LS ELECTRIC LSLV-H100 Modbus register map

Fan/pump (HVAC) drive. Built-in RS-485 with Modbus-RTU, LS INV 485, BACnet, Metasys-N2. Covers the compatible common area (0h0001-0h001B), monitor area (0h0300-), control area (0h0380-) and memory control (0h03E0). · Inverter (VFD) · H100

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)9600 bps — options: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200
Data · parity · stop8 · None · 1
Slave ID (factory)1 (1~250)
Manual address style1-based numbers (wire address + 1)

Registers (46)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

46

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
0h00010 (0x0000)HRInverter capacityU16R03·04
0 = 0.75kW · 1 = 1.5kW · 2 = 2.2kW · 3 = 3.7kW · 4 = 5.5kW · 5 = 7.5kW · 6 = 11kW · 7 = 15kW · 8 = 18.5kW · 9 = 22kW · 10 = 30kW · 11 = 37kW · 12 = 45kW · 13 = 55kW · 14 = 75kW · 15 = 90kW · 16 = 110kW · 17 = 132kW · 18 = 160kW · 19 = 185kW · 20 = 220kW · 21 = 250kW · 22 = 315kW · 23 = 355kW · 24 = 400kW · 25 = 500kW
p.350 (PDF 367)
0h00021 (0x0001)HRInput voltage classU16R03·04
0 = 220 V class · 1 = 440 V class
p.350 (PDF 367)
0h00032 (0x0002)HRVersionU16R03·04
Example: 0h0064 = version 1.00, 0h0065 = version 1.01
p.350 (PDF 367)
0h00054 (0x0004)HRTarget frequencyU16×0.01 HzR/W03·04·06·10
p.350 (PDF 367)
0h00065 (0x0005)HROperation commandU16R/W03·04·06·10
B0-B4 read/write, B5 reserved. B6-B8 (read) run command source: 0 keypad, 1 Fx/Rx-1, 2 Fx/Rx-2, 3 built-in 485, 4 comm option, 5 time event. B9-B14 (read) frequency source: 0 keypad freq, 2-8 terminal multi-step, 17 up, 18 down, 19 steady, 22 V1, 24 V2, 25 I2, 26 pulse, 27 built-in 485, 28 comm option, 30 jog, 31 PID. B15 reserved.
b0 Stop (S) · b1 Forward run (F) · b2 Reverse run (R) · b3 Trip reset (0→1) / read: trip state · b4 Free-run stop
p.350 (PDF 367)
0h00076 (0x0006)HRAcceleration timeU16×0.1 sR/W03·04·06·10
p.351 (PDF 368)
0h00087 (0x0007)HRDeceleration timeU16×0.1 sR/W03·04·06·10
p.351 (PDF 368)
0h00098 (0x0008)HROutput currentU16×0.1 AR03·04
p.351 (PDF 368)
0h000A9 (0x0009)HROutput frequencyU16×0.01 HzR03·04
p.351 (PDF 368)
0h000B10 (0x000A)HROutput voltageU16VR03·04
p.351 (PDF 368)
0h000C11 (0x000B)HRDC link voltageU16VR03·04
p.351 (PDF 368)
0h000D12 (0x000C)HROutput powerU16×0.1 kWR03·04
p.351 (PDF 368)
0h000E13 (0x000D)HROperation statusU16R03·04
b0 Stopped · b1 Running forward · b2 Running reverse · b3 Fault (trip), per OUT-30 setting · b4 Accelerating · b5 Decelerating · b6 Speed reached · b7 DC braking · b8 Decelerating to stop · b9 Jog mode · b11 Forward run command · b12 Reverse run command · b13 Run command source is communication · b14 Frequency source is communication · b15 0 HAND, 1 AUTO
p.351 (PDF 368)
0h000F14 (0x000E)HRTrip informationU16R03·04
b0 Latch type trip · b3 Level type trip · b10 H/W diagnosis
p.352 (PDF 369)
0h001015 (0x000F)HRInput terminal informationU16R03·04
b0 P1 · b1 P2 · b2 P3 · b3 P4 · b4 P5 · b5 P6 · b6 P7
p.352 (PDF 369)
0h001116 (0x0010)HROutput terminal informationU16R03·04
