PortDock

LS ELECTRIC LSLV-S300 Modbus register map

Built-in RS-485 Modbus-RTU. Covers the expansion common area: monitoring (0300h-), control (0380h-) and trip (0400h-). With INTC-06 at its default (1), frame address = manual address - 1. · Inverter (VFD) · S300

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)9600 bps — options: 1200, 2400, 4800, 9600, 19200, 38400, 115200
Data · parity · stop8 · None · 1
Slave ID (factory)1 (1~250)
Max per request16 registers
Manual address style1-based numbers (wire address + 1)

Registers (33)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

33

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
0300h767 (0x02FF)HRInverter modelU16R03·04
17 = S300 (0011h)
p.462 (PDF 496)
0301h768 (0x0300)HRInverter capacity (bit-coded)U16R03·04
B15-B14 unit (0 W, 1 kW, 2 MW), B13-B4 integer part, B3-B0 fraction. e.g. 1.5 kW = 4015h, 7.5 kW = 4075h, 400 W = 1900h.
p.462 (PDF 496)
0302h769 (0x0301)HRInput voltage / phase / coolingU16R03·04
561 = 200 V class, 3-phase, forced cooling · 1073 = 400 V class, 3-phase, forced cooling
p.463 (PDF 497)
0303h770 (0x0302)HRInverter S/W versionU16R03·04
Hex: 0066h = version 1.00 (manual example)
p.463 (PDF 497)
0305h772 (0x0304)HROperating stateU16R03·04
B15-B12: 0 trip, 2 warning, 4 run disabled, 8 normal. B7-B4: 1 speed search, 2 accelerating, 3 steady, 4 decelerating, 5 decel to stop, 6 H/W overcurrent suppression, 7 S/W overcurrent suppression, 8 dwell. B3-B0: 0 stop, 1 forward, 2 reverse, 3 DC operation.
p.463 (PDF 497)
0306h773 (0x0305)HRRun / frequency command sourceU16R03·04
B15-B8 run source: 0 Smart Operator, 1 comm option, 3 built-in RS485, 4 terminal, 5 USB. B7-B0 frequency source: 0 Smart Operator speed, 1 Smart Operator torque, 2-4 up/down, 5 AI1, 6 AI2, 7 AI3, 9 pulse, 10 built-in RS485, 11 comm option, 13 jog, 14 PID, 15 USB, 25 multi-step.
p.464 (PDF 498)
0310h783 (0x030F)HROutput currentU16×0.1 AR03·04
p.465 (PDF 499)
0311h784 (0x0310)HROutput frequencyU16×0.01 HzR03·04
p.465 (PDF 499)
0314h787 (0x0313)HROutput voltageU16VR03·04
p.465 (PDF 499)
0315h788 (0x0314)HRDC link voltageU16VR03·04
p.465 (PDF 499)
0316h789 (0x0315)HROutput powerU16×0.1 kWR03·04
p.465 (PDF 499)
0317h790 (0x0316)HROutput torqueU16×0.1 %R03·04
p.465 (PDF 499)
0320h799 (0x031F)HRDigital input statusU16R03·04
b0 DI1 · b1 DI2 · b2 DI3 · b3 DI4 · b4 DI5 · b5 DI6 · b6 DI7 · b7 DI8
p.466~467 (PDF 500~501)
0321h800 (0x0320)HRDigital output statusU16R03·04
b0 DO1 · b1 DO2 · b2 DO3
p.467 (PDF 501)
0324h803 (0x0323)HRAnalog input 1 (V1, I1)U16×0.01 %R03·04
p.468 (PDF 502)
0325h804 (0x0324)HRAnalog input 2 (V2, I2)U16×0.01 %R03·04
p.468 (PDF 502)
0326h805 (0x0325)HRAnalog input 3 (V3, I3)U16×0.01 %R03·04
p.468 (PDF 502)
0328h807 (0x0327)HRAnalog output 1U16×0.01 %R03·04
p.468 (PDF 502)
032Dh812 (0x032C)HRTemperature (NTC)U16℃R03·04
p.468 (PDF 502)
032Eh813 (0x032D)HREnergy consumption (kWh part)U16kWhR03·04
Read together with 032Fh (MWh part). Scale cell is '-'.
p.469 (PDF 503)
032Fh814 (0x032E)HREnergy consumption (MWh part)U16MWhR03·04
p.469 (PDF 503)
0380h895 (0x037F)HRFrequency commandU16×0.01 HzR/W03·04·06·10
p.471 (PDF 505)
0381h896 (0x0380)HRSpeed command (rpm)U16rpmR/W03·04·06·10
p.471 (PDF 505)
0382h897 (0x0381)HRRun commandU16R/W03·04·06·10
b0 Run · b1 Direction (0 reverse, 1 forward) · b2 Trip reset · b3 Free-run stop
