An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU, Modbus ASCII |
|---|---|
| Baud (factory) | 19200 bps — options: 1200, 2400, 4800, 9600, 19200, 38400, 57600 |
| Data · parity · stop | 8 · Even · 1 |
| Slave ID (factory) | 1 (1~247) |
| Max per request | 16 registers |
| Manual address style | Wire address as is (0-based) |
- Addressing: read example 01 03 21 00 00 01 reads 2100H (status word 1) — the table's hex address is the frame address (p.163). Parameter Pxx.yy = xxyyH (e.g. P00.03 = 0003H; writing 100 Hz = 2710H, p.164).
- Defaults: P14.00 address 1, P14.01 = 4 (19200 bps), P14.02 = 1 (RTU E,8,1) (pp.111-112). FC 03, 06 and 10, up to 16 per request.
Registers (28)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| P00.01 (0001H) | 1 (0x0001) | HR | Running command channel | U16 | R/W | 03·06·10 | 0 = Keypad · 1 = Terminal · 2 = Communication p.50~51 | |
| P00.03 (0003H) | 3 (0x0003) | HR | Max. output frequency | U16 | ×0.01 Hz | R/W | 03·06·10 | Write example: 100 Hz → 2710H (03 06 00 03 27 10) p.50~51 |
| P14.00 (0E00H) | 3584 (0x0E00) | HR | Local communication address | U16 | R/W | 03·06·10 | Range 1 ~ 247 p.111~112 | |
| P14.01 (0E01H) | 3585 (0x0E01) | HR | Communication baud rate | U16 | R/W | 03·06·10 | 0 = 1200 bps · 1 = 2400 bps · 2 = 4800 bps · 3 = 9600 bps · 4 = 19200 bps (default) · 5 = 38400 bps · 6 = 57600 bps p.111~112 | |
| P14.02 (0E02H) | 3586 (0x0E02) | HR | Data bit check | U16 | R/W | 03·06·10 | 6-17 are ASCII formats 0 = RTU N,8,1 · 1 = RTU E,8,1 (default) · 2 = RTU O,8,1 · 3 = RTU N,8,2 · 4 = RTU E,8,2 · 5 = RTU O,8,2 p.111~112 | |
| P00.02 (0002H) | 2 (0x0002) | HR | Communication mode of running commands | U16 | R/W | 03·06·10 | 0 = Modbus (default) p.50~51 | |
| 2000H | 8192 (0x2000) | HR | Communication-based control command | U16 | R/W | 03·06·10 | With P00.01 = 2 (communication) and P00.02 = 0 (Modbus) (p.159) 1 = Forward running · 2 = Reverse running · 3 = Forward jogging · 4 = Reverse jogging · 5 = Stop · 6 = Coast to stop · 7 = Fault reset · 8 = Jogging stop p.157~159, p.163 | |
| 2001H | 8193 (0x2001) | HR | Communication-based frequency setting | U16 | ×0.01 Hz | R/W | 03·06·10 | p.157~159 |
| 2002H | 8194 (0x2002) | HR | PID reference | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 100 % p.157~159 |
| 2003H | 8195 (0x2003) | HR | PID feedback | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 100 % p.157~159 |
| 2004H | 8196 (0x2004) | HR | Torque setting (% of motor rated current) | S16 | ×0.1 % | R/W | 03·06·10 | Range -300 ~ 300 % p.157~159 |
| 2005H | 8197 (0x2005) | HR | Forward running upper limit frequency | U16 | ×0.01 Hz | R/W | 03·06·10 | p.157~159 |
| 2006H | 8198 (0x2006) | HR | Reverse running upper limit frequency | U16 | ×0.01 Hz | R/W | 03·06·10 | p.157~159 |
| 2007H | 8199 (0x2007) | HR | Electromotive torque upper limit | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 300 % p.157~159 |
| 2008H | 8200 (0x2008) | HR | Braking torque upper limit | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 300 % p.157~159 |
| 200AH | 8202 (0x200A) | HR | Virtual input terminal command | U16 | R/W | 03·06·10 | Range 0 ~ 511 p.157~159 | |
| 200BH | 8203 (0x200B) | HR | Virtual output terminal command | U16 | R/W | 03·06·10 | Range 0 ~ 15 p.157~159 | |
| 200DH | 8205 (0x200D) | HR | AO setting 1 | S16 | ×0.1 % | R/W | 03·06·10 | Range -100 ~ 100 % p.157~159 |
| 200EH | 8206 (0x200E) | HR | AO setting 2 | S16 | ×0.1 % | R/W | 03·06·10 | Range -100 ~ 100 % p.157~159 |
| 2100H | 8448 (0x2100) | HR | VFD status word 1 | U16 | R | 03 | Read example 01 03 21 00 00 01 → 00 03 = stopped (p.163) 1 = Forward running · 2 = Reverse running · 3 = Stopped · 4 = Faulty · 5 = POFF p.157~159, p.163 | |
| 2101H | 8449 (0x2101) | HR | VFD status word 2 | U16 | R | 03 | bit1-2 motor 1-4; bit5-6 = 00 keypad, 01 terminal, 10 communication control b0 Ready to run · b3 SM (0 = AM) · b4 Overload pre-alarm p.157~159 | |
| 2102H | 8450 (0x2102) | HR | VFD fault code | U16 | R | 03 | p.157~159 | |
| 2103H | 8451 (0x2103) | HR | VFD identification code | U16 | R | 03 | GD200A = 0x0107 p.157~159 | |
| 3000H | 12288 (0x3000) | HR | Running frequency (output frequency) | U16 | ×0.01 Hz | R | 03 | The table gives only ranges (0.00 Hz-, 0.0-5000.0 A etc.); the scale follows the manual's rule of using the range's decimals (fieldbus ratio, example on p.164) p.157~159, p.164 |
| 3001H | 12289 (0x3001) | HR | Set frequency | U16 | ×0.01 Hz | R | 03 | The table gives only ranges (0.00 Hz-, 0.0-5000.0 A etc.); the scale follows the manual's rule of using the range's decimals (fieldbus ratio, example on p.164) p.157~159, p.164 |
| 3002H | 12290 (0x3002) | HR | Bus voltage | U16 | V | R | 03 | The table gives only ranges (0.00 Hz-, 0.0-5000.0 A etc.); the scale follows the manual's rule of using the range's decimals (fieldbus ratio, example on p.164) Range 0 ~ 1200 V p.157~159, p.164 |
| 3003H | 12291 (0x3003) | HR | Output voltage | U16 | V | R | 03 | The table gives only ranges (0.00 Hz-, 0.0-5000.0 A etc.); the scale follows the manual's rule of using the range's decimals (fieldbus ratio, example on p.164) Range 0 ~ 1200 V p.157~159, p.164 |
| 3004H | 12292 (0x3004) | HR | Output current | U16 | ×0.1 A | R | 03 | The table gives only ranges (0.00 Hz-, 0.0-5000.0 A etc.); the scale follows the manual's rule of using the range's decimals (fieldbus ratio, example on p.164) Range 0 ~ 5000 A p.157~159, p.164 |
Notes
- Monitors from 3000H list only ranges (p.159); only 3000H-3004H, whose decimals are clear, are included (percentage values such as power and torque are left out). Printed page = PDF page − 7.
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- invt/gd200a.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- Goodrive200A Series VFD Manual — INVT, V3.1 (2026-07) · P00 printed pp.50-51, P14 pp.111-112, 9 communication protocol address table pp.157-159, examples pp.163-164 · checked 2026-11-01