Siemens SINAMICS G120 Modbus register map

RS485 Modbus RTU (p2030 = 2). Frame address = register - 40001: control word 40100, setpoint 40101, status word 40110, actual value 40111, output frequency 40342, current 40345, power 40347, fault 40400 · Inverter (VFD) · SINAMICS G120C

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)19200 bps — options: 4800, 9600, 19200, 38400, 57600, 76800, 93750, 115200, 187500
Data · parity · stop8 · Even · 1
Max per request125 registers
Manual address style40001/30001 style (wire address + 1, first digit = table)

Registers (47)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

47

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
4010099 (0x0063)HRControl word (process data 1)U16R/W03·06·10
p.126
40101100 (0x0064)HRMain setpoint (process data 2)U16R/W03·06·10
p.126
40110109 (0x006D)HRStatus word (process data 1)U16R03
p.126
40111110 (0x006E)HRMain actual value (process data 2)U16R03
p.126
40200199 (0x00C7)HRDO 0 (p0730)U16R/W03·06·10
p.127
40201200 (0x00C8)HRDO 1 (p0731)U16R/W03·06·10
p.127
40202201 (0x00C9)HRDO 2 (p0732)U16R/W03·06·10
p.127
40220219 (0x00DB)HRAO 0 (r0774.0)S16×0.01 %R03
Range -100 ~ 100 %
p.127
40221220 (0x00DC)HRAO 1 (r0774.1)S16×0.01 %R03
Range -100 ~ 100 %
p.127
40240239 (0x00EF)HRDI 0U16R03
p.127
40241240 (0x00F0)HRDI 1U16R03
p.127
40242241 (0x00F1)HRDI 2U16R03
p.127
40243242 (0x00F2)HRDI 3U16R03
p.127
40244243 (0x00F3)HRDI 4U16R03
p.127
40245244 (0x00F4)HRDI 5U16R03
p.127
40260259 (0x0103)HRAI 0 (r0755[0])S16×0.01 %R03
Range -300 ~ 300 %
p.127
40261260 (0x0104)HRAI 1 (r0755[1])S16×0.01 %R03
Range -300 ~ 300 %
p.127
40300299 (0x012B)HRPowerstack number r0200U16R03
p.127
40301300 (0x012C)HRConverter firmware r0018U16R03
p.127
40320319 (0x013F)HRRated power r0206U16×0.01 kWR03
p.127
40321320 (0x0140)HRCurrent limit p0640U16×0.1 AR/W03·06·10
Range 10 ~ 400 A
p.127
40322321 (0x0141)HRRamp-up time p1120U16×0.01 sR/W03·06·10
Range 0 ~ 650 s
p.127
40323322 (0x0142)HRRamp-down time p1121U16×0.01 sR/W03·06·10
Range 0 ~ 650 s
p.127
40324323 (0x0143)HRReference speed p2000U16rpmR/W03·06·10
Range 6 ~ 32767 rpm
p.127
40340339 (0x0153)HRSpeed setpoint r0020S16rpmR03
p.127
40341340 (0x0154)HRActual speed value r0022S16rpmR03
p.127
40342341 (0x0155)HROutput frequency r0024S16×0.01 HzR03
p.128
40343342 (0x0156)HROutput voltage r0025U16VR03
p.128
40344343 (0x0157)HRDC link voltage r0026U16VR03
p.128
40345344 (0x0158)HRCurrent actual value r0027U16×0.01 AR03
p.128
40346345 (0x0159)HRActual torque value r0031S16×0.01 NmR03
p.128
40347346 (0x015A)HRActual active power r0032U16×0.01 kWR03
p.128
40348347 (0x015B)HREnergy consumption r0039U16kWhR03
p.128
40349348 (0x015C)HRControl priority r0807 (HAND/AUTO)U16R03
p.128
40400399 (0x018F)HRFault number, index 0 (r0947)U16R03
p.128
40401400 (0x0190)HRFault number, index 1 (r0947)U16R03
p.128
40402401 (0x0191)HRFault number, index 2 (r0947)U16R03
p.128
40403402 (0x0192)HRFault number, index 3 (r0947)U16R03
p.128
40404403 (0x0193)HRFault number, index 4 (r0947)U16R03
p.128
40405404 (0x0194)HRFault number, index 5 (r0947)U16R03
p.128
40406405 (0x0195)HRFault number, index 6 (r0947)U16R03
p.128
40407406 (0x0196)HRFault number, index 7 (r0947)U16R03
p.128
40408407 (0x0197)HRAlarm number r2110U16R03
p.128
40409408 (0x0198)HRActual alarm code r2132U16R03
p.128
40499498 (0x01F2)HRPRM ERROR codeU16R03
p.128
40500499 (0x01F3)HRTechnology controller enable p2200U16R/W03·06·10
Range 0 ~ 1
p.128
40501500 (0x01F4)HRTechnology controller MOP p2240S16×0.01 %R/W03·06·10
Range -200 ~ 200 %
p.128

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).

Download JSON