 %) |
| 4 AWG | 5.189 | 21.15 | 0.815 | 25 (+18 %) |
| 5 AWG | 4.621 | 16.77 | 1.028 | 16 (−5 %) |
| 6 AWG | 4.115 | 13.30 | 1.296 | 16 (+20 %) |
| 7 AWG | 3.665 | 10.55 | 1.634 | 10 (−5 %) |
| 8 AWG | 3.264 | 8.366 | 2.061 | 10 (+20 %) |
| 9 AWG | 2.906 | 6.634 | 2.599 | 6 (−10 %) |
| 10 AWG | 2.588 | 5.261 | 3.277 | 6 (+14 %) |
| 11 AWG | 2.305 | 4.172 | 4.132 | 4 (−4 %) |
| 12 AWG | 2.053 | 3.309 | 5.211 | 4 (+21 %) |
| 13 AWG | 1.828 | 2.624 | 6.571 | 2.5 (−5 %) |
| 14 AWG | 1.628 | 2.081 | 8.286 | 2.5 (+20 %) |
| 15 AWG | 1.450 | 1.650 | 10.45 | 1.5 (−9 %) |
| 16 AWG | 1.291 | 1.309 | 13.17 | 1.5 (+15 %) |
| 17 AWG | 1.150 | 1.038 | 16.61 | 1 (−4 %) |
| 18 AWG | 1.024 | 0.823 | 20.95 | 0.75 (−9 %) |
| 19 AWG | 0.912 | 0.653 | 26.42 | 0.75 (+15 %) |
| 20 AWG | 0.812 | 0.518 | 33.31 | 0.5 (−3 %) |
| 21 AWG | 0.723 | 0.410 | 42.00 | 0.5 (+22 %) |
| 22 AWG | 0.644 | 0.326 | 52.96 | 0.5 (+54 %) |
| 23 AWG | 0.573 | 0.258 | 66.79 | 0.5 (+94 %) |
| 24 AWG | 0.511 | 0.205 | 84.22 | 0.5 (+144 %) |
| 25 AWG | 0.455 | 0.162 | 106.2 | 0.5 (+208 %) |
| 26 AWG | 0.405 | 0.129 | 133.9 | 0.5 (+288 %) |
| 27 AWG | 0.361 | 0.102 | 168.9 | 0.5 (+390 %) |
| 28 AWG | 0.321 | 0.0810 | 212.9 | 0.5 (+517 %) |
| 29 AWG | 0.286 | 0.0642 | 268.5 | 0.5 (+679 %) |
| 30 AWG | 0.255 | 0.0509 | 338.6 | 0.5 (+882 %) |
| 31 AWG | 0.227 | 0.0404 | 426.9 | 0.5 (+1138 %) |
| 32 AWG | 0.202 | 0.0320 | 538.3 | 0.5 (+1461 %) |
| 33 AWG | 0.180 | 0.0254 | 678.8 | 0.5 (+1869 %) |
| 34 AWG | 0.160 | 0.0201 | 856.0 | 0.5 (+2382 %) |
| 35 AWG | 0.143 | 0.0160 | 1079.4 | 0.5 (+3030 %) |
| 36 AWG | 0.127 | 0.0127 | 1361.1 | 0.5 (+3847 %) |
| 37 AWG | 0.113 | 0.0100 | 1716.3 | 0.5 (+4877 %) |
| 38 AWG | 0.101 | 0.0080 | 2164.2 | 0.5 (+6176 %) |
| 39 AWG | 0.090 | 0.0063 | 2729.0 | 0.5 (+7814 %) |
| 40 AWG | 0.080 | 0.0050 | 3441.1 | 0.5 (+9879 %) |
Metric sizes (IEC 60228)
| Area mm² | Diameter mm (solid equiv.) | Ω/km (copper 20 °C) | Nearest AWG | Equal or larger AWG |
|---|---|---|---|---|
| 0.5 | 0.80 | 34.48 | 20 AWG | 20 AWG |
| 0.75 | 0.98 | 22.99 | 18 AWG | 18 AWG |
| 1 | 1.13 | 17.24 | 17 AWG | 17 AWG |
| 1.5 | 1.38 | 11.49 | 15 AWG | 15 AWG |
| 2.5 | 1.78 | 6.897 | 13 AWG | 13 AWG |
| 4 | 2.26 | 4.310 | 11 AWG | 11 AWG |
| 6 | 2.76 | 2.874 | 9 AWG | 9 AWG |
| 10 | 3.57 | 1.724 | 7 AWG | 7 AWG |
| 16 | 4.51 | 1.078 | 5 AWG | 5 AWG |
| 25 | 5.64 | 0.690 | 3 AWG | 3 AWG |
| 35 | 6.68 | 0.493 | 2 AWG | 1 AWG |
| 50 | 7.98 | 0.345 | 1/0 (0) AWG | 1/0 (0) AWG |
| 70 | 9.44 | 0.246 | 2/0 (00) AWG | 3/0 (000) AWG |
| 95 | 11.00 | 0.181 | 3/0 (000) AWG | 4/0 (0000) AWG |
| 120 | 12.36 | 0.144 | 4/0 (0000) AWG | — |
| 150 | 13.82 | 0.115 | — | — |
| 185 | 15.35 | 0.0932 | — | — |
| 240 | 17.48 | 0.0718 | — | — |
| 300 | 19.54 | 0.0575 | — | — |
Reading the table
- AWG and metric sizes never match exactly. «Nearest» is by area ratio; a negative difference means the metric size is smaller — when ampacity or voltage drop is tight, pick the equal-or-larger size.
- Diameters are for a solid conductor. Stranded wire of the same area is wider, and insulation adds more — use the maker's overall diameter for conduit and duct fill.
- Real cable resistance: IEC 60228 sets maximum values per conductor class (solid, stranded, flexible); stranded and tinned conductors are slightly higher.
- Ampacity does not follow from size alone (installation method, ambient temperature, grouping) and is not listed here.
FAQ
How many mm² is 18 AWG?
About 0.823 mm² (1.024 mm diameter). The nearest metric size is 0.75 mm², slightly smaller. 16 AWG is about 1.31 mm², 14 AWG about 2.08 mm², 12 AWG about 3.31 mm².
What AWG is 1.5 mm²?
15 AWG (1.65 mm²) is nearest, but 15 AWG is uncommon, so the usual US-gauge substitute is 14 AWG (2.08 mm²). 16 AWG (1.31 mm²) is smaller than 1.5 mm².
What do 4/0 and 2/0 mean?
Gauges larger than 0 repeat the zero: 1/0 = 0, 2/0 = 00, 3/0 = 000, 4/0 = 0000. 4/0 AWG is about 107 mm².
To size a wire from length and current, use the voltage drop calculator; for cable types by use, the cable selection helper; for how many wires fit in a conduit, the conduit and duct fill calculator.