p.471 (PDF 505)
0383h898 (0x0382)HRAcceleration timeU16×0.1 sR/W03·04·06·10
p.471 (PDF 505)
0384h899 (0x0383)HRDeceleration timeU16×0.1 sR/W03·04·06·10
p.471 (PDF 505)
0385h900 (0x0384)HRVirtual digital input controlU16R/W03·04·06·10
Per bit: 0 Off, 1 On.
b0 Virtual DI1 · b1 Virtual DI2 · b2 Virtual DI3 · b3 Virtual DI4 · b4 Virtual DI5 · b5 Virtual DI6 · b6 Virtual DI7 · b7 Virtual DI8 · b8 Virtual DI9 · b9 Virtual DI10 · b10 Virtual DI11 · b11 Virtual DI12 · b12 Virtual DI13 · b13 Virtual DI14 · b14 Virtual DI15 · b15 Virtual DI16
p.472 (PDF 506)
0388h903 (0x0387)HRPID referenceU16×0.1 %R/W03·04·06·10
p.473 (PDF 507)
0389h904 (0x0388)HRPID feedbackU16×0.1 %R/W03·04·06·10
p.473 (PDF 507)
0390h911 (0x038F)HRTorque commandU16×0.1 %R/W03·04·06·10
p.473 (PDF 507)
0400h1023 (0x03FF)HRCurrent trip 1 indexU16R03·04
Trip mode area (read-only).
0 = ADC Offset · 1 = Watchdog · 2 = Gate Power Loss · 3 = Main OS Error · 4 = Over Load · 5 = Under Load · 6 = Inverter Over Load · 7 = E-Thermal · 8 = Ground Fault · 9 = Out Phase U Open · 10 = In Phase Open · 11 = Over Speed · 12 = Speed Deviation · 13 = Drv Over Heat · 14 = NTC Open · 15 = NTC Short · 16 = Over Current · 17 = Over Voltage · 18 = IO Board · 19 = BX · 20 = Mechanical Brake · 21 = External 1 · 22 = External 2 · 23 = External 3 · 24 = External 4 · 25 = Arm Short · 26 = Fuse Open · 27 = Encoder · 28 = Encoder No Connection · 29 = Encoder Wrong Dir · 30 = Motor Over Heat · 31 = Main Fan Fault · 32 = Parameter Write · 33 = Pre PID Fail · 34 = No Motor · 35 = Option 1 · 36 = Option 2 · 37 = Option 3 · 38 = Low Voltage · 39 = Lost Sensor · 40 = Lost Int Comm · 41 = Lost Opt Comm · 42 = Lost Keypad · 43 = Lost USB · 44 = Lost AI 1 · 45 = Lost AI 2 · 46 = Lost AI 3 · 47 = Lost AI 4 · 48 = Lost Ext AI 1 · 49 = Lost Ext AI 2 · 50 = Lost Ext AI 3 · 51 = Lost Ext AI 4 · 52 = STO Feedback A · 53 = STO Feedback B · 54 = STO P24 Fault · 55 = STO P5 Fault · 56 = Aux Fan Fault · 57 = Control Fan Fault · 58 = Data Storage · 59 = Precharge Fail · 60 = H/W OCS Fail · 61 = TR Tune Fail · 62 = RS Tune Fail · 63 = SLS Tune Fail · 64 = LS Tune Fail · 65 = IF Tune Fail · 66 = MC Fault · 67 = Reserved · 68 = Lost P24V · 69 = Out Phase V Open · 70 = Out Phase W Open · 71 = Reset/Restart Fail · 72 = Outline Short · 73 = KEB Safety Stop · 74 = System Error-1 · 75 = Br Release Invalid · 76 = Br Releasing Fail · 77 = Br Engaging Fail · 78 = Main Cap Diag Fail · 79 = Encoder Tuning Err · 80 = Pole Pos Detect F · 81 = Pos Max Track Err · 82 = Pos Tar Bound Err · 83 = Pos SW Limit High · 84 = Pos SW Limit Low · 85 = Pos HW Limit High · 86 = Pos HW Limit Low · 87 = Pos Multi Sync F · 88 = Cur Pos Overf Err · 89 = Power Index Error · 90 = CAN Bus Error · 91 = Prevent Cmd Trip · 92 = WebBreak Trip · 93 = Ambient Sensor Flt · 94 = Ambient Over Heat · 95 = Ambient Under Heat · 96 = Ana In Lvl Detect · 97 = RP Wire Error · 65535 = None (FFFFh)
p.477~480 (PDF 511~514)
0401h1024 (0x0400)HRCurrent trip 2 indexU16R03·04
Same codes as 0400h.
p.480 (PDF 514)
0407h1030 (0x0406)HRDrive state before tripU16R03·04
0 = Stop · 1 = Zero-speed run · 2 = Accelerating · 3 = Decelerating · 4 = Steady speed · 5 = Torque run
p.481 (PDF 515)

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

Download JSON

Sources