PortDock

Choosing RS-485 termination and bias resistor values — 120 Ω, 560 Ω, 200 mV

Termination and bias (failsafe) resistor values from the Modbus rules (150 Ω, 450–650 Ω) and the 200 mV receiver threshold — stop garbage bytes between frames.

Tools for this guideSerial Windows program · freeModbus Master Windows program · freeRS-485 Termination & Bias Calculator web · no installSerial Timing Calculator web · no install

RS-485 wiring has two kinds of resistors. «Termination» at the two ends of the line reduces reflections; «bias» resistors at one place on the bus (pull-up and pull-down, also called failsafe) define the line state when nobody transmits. Both sit on the same pair and affect each other, so calculate them together.

Termination: at the two ends only

A terminator goes across A and B and should match the cable's characteristic impedance. TI notes that within ±20 % of the characteristic impedance is fine and typical values run from about 90 to 120 Ω. The Modbus specification gives a 150 Ω (0.5 W) resistor, or — when the line is biased — a 1 nF (10 V min) capacitor in series with 120 Ω (0.25 W) as the better choice. Either way, only near the two ends of the trunk, never on a stub.

Terminating at every device puts them in parallel and loads the driver. The standard RS-485 driver output test requires at least 1.5 V differential into 54 Ω; three 120 Ω terminators make 40 Ω, a heavier load and a smaller signal.

Biasing: why it is needed

On half-duplex RS-485, nobody drives the line while the master waits for a reply. With termination only, the A–B voltage then sits near 0, the receiver output is undefined, noise looks like a start bit and garbage bytes such as 00 or FF appear. Biasing pulls B (D1 in Modbus terms) up to 5 V and A (D0) down to common so that B − A is positive at idle — a «1» (mark).

RS-485 biasing: B (D1) pulled up to 5 V through 560 Ω and A (D0) pulled down to common through 560 Ω, with two 120 Ω end terminators across A–B carrying the bias current. Idle B − A = 5 V × 60 Ω ÷ 1180 Ω ≈ 254 mV
Bias current flows pull-up → terminators (in parallel) → pull-down; the voltage across the terminators is the idle differential voltage.

Calculating the bias value

Receivers produce a defined output for differential inputs of ±200 mV or more. The voltage the bias current develops across the parallel end terminators must exceed 200 mV.

Rline = terminators in parallel (two 120 Ω → 60 Ω)
Idle voltage = Vcc × Rline ÷ (Rpull-up + Rline + Rpull-down)
Example: 5 V × 60 ÷ (560 + 60 + 560) ≈ 254 mV
SupplyPull-up/downTermination (both ends)Idle voltage200 mV
5 V560 Ω150 Ω314 mVabove
5 V650 Ω150 Ω273 mVabove
5 V560 Ω120 Ω254 mVabove
5 V1 kΩ120 Ω146 mVbelow
3.3 V560 Ω120 Ω168 mVbelow
3.3 V390 Ω120 Ω236 mVabove

The Modbus specification puts biasing, if needed, at one place for the whole bus (usually the master): pull-up to 5 V and pull-down to common, 450–650 Ω. 650 Ω allows more devices on the bus, and biasing reduces the maximum device count by 4. With 3.3 V transceivers the same resistors often fall short, so use smaller resistors, block the DC path with 1 nF + 120 Ω termination, or pick a transceiver with built-in failsafe (offset receiver threshold).

Bias enabled in several places

USB-RS485 converters, PLC communication cards and devices often have a bias switch or jumper. Enabling several puts the pull-ups and pull-downs in parallel, lowering the resistance and making every driver push that much more current. Enable one and disable the rest, and check device manuals for bias enabled at the factory.

Telling problems apart

SymptomCheck first
Bytes such as 00 or FF arrive while no request is sentNo bias, or idle voltage below 200 mV
An extra byte in front of replies, CRC failsToo little bias — the receiver catches noise as a driver switches on
Works on short/slow lines, fails when longer or fasterMissing termination, or not at the two ends
Signals weaken and fail as devices are addedTerminators on middle devices, bias enabled in several places
Everything set right, only far devices failBaud vs length (roughly bps × m ≤ 10⁸), common (GND) wire, A/B polarity

In PortDock

Published 2026-10-23