LS ELECTRIC LSLV-S100 Modbus register map

Built-in RS-485 Modbus-RTU. Compatible common area (0h0000-) and S100 expansion common area (0h0300-) · Inverter (VFD) · S100

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)9600 bps — options: 1200, 2400, 4800, 9600, 19200, 38400, 115200
Data · parity · stop8 · None · 1
Slave ID (factory)1 (1~250)
Manual address style1-based numbers (wire address + 1)

Registers (36)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
0h00010 (0x0000)HRInverter capacityU16R03·04
0 = 0.75kW · 1 = 1.5kW · 2 = 2.2kW · 3 = 3.7kW · 4 = 5.5kW · 5 = 7.5kW · 6 = 11kW · 7 = 15kW · 8 = 18.5kW · 9 = 22kW · 10 = 30kW · 11 = 37kW · 12 = 45kW · 13 = 55kW · 14 = 75kW · 256 = 0.4kW · 257 = 1.1kW · 258 = 3.0kW · 259 = 4.0kW
p.296 (PDF 310)
0h00021 (0x0001)HRInput voltage classU16R03·04
0 = 220V product · 1 = 440V product
p.296 (PDF 310)
0h00032 (0x0002)HRS/W versionU16R03·04
Hex: 0x0100 = version 1.00
p.296 (PDF 310)
0h00054 (0x0004)HRFrequency commandU16×0.01 HzR/W03·04·06·10
p.296 (PDF 310)
0h00065 (0x0005)HROperation commandU16R/W03·04·06·10
B5-B15 read-only: B6-B8 run command source (0 keypad, 1 Fx/Rx-1, 2 Fx/Rx-2, 3 built-in 485, 4 comm option), B9-B14 frequency source (0 keypad freq, 1 keypad torque, 2-16 multi-step, 17 up, 18 down, 19 steady, 22 V1, 24 V2, 25 I2, 27 built-in 485, 28 comm option, 30 jog, 31 PID)
b0 Stop (S) · b1 Forward run (F) · b2 Reverse run (R) · b3 W: trip reset (0->1) / R: trip status · b4 Emergency stop
p.296 (PDF 310)
0h00076 (0x0006)HRAcceleration timeU16×0.1 sR/W03·04·06·10
p.296 (PDF 310)
0h00087 (0x0007)HRDeceleration timeU16×0.1 sR/W03·04·06·10
p.296 (PDF 310)
0h00098 (0x0008)HROutput currentU16×0.1 AR03·04
p.297 (PDF 311)
0h000A9 (0x0009)HROutput frequencyU16×0.01 HzR03·04
p.297 (PDF 311)
0h000B10 (0x000A)HROutput voltageU16VR03·04
p.297 (PDF 311)
0h000C11 (0x000B)HRDC link voltageU16VR03·04
p.297 (PDF 311)
0h000D12 (0x000C)HROutput powerU16×0.1 kWR03·04
p.297 (PDF 311)
0h000E13 (0x000D)HROperation statusU16R03·04
b0 Stopped · b1 Running forward · b2 Running reverse · b3 Fault trip · b4 Accelerating · b5 Decelerating · b6 Speed reached · b7 DC braking · b8 Drive stopping · b9 Jog mode · b10 Brake release signal · b11 Forward run command · b12 Reverse run command · b13 Run command source is communication · b14 Frequency command source is communication
p.297 (PDF 311)
0h000F14 (0x000E)HRFault trip informationU16R03·04
b0 Latch type trip · b3 Level type trip · b10 H/W diagnosis trip
p.297 (PDF 311)
0h001015 (0x000F)HRInput terminal statusU16R03·04
b0 P1 · b1 P2 · b2 P3 · b3 P4 · b4 P5 · b5 P6 · b6 P7
p.298 (PDF 312)
0h001116 (0x0010)HROutput terminal statusU16R03·04
b0 Relay 1 · b1 Q1
p.298 (PDF 312)
0h0301768 (0x0300)HRInverter capacity (ext.)U16R03·04
6400 = 0.4kW · 12800 = 0.75kW · 16401 = 1.1kW · 16405 = 1.5kW · 16418 = 2.2kW · 16432 = 3.0kW · 16439 = 3.7kW · 16448 = 4.0kW · 16469 = 5.5kW · 16501 = 7.5kW · 16560 = 11kW · 16624 = 15kW · 16677 = 18.5kW · 16736 = 22kW · 16864 = 30kW · 16976 = 37kW · 17104 = 45kW · 17264 = 55kW · 17584 = 75kW
