An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU, Modbus ASCII |
|---|---|
| Baud (factory) | 19200 bps — options: 1200, 2400, 4800, 9600, 19200, 38400, 57600 |
| Data · parity · stop | 8 · Even · 1 |
| Slave ID (factory) | 1 (1~247) |
| Max per request | 16 registers |
| Manual address style | Wire address as is (0-based) |
- Addressing: read example 01 03 21 00 00 01 reads 2100H (status word 1), write example 03 06 20 00 00 01 writes 2000H (command) — the hex address in the table is the frame address (pp.138-140). Parameter Pxx.yy maps xx and yy to hex bytes: P05.05 = 0505H, P10.01 = 0A01H (p.131).
- Defaults: P14.00 address 1, P14.01 = 4 (19200 bps), P14.02 = 1 (RTU E,8,1) (pp.99-100). FC 03, 06 and 10, up to 16 words per request (p.125 onward).
- Values are scaled integers ('fieldbus ratio'), set by the decimals of the setting range or default (one decimal = ×10) (p.135). Setting the high bit of a parameter address (e.g. 8007H) writes RAM only, not EEPROM (write-only) (pp.131-132).
Registers (34)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| P00.01 (0001H) | 1 (0x0001) | HR | Running command channel | U16 | R/W | 03·06·10 | 0 = Keypad · 1 = Terminal · 2 = Communication p.31~32 | |
| P00.03 (0003H) | 3 (0x0003) | HR | Max. output frequency | U16 | ×0.01 Hz | R/W | 03·06·10 | Write example: 100 Hz → 2710H (03 06 00 03 27 10) p.31~32 |
| P14.00 (0E00H) | 3584 (0x0E00) | HR | Local communication address | U16 | R/W | 03·06·10 | Range 1 ~ 247 p.99~101 | |
| P14.01 (0E01H) | 3585 (0x0E01) | HR | Communication baud rate | U16 | R/W | 03·06·10 | 0 = 1200 bps · 1 = 2400 bps · 2 = 4800 bps · 3 = 9600 bps · 4 = 19200 bps (default) · 5 = 38400 bps · 6 = 57600 bps p.99~101 | |
| P14.02 (0E02H) | 3586 (0x0E02) | HR | Data bit check | U16 | R/W | 03·06·10 | 6-17 are ASCII formats 0 = RTU N,8,1 · 1 = RTU E,8,1 (default) · 2 = RTU O,8,1 · 3 = RTU N,8,2 · 4 = RTU E,8,2 · 5 = RTU O,8,2 p.99~101 | |
| P14.04 (0E04H) | 3588 (0x0E04) | HR | RS485 communication timeout | U16 | ×0.1 s | R/W | 03·06·10 | 0.0 = disabled; exceeding it reports 'CE' Range 0 ~ 60 s p.101 |
| 2000H | 8192 (0x2000) | HR | Communication control command | U16 | R/W | 03·06·10 | With P00.01 = 2 (communication). Write example 03 06 20 00 00 01 = forward running (p.139) 1 = Forward running · 2 = Reverse running · 3 = Forward jogging · 4 = Reverse jogging · 5 = Stop · 6 = Coast to stop · 7 = Fault reset · 8 = Jogging stop p.132~134, p.139 | |
| 2001H | 8193 (0x2001) | HR | Communication setting frequency | U16 | ×0.01 Hz | R/W | 03·06·10 | 0 to Fmax p.132~134 |
| 2002H | 8194 (0x2002) | HR | PID reference | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 100 % p.132~134 |
| 2003H | 8195 (0x2003) | HR | PID feedback | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 100 % p.132~134 |
| 2004H | 8196 (0x2004) | HR | Torque setting (% of motor rated current) | S16 | ×0.1 % | R/W | 03·06·10 | Range -300 ~ 300 % p.132~134 |
| 2005H | 8197 (0x2005) | HR | Forward upper limit frequency | U16 | ×0.01 Hz | R/W | 03·06·10 | p.132~134 |
| 2006H | 8198 (0x2006) | HR | Reverse upper limit frequency | U16 | ×0.01 Hz | R/W | 03·06·10 | p.132~134 |