B6-B8 reserved (Relay 8-6 with extension IO)
b0 Relay 1 · b1 Relay 2 · b2 Relay 3 · b3 Relay 4 · b4 Relay 5 · b5 Q1
p.352 (PDF 369)
0h001217 (0x0011)HRV1 voltage inputU16×0.1 %R03·04
p.353 (PDF 370)
0h001318 (0x0012)HRThermal inputU16×0.1 %R03·04
p.353 (PDF 370)
0h001419 (0x0013)HRV2 voltage inputU16×0.1 %R03·04
p.353 (PDF 370)
0h001520 (0x0014)HRI2 current inputU16×0.1 %R03·04
p.353 (PDF 370)
0h001621 (0x0015)HRMotor speedU16rpmR03·04
p.353 (PDF 370)
0h001A25 (0x0019)HRHz/Rpm selectionU16R03·04
0 = Hz · 1 = rpm
p.353 (PDF 370)
0h001B26 (0x001A)HRSelected motor polesU16R03·04
p.353 (PDF 370)
0h0305772 (0x0304)HRInverter operation stateU16R03·04
B15-B12: 0 normal, 4 warning, 8 fault / B7-B4: 1 speed search, 2 accel, 3 steady, 4 decel, 5 decel stop, 6 H/W current suppression, 7 S/W current suppression, 8 dwell / B3-B0: 0 stop, 1 forward, 2 reverse, 3 DC
p.354 (PDF 371)
0h0306773 (0x0305)HRRun / frequency command sourceU16R03·04
B15-B8 run command: 0 keypad, 1 comm option, 3 built-in 485, 4 terminal / B7-B0 frequency: 0 keypad speed, 2-4 up/down, 5 V1, 7 V2, 8 I2, 9 pulse, 10 built-in 485, 11 comm option, 13 jog, 14 PID, 25-31 multi-step
p.355 (PDF 372)
0h0310783 (0x030F)HROutput currentU16×0.1 AR03·04
p.356 (PDF 373)
0h0311784 (0x0310)HROutput frequencyU16×0.01 HzR03·04
p.356 (PDF 373)
0h0312785 (0x0311)HROutput speedU16rpmR03·04
p.356 (PDF 373)
0h0314787 (0x0313)HROutput voltageU16VR03·04
p.356 (PDF 373)
0h0315788 (0x0314)HRDC link voltageU16VR03·04
p.356 (PDF 373)
0h0316789 (0x0315)HROutput powerU16kWR03·04
0.1 kW units below 110 kW capacity, 1 kW units from 110 kW — scale depends on capacity.
p.356 (PDF 373)
0h0318791 (0x0317)HRPID referenceU16×0.1 %R03·04
p.356 (PDF 373)
0h0319792 (0x0318)HRPID feedbackU16×0.1 %R03·04
p.356 (PDF 373)
0h032E813 (0x032D)HREnergy (kWh)U16×0.1 kWhR03·04
p.357 (PDF 374)
0h032F814 (0x032E)HREnergy (MWh)U16MWhR03·04
p.357 (PDF 374)
0h035D860 (0x035C)HRInverter temperatureU16℃R03·04
p.361 (PDF 378)
0h035E861 (0x035D)HRPower factorU16×0.1R03·04
p.361 (PDF 378)
0h0361864 (0x0360)HROutput torqueU16×0.1 %R03·04
Percent of motor rated torque
p.361 (PDF 378)
0h0380895 (0x037F)HRFrequency command (ext.)U16×0.01 HzR/W03·04·06·10
p.361 (PDF 378)
0h0381896 (0x0380)HRRpm commandU16rpmR/W03·04·06·10
p.361 (PDF 378)
0h0382897 (0x0381)HROperation command (ext.)U16R/W03·04·06·10
Example: forward run 0003h, reverse run 0001h
b0 0 stop / 1 run · b1 0 reverse / 1 forward · b2 Trip reset (0→1) · b3 Free-run stop (0→1)
p.361 (PDF 378)
0h0383898 (0x0382)HRAcceleration time (ext.)U16×0.1 sR/W03·04·06·10
p.361 (PDF 378)
0h0384899 (0x0383)HRDeceleration time (ext.)U16×0.1 sR/W03·04·06·10
p.362 (PDF 379)
0h0388903 (0x0387)HRPID reference (comm)U16×0.1 %R/W03·04·06·10
p.362 (PDF 379)
0h0389904 (0x0388)HRPID feedback (comm)U16×0.1 %R/W03·04·06·10
p.362 (PDF 379)
0h03E0991 (0x03DF)HRSave parametersU16R/W03·04·06·10
Write 0 then 1 to save (p.337). Not changeable during run
0 = No · 1 = Yes
p.364 (PDF 381)

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.