p.299 (PDF 313)
0h0305772 (0x0304)HRInverter operation stateU16R03·04
B15-B12: 0 normal, 4 warning, 8 fault / B7-B4: 1 speed search, 2 accel, 3 steady, 4 decel, 5 decel to stop, 6 H/W OCS, 7 S/W OCS, 8 dwell / B3-B0: 0 stop, 1 forward, 2 reverse, 3 DC operation
p.299 (PDF 313)
0h0306773 (0x0305)HRRun / frequency command sourceU16R03·04
B15-B8 run source: 0 keypad, 1 comm option, 2 user sequence, 3 built-in 485, 4 terminal / B7-B0 freq source: 0 keypad speed, 1 keypad torque, 2-4 up/down, 5 V1, 7 V2, 8 I2, 9 pulse, 10 built-in 485, 11 comm option, 12 user sequence, 13 jog, 14 PID, 25-39 multi-step
p.300 (PDF 314)
0h0310783 (0x030F)HROutput currentU16×0.1 AR03·04
p.300 (PDF 314)
0h0311784 (0x0310)HROutput frequencyU16×0.01 HzR03·04
p.300 (PDF 314)
0h0314787 (0x0313)HROutput voltageU16VR03·04
p.300 (PDF 314)
0h0315788 (0x0314)HRDC link voltageU16VR03·04
p.300 (PDF 314)
0h0316789 (0x0315)HROutput powerU16×0.1 kWR03·04
p.300 (PDF 314)
0h0317790 (0x0316)HROutput torqueU16×0.1 %R03·04
p.300 (PDF 314)
0h032D812 (0x032C)HRInverter module temperatureU16℃R03·04
p.302 (PDF 316)
0h032E813 (0x032D)HREnergy consumption (kWh)U16×0.1 kWhR03·04
p.302 (PDF 316)
0h0330815 (0x032F)HRLatch type trip info 1U16R03·04
b0 Overload trip · b1 Underload trip · b2 Inverter overload trip · b3 E-Thermal trip · b4 Ground fault trip · b5 Output open-phase trip · b6 Input open-phase trip · b9 NTC trip · b10 Overcurrent trip · b11 Overvoltage trip · b12 External trip · b13 Arm short · b14 Over heat trip · b15 Fuse open trip
p.302 (PDF 316)
0h0331816 (0x0330)HRLatch type trip info 2U16R03·04
b2 Thermal trip · b3 Fan trip · b5 Error while writing parameter · b6 Pre PID fail · b7 Bad contact at basic I/O board · b8 External brake trip · b9 No motor trip · b10 Bad option card · b12 Safety A · b13 Safety B
p.302 (PDF 316)
0h0332817 (0x0331)HRLevel type trip infoU16R03·04
b0 BX · b1 Low voltage · b2 Lost command · b3 Keypad lost command · b6 Lost option command · b7 BLE app lost
p.303 (PDF 317)
0h0334819 (0x0333)HRWarning informationU16R03·04
b0 Overload · b1 Underload · b2 Inverter overload · b3 Lost command · b4 Fan running · b5 DB · b6 Wrong encoder installation · b7 Encoder disconnection · b8 Keypad lost · b9 Auto tuning failed · b10 Fan exchange · b11 Fire mode · b15 Comm idle status
p.303 (PDF 317)
0h0380895 (0x037F)HRFrequency command (ext.)U16×0.01 HzR/W03·04·06·10
p.304 (PDF 318)
0h0382897 (0x0381)HROperation command (ext.)U16R/W03·04·06·10
Forward run 0x0003, reverse run 0x0001
b0 0 stop / 1 run · b1 0 reverse / 1 forward · b2 Trip reset (0->1) · b3 Free-run stop (0->1)
p.304 (PDF 318)
0h0383898 (0x0382)HRAcceleration time (ext.)U16×0.1 sR/W03·04·06·10
p.304 (PDF 318)
0h0384899 (0x0383)HRDeceleration time (ext.)U16×0.1 sR/W03·04·06·10
p.304 (PDF 318)
0h03E0991 (0x03DF)HRSave parametersU16R/W03·04·06·10
Write 0 then 1 to save. Not changeable during run
0 = No · 1 = Yes
p.306 (PDF 320)

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.