Built-in RS485 Modbus RTU/ASCII. Command 2000H, frequency 2001H, status 2100H, parameter Pxx.yy = xxyyH. · Inverter (VFD) · Goodrive200A

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU, Modbus ASCII
Baud (factory)19200 bps — options: 1200, 2400, 4800, 9600, 19200, 38400, 57600
Data · parity · stop8 · Even · 1
Slave ID (factory)1 (1~247)
Max per request16 registers
Manual address styleWire address as is (0-based)

Registers (28)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

28

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
P00.01 (0001H)1 (0x0001)HRRunning command channelU16R/W03·06·10
0 = Keypad · 1 = Terminal · 2 = Communication
p.50~51
P00.03 (0003H)3 (0x0003)HRMax. output frequencyU16×0.01 HzR/W03·06·10
Write example: 100 Hz → 2710H (03 06 00 03 27 10)
p.50~51
P14.00 (0E00H)3584 (0x0E00)HRLocal communication addressU16R/W03·06·10
Range 1 ~ 247
p.111~112
P14.01 (0E01H)3585 (0x0E01)HRCommunication baud rateU16R/W03·06·10
0 = 1200 bps · 1 = 2400 bps · 2 = 4800 bps · 3 = 9600 bps · 4 = 19200 bps (default) · 5 = 38400 bps · 6 = 57600 bps
p.111~112
P14.02 (0E02H)3586 (0x0E02)HRData bit checkU16R/W03·06·10
6-17 are ASCII formats
0 = RTU N,8,1 · 1 = RTU E,8,1 (default) · 2 = RTU O,8,1 · 3 = RTU N,8,2 · 4 = RTU E,8,2 · 5 = RTU O,8,2
p.111~112
P00.02 (0002H)2 (0x0002)HRCommunication mode of running commandsU16R/W03·06·10
0 = Modbus (default)
p.50~51
2000H8192 (0x2000)HRCommunication-based control commandU16R/W03·06·10
With P00.01 = 2 (communication) and P00.02 = 0 (Modbus) (p.159)
1 = Forward running · 2 = Reverse running · 3 = Forward jogging · 4 = Reverse jogging · 5 = Stop · 6 = Coast to stop · 7 = Fault reset · 8 = Jogging stop
p.157~159, p.163
2001H8193 (0x2001)HRCommunication-based frequency settingU16×0.01 HzR/W03·06·10
p.157~159
2002H8194 (0x2002)HRPID referenceU16×0.1 %R/W03·06·10
Range 0 ~ 100 %
p.157~159
2003H8195 (0x2003)HRPID feedbackU16×0.1 %R/W03·06·10
Range 0 ~ 100 %
p.157~159
2004H8196 (0x2004)HRTorque setting (% of motor rated current)S16×0.1 %R/W03·06·10
Range -300 ~ 300 %
p.157~159
2005H8197 (0x2005)HRForward running upper limit frequencyU16×0.01 HzR/W03·06·10
p.157~159
2006H8198 (0x2006)HRReverse running upper limit frequencyU16×0.01 HzR/W03·06·10
p.157~159
2007H8199 (0x2007)HRElectromotive torque upper limitU16×0.1 %R/W03·06·10
Range 0 ~ 300 %
p.157~159
2008H8200 (0x2008)HRBraking torque upper limitU16×0.1 %R/W03·06·10
Range 0 ~ 300 %
p.157~159
200AH8202 (0x200A)HRVirtual input terminal commandU16R/W03·06·10
Range 0 ~ 511
p.157~159
200BH8203 (0x200B)HRVirtual output terminal commandU16R/W03·06·10
Range 0 ~ 15
p.157~159
200DH8205 (0x200D)HRAO setting 1S16×0.1 %R/W03·06·10
Range -100 ~ 100 %
p.157~159
200EH8206 (0x200E)HRAO setting 2S16×0.1 %R/W03·06·10
Range -100 ~ 100 %
p.157~159
2100H8448 (0x2100)HRVFD status word 1U16R03
Read example 01 03 21 00 00 01 → 00 03 = stopped (p.163)
1 = Forward running · 2 = Reverse running · 3 = Stopped · 4 = Faulty · 5 = POFF
p.157~159, p.163
2101H8449 (0x2101)HRVFD status word 2U16R03
bit1-2 motor 1-4; bit5-6 = 00 keypad, 01 terminal, 10 communication control
b0 Ready to run · b3 SM (0 = AM) · b4 Overload pre-alarm
p.157~159
2102H8450 (0x2102)HRVFD fault codeU16R03
p.157~159
2103H8451 (0x2103)HRVFD identification codeU16R03
GD200A = 0x0107
p.157~159
3000H12288 (0x3000)HRRunning frequency (output frequency)U16×0.01 HzR03
The table gives only ranges (0.00 Hz-, 0.0-5000.0 A etc.); the scale follows the manual's rule of using the range's decimals (fieldbus ratio, example on p.164)
p.157~159, p.164
3001H12289 (0x3001)HRSet frequencyU16×0.01 HzR03
The table gives only ranges (0.00 Hz-, 0.0-5000.0 A etc.); the scale follows the manual's rule of using the range's decimals (fieldbus ratio, example on p.164)
p.157~159, p.164
3002H12290 (0x3002)HRBus voltageU16VR03
The table gives only ranges (0.00 Hz-, 0.0-5000.0 A etc.); the scale follows the manual's rule of using the range's decimals (fieldbus ratio, example on p.164)
Range 0 ~ 1200 V
p.157~159, p.164
3003H12291 (0x3003)HROutput voltageU16VR03
The table gives only ranges (0.00 Hz-, 0.0-5000.0 A etc.); the scale follows the manual's rule of using the range's decimals (fieldbus ratio, example on p.164)
Range 0 ~ 1200 V
p.157~159, p.164
3004H12292 (0x3004)HROutput currentU16×0.1 AR03
The table gives only ranges (0.00 Hz-, 0.0-5000.0 A etc.); the scale follows the manual's rule of using the range's decimals (fieldbus ratio, example on p.164)
Range 0 ~ 5000 A
p.157~159, p.164

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).

Download JSON