PortDock

Conduit & Duct Fill Calculator

Conduit or duct fill % from wire diameters and counts, against NEC conduit fill (53/31/40 %), wireways (20 %) and NFPA 79 panel duct (50 %).

Wires (overall diameter mm × count; a multi-core cable counts as one)

Results
Total wire area
Inside area
Fill
Limit
Smallest inside diameter within the limit
Max count of the first-row wire alone

Results update as you type. Everything runs in your browser; nothing you type is sent anywhere.

Limits and sources

  • Conduit — NEC (NFPA 70) Chapter 9 Table 1: 1 conductor 53 %, 2 conductors 31 %, more than 2: 40 %. A multiconductor cable counts as one conductor (Note 9). Nipples up to 600 mm (24 in) may be filled to 60 % (Note 4) — not covered here.
  • Wireways — NEC 376.22(A) (metal) and 378.22 (nonmetallic): conductors may fill at most 20 % of the interior area.
  • Panel wiring duct — NFPA 79 (Electrical Standard for Industrial Machinery) 13.5.2 (2007 and 2012 editions): conductors and cables may fill at most 50 % of the duct's interior area. The clause number may differ by edition.
  • Other national codes (IEC countries, Korea's KEC, …) have their own rules; this tool does not include them.

Formulas

  • Wire area = π ÷ 4 × (overall diameter)²
  • Conduit inside area = π ÷ 4 × ID², duct = inside width × height
  • Fill = total wire area ÷ inside area × 100

Notes

  • Use the maker's overall diameter including insulation. AWG and mm² diameters are for the bare conductor and are too small.
  • Conduit inside diameters vary by type (rigid, EMT, PVC, flexible) and trade size — enter the catalogue ID, not the trade size.
  • Enter the duct's inside dimensions, not the outside — slots and cover take some room.
  • Even within the limit, many bends or long pulls make installation hard, and bundling reduces ampacity (correction factors). Have a qualified person check against your local code.

FAQ

How many wires fit in a conduit?

Under NEC Chapter 9 Table 1, with more than two conductors the total area including insulation may be at most 40 % of the conduit's inside area. Example: 3 mm OD wires in a 16 mm ID conduit — up to 11 (about 38.7 %).

Why is two conductors the lowest at 31 %?

The usual explanation is that two conductors side by side span the conduit's diameter and can jam when pulled; the table sets the limit lower than for one (53 %) or three or more (40 %).

How full can panel wiring duct be?

NFPA 79 limits fill to 50 % of the duct's interior area, which also leaves room for wiring added later.

To pick wire sizes, see the cable selection helper and the AWG to mm² table; whether signal and power cables may share a duct is covered in the field noise guide.