PortDock

AWG to mm² Conversion Table

AWG 0000 to 40 diameter and area (ASTM B258 formula), nearest metric mm² size (IEC 60228) and copper Ω/km at 20 °C. Convert either way.

Result
Diameter (solid equivalent)
Cross-section
Copper resistance at 20 °C (one conductor)
Nearest metric size
Nearest AWG
AWG of equal or larger area

Results update as you type. Everything runs in your browser; nothing you type is sent anywhere.

Formulas

  • Diameter d = 0.127 mm × 92^((36 − n) ÷ 39) (n: AWG number; 0 = 0, 00 = −1, 000 = −2, 0000 = −3)
  • Area A = π ÷ 4 × d²
  • Resistance R (Ω/km) = ρ × 1000 ÷ A, ρ = 1/58 ≈ 0.017241 Ω·mm²/m (copper, 20 °C)

The AWG formula is from ASTM B258; copper resistivity is the IEC 60028 annealed copper value. Every 6 gauges the diameter doubles; every 3 gauges the area roughly doubles.

AWG table (0000 to 40)

AWGDiameter mmArea mm²Ω/km (copper 20 °C)Nearest mm² (difference)
4/0 (0000) AWG11.684107.20.161120 (+12 %)
3/0 (000) AWG10.40585.030.20395 (+12 %)
2/0 (00) AWG9.26667.430.25670 (+4 %)
1/0 (0) AWG8.25153.480.32250 (−6 %)
1 AWG7.34842.410.40750 (+18 %)
2 AWG6.54433.630.51335 (+4 %)
3 AWG5.82726.670.64625 (−6 %)
4 AWG5.18921.150.81525 (+18 %)
5 AWG4.62116.771.02816 (−5 %)
6 AWG4.11513.301.29616 (+20 %)
7 AWG3.66510.551.63410 (−5 %)
8 AWG3.2648.3662.06110 (+20 %)
9 AWG2.9066.6342.5996 (−10 %)
10 AWG2.5885.2613.2776 (+14 %)
11 AWG2.3054.1724.1324 (−4 %)
12 AWG2.0533.3095.2114 (+21 %)
13 AWG1.8282.6246.5712.5 (−5 %)
14 AWG1.6282.0818.2862.5 (+20 %)
15 AWG1.4501.65010.451.5 (−9 %)
16 AWG1.2911.30913.171.5 (+15 %)
17 AWG1.1501.03816.611 (−4 %)
18 AWG1.0240.82320.950.75 (−9 %)
19 AWG0.9120.65326.420.75 (+15 %)
20 AWG0.8120.51833.310.5 (−3 %)
21 AWG0.7230.41042.000.5 (+22 %)
22 AWG0.6440.32652.960.5 (+54 %)
23 AWG0.5730.25866.790.5 (+94 %)
24 AWG0.5110.20584.220.5 (+144 %)
25 AWG0.4550.162106.20.5 (+208 %)
26 AWG0.4050.129133.90.5 (+288 %)
27 AWG0.3610.102168.90.5 (+390 %)
28 AWG0.3210.0810212.90.5 (+517 %)
29 AWG0.2860.0642268.50.5 (+679 %)
30 AWG0.2550.0509338.60.5 (+882 %)
31 AWG0.2270.0404426.90.5 (+1138 %)
32 AWG0.2020.0320538.30.5 (+1461 %)
33 AWG0.1800.0254678.80.5 (+1869 %)
34 AWG0.1600.0201856.00.5 (+2382 %)
35 AWG0.1430.01601079.40.5 (+3030 %)
36 AWG0.1270.01271361.10.5 (+3847 %)
37 AWG0.1130.01001716.30.5 (+4877 %)
38 AWG0.1010.00802164.20.5 (+6176 %)
39 AWG0.0900.00632729.00.5 (+7814 %)
40 AWG0.0800.00503441.10.5 (+9879 %)

Metric sizes (IEC 60228)

Area mm²Diameter mm (solid equiv.)Ω/km (copper 20 °C)Nearest AWGEqual or larger AWG
0.50.8034.4820 AWG20 AWG
0.750.9822.9918 AWG18 AWG
11.1317.2417 AWG17 AWG
1.51.3811.4915 AWG15 AWG
2.51.786.89713 AWG13 AWG
42.264.31011 AWG11 AWG
62.762.8749 AWG9 AWG
103.571.7247 AWG7 AWG
164.511.0785 AWG5 AWG
255.640.6903 AWG3 AWG
356.680.4932 AWG1 AWG
507.980.3451/0 (0) AWG1/0 (0) AWG
709.440.2462/0 (00) AWG3/0 (000) AWG
9511.000.1813/0 (000) AWG4/0 (0000) AWG
12012.360.1444/0 (0000) AWG—
15013.820.115——
18515.350.0932——
24017.480.0718——
30019.540.0575——

Reading the table

  • AWG and metric sizes never match exactly. «Nearest» is by area ratio; a negative difference means the metric size is smaller — when ampacity or voltage drop is tight, pick the equal-or-larger size.
  • Diameters are for a solid conductor. Stranded wire of the same area is wider, and insulation adds more — use the maker's overall diameter for conduit and duct fill.
  • Real cable resistance: IEC 60228 sets maximum values per conductor class (solid, stranded, flexible); stranded and tinned conductors are slightly higher.
  • Ampacity does not follow from size alone (installation method, ambient temperature, grouping) and is not listed here.

FAQ

How many mm² is 18 AWG?

About 0.823 mm² (1.024 mm diameter). The nearest metric size is 0.75 mm², slightly smaller. 16 AWG is about 1.31 mm², 14 AWG about 2.08 mm², 12 AWG about 3.31 mm².

What AWG is 1.5 mm²?

15 AWG (1.65 mm²) is nearest, but 15 AWG is uncommon, so the usual US-gauge substitute is 14 AWG (2.08 mm²). 16 AWG (1.31 mm²) is smaller than 1.5 mm².

What do 4/0 and 2/0 mean?

Gauges larger than 0 repeat the zero: 1/0 = 0, 2/0 = 00, 3/0 = 000, 4/0 = 0000. 4/0 AWG is about 107 mm².

To size a wire from length and current, use the voltage drop calculator; for cable types by use, the cable selection helper; for how many wires fit in a conduit, the conduit and duct fill calculator.