| 200AH | 8202 (0x200A) | HR | Virtual input terminal command | U16 | R/W | 03·06·10 | Range 0 ~ 511 p.132~134 | |
| 200DH | 8205 (0x200D) | HR | AO output setting 1 | S16 | ×0.1 % | R/W | 03·06·10 | Range -100 ~ 100 % p.132~134 |
| 2100H | 8448 (0x2100) | HR | Status word 1 | U16 | R | 03 | 0002H is printed with the same text as 0001H ('Forward running'), so it is omitted. Read example 01 03 21 00 00 01 → 00 03 = stop (pp.138-139) 1 = Forward running · 3 = Stop · 4 = Fault · 5 = POFF state · 6 = Pre-exciting p.132~134, p.138 | |
| 2101H | 8449 (0x2101) | HR | Status word 2 | U16 | R | 03 | bit1-2 motor 1-4; bit5-6 = 00 keypad, 01 terminal, 10 communication control b0 Bus voltage established · b3 Synchronous motor (0 = asynchronous) · b4 Overload pre-alarm p.132~134 | |
| 2102H | 8450 (0x2102) | HR | Fault code | U16 | R | 03 | Codes follow the P07.27 fault type list 0 = No fault · 4 = Overcurrent during acceleration (OC1) · 5 = Overcurrent during deceleration (OC2) · 6 = Overcurrent at constant speed (OC3) · 7 = Overvoltage during acceleration (OV1) · 8 = Overvoltage during deceleration (OV2) · 9 = Overvoltage at constant speed (OV3) · 10 = Bus undervoltage (UV) · 11 = Motor overload (OL1) · 12 = VFD overload (OL2) · 18 = RS485 communication fault (CE) p.132~134, p.73 | |
| 2103H | 8451 (0x2103) | HR | VFD identifying code | U16 | R | 03 | GD20 = 0x0106 p.132~134 | |
| 3000H | 12288 (0x3000) | HR | Running frequency (output frequency) | U16 | ×0.01 Hz | R | 03 | p.132~134 |
| 3001H | 12289 (0x3001) | HR | Set frequency | U16 | ×0.01 Hz | R | 03 | p.132~134 |
| 3002H | 12290 (0x3002) | HR | Bus voltage | U16 | ×0.1 V | R | 03 | p.132~134 |
| 3003H | 12291 (0x3003) | HR | Output voltage | U16 | V | R | 03 | p.132~134 |
| 3004H | 12292 (0x3004) | HR | Output current | U16 | ×0.1 A | R | 03 | p.132~134 |
| 3005H | 12293 (0x3005) | HR | Rotating speed | U16 | rpm | R | 03 | p.132~134 |
| 3006H | 12294 (0x3006) | HR | Output power | S16 | ×0.1 % | R | 03 | Range -300 ~ 300 % p.132~134 |
| 3007H | 12295 (0x3007) | HR | Output torque | S16 | ×0.1 % | R | 03 | Range -250 ~ 250 % p.132~134 |
| 3008H | 12296 (0x3008) | HR | PID setting | S16 | ×0.1 % | R | 03 | Range -100 ~ 100 % p.132~134 |
| 3009H | 12297 (0x3009) | HR | PID feedback | S16 | ×0.1 % | R | 03 | Range -100 ~ 100 % p.132~134 |
| 300AH | 12298 (0x300A) | HR | Input state | U16 | R | 03 | Range 0 ~ 511 p.132~134 | |
| 300BH | 12299 (0x300B) | HR | Output state | U16 | R | 03 | Range 0 ~ 511 p.132~134 | |
| 300CH | 12300 (0x300C) | HR | AI 1 | U16 | ×0.01 V | R | 03 | Range 0 ~ 10 V p.132~134 |
| 300DH | 12301 (0x300D) | HR | AI 2 | U16 | ×0.01 V | R | 03 | Range 0 ~ 10 V p.132~134 |
| 300EH | 12302 (0x300E) | HR | AI 3 | S16 | ×0.01 V | R | 03 | Range -10 ~ 10 V p.132~134 |
Notes
- Printed page = PDF page − 5.
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- invt/gd20.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- Goodrive20 Series VFD Manual (GD20 VFD Manual) — INVT, V2.1 (2025-09) · P00 printed pp.31-32, P07.27 p.73, P14 pp.99-101, 7 communication protocol pp.117-140 (address table 7.4.2 pp.132-134, examples 7.5 pp.138-140) · checked 2026-11-01