An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 9600 bps — options: 9600, 19200, 38400, 57600, 76800, 93750, 115200 |
| Data · parity · stop | 8 · Even · 1 |
| Slave ID (factory) | 1 (1~247) |
| Max per request | 125 registers |
| Manual address style | 40001/30001 style (wire address + 1, first digit = table) |
- The mapping table lists 'Register No.' in two columns: 0 ↔ 40001, 99 ↔ 40100 (pp.177-180). The first column is the wire address (= number − 40001). There is no numeric frame example; this two-column table is the evidence.
- Defaults: P2023 = 1 (USS); Modbus = 2, then power-cycle. P2010 = 6 (9600 bps), P2021 address 1 (1-247), P2034 = 2 (even parity), P2035 = 1 (1 stop bit), P2022 reply timeout 1000 ms (p.176, parameter list p.275). With 2 stop bits parity must be none.
- Only FC 03, 06, 16. Up to 125 registers per read and 123 per write (pp.174-175). For control set P0700 = 5 and P1000 = 5.
Registers (42)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 40001 | 0 (0x0000) | HR | Watchdog time | U16 | ms | R/W | 03·06·10 | Range 0 ~ 65535 ms p.177 |
| 40003 | 2 (0x0002) | HR | Frequency setpoint (HSW) | U16 | ×0.01 % | R/W | 03·06·10 | Range 0 ~ 100 % p.177 |
| 40004 | 3 (0x0003) | HR | Run enable (STW:3) | U16 | R/W | 03·06·10 | 0 = 0 · 1 = 1 p.177 | |
| 40005 | 4 (0x0004) | HR | Forward/reverse command (STW:11) | U16 | R/W | 03·06·10 | 0 = 0 · 1 = 1 p.177 | |
| 40006 | 5 (0x0005) | HR | Start command (STW:0) | U16 | R/W | 03·06·10 | 0 = 0 · 1 = 1 p.177 | |
| 40007 | 6 (0x0006) | HR | Fault acknowledgement (STW:7) | U16 | R/W | 03·06·10 | 0 = 0 · 1 = 1 p.177 | |
| 40010 | 9 (0x0009) | HR | Current limit (P0640) | U16 | ×0.1 % | R/W | 03·06·10 | Range 10 ~ 400 % p.177 |
| 40011 | 10 (0x000A) | HR | Acceleration time (P1120) | U16 | ×0.01 s | R/W | 03·06·10 | Range 0 ~ 650 s p.177 |
| 40012 | 11 (0x000B) | HR | Deceleration time (P1121) | U16 | ×0.01 s | R/W | 03·06·10 | Range 0 ~ 650 s p.177 |
| 40016 | 15 (0x000F) | HR | Reference frequency (P2000) | U16 | ×0.01 Hz | R/W | 03·06·10 | Range 1 ~ 550 Hz p.177 |
| 40024 | 23 (0x0017) | HR | Frequency output (r0024) | S16 | ×0.01 Hz | R | 03 | p.178 |
| 40025 | 24 (0x0018) | HR | Speed (r0022) | S16 | rpm | R | 03 | p.178 |
| 40026 | 25 (0x0019) | HR | Current filtered (r0027) | U16 | ×0.01 A | R | 03 | p.178 |
| 40027 | 26 (0x001A) | HR | Torque (r0031) | S16 | ×0.01 Nm | R | 03 | p.178 |
| 40028 | 27 (0x001B) | HR | Actual power (r0032) | U16 | ×0.01 kW | R | 03 | p.178 |
| 40029 | 28 (0x001C) | HR | Total kWh (r0039) | U16 | kWh | R | 03 | p.178 |
| 40030 | 29 (0x001D) | HR | DC bus voltage (r0026) | U16 | V | R | 03 | p.178 |
| 40031 | 30 (0x001E) | HR | Reference (r0020) | S16 | ×0.01 Hz | R | 03 | p.178 |
| 40033 | 32 (0x0020) | HR | Voltage output (r0025) | U16 | V | R | 03 | p.178 |
| 40034 | 33 (0x0021) | HR | Forward/reverse (ZSW:14) | U16 | R | 03 | FWD / REV p.178 | |
| 40035 | 34 (0x0022) | HR | Stop/run (ZSW:2) | U16 | R | 03 | STOP / RUN p.178 | |
| 40038 | 37 (0x0025) | HR | Enabled (ZSW:0) | U16 | R | 03 | ON / OFF p.178 | |
| 40039 | 38 (0x0026) | HR | Ready to run (ZSW:1) | U16 | R | 03 | READY / OFF p.178 | |
| 40054 | 53 (0x0035) | HR | Fault (ZSW:3) | U16 | R | 03 | FAULT / OFF p.178 | |
| 40055 | 54 (0x0036) | HR | Last fault (r0947[0]) | U16 | R | 03 | Range 0 ~ 32767 p.178 | |
| 40059 | 58 (0x003A) | HR | Warning (ZSW:7) | U16 | R | 03 | WARN / OK p.178 | |
| 40060 | 59 (0x003B) | HR | Last warning (r2110) | U16 | R | 03 | Range 0 ~ 32767 p.178 | |
| 40100 | 99 (0x0063) | HR | Control word STW (PZD 1) | U16 | R/W | 03·06·10 | Bit meanings: r0054 (parameter list) p.178 | |
| 40101 | 100 (0x0064) | HR | Speed setpoint HSW (PZD 2) | U16 | R/W | 03·06·10 | p.179 | |
| 40110 | 109 (0x006D) | HR | Status word ZSW (PZD 1) | U16 | R | 03 | Bit meanings: r0052 (parameter list) p.179 | |
| 40111 | 110 (0x006E) | HR | Actual speed HIW (PZD 2) | U16 | R | 03 | p.179 | |
| 40240 | 239 (0x00EF) | HR | Digital input 1 (r0722.0) | U16 | R | 03 | HIGH / LOW p.179 | |
| 40241 | 240 (0x00F0) | HR | Digital input 2 (r0722.1) | U16 | R | 03 | HIGH / LOW p.179 | |
| 40260 | 259 (0x0103) | HR | Analog input 1 (r0754[0]) | S16 | ×0.01 % | R | 03 | Range -300 ~ 300 % p.179 |
| 40300 | 299 (0x012B) | HR | Inverter model (r0201) | U16 | R | 03 | p.179 | |
| 40301 | 300 (0x012C) | HR | Inverter version (r0018) | U16 | ×0.01 | R | 03 | p.179 |
| 40342 | 341 (0x0155) | HR | Frequency output (r0024) | S16 | ×0.01 Hz | R | 03 | p.179 |
| 40345 | 344 (0x0158) | HR | Current filtered (r0027) | U16 | ×0.01 A | R | 03 | p.179 |
| 40347 | 346 (0x015A) | HR | Actual power (r0032) | U16 | ×0.01 kW | R | 03 | p.179 |
| 40400 | 399 (0x018F) | HR | Fault 1 (r0947[0]) | U16 | R | 03 | Range 0 ~ 32767 p.179 | |
| 40408 | 407 (0x0197) | HR | Warning (r2110[0]) | U16 | R | 03 | Range 0 ~ 32767 p.180 | |
| 40499 | 498 (0x01F2) | HR | Parameter error code | U16 | R | 03 | Range 0 ~ 254 p.180 |
Notes
- 'Scaling factor' means raw = value × factor, so scale is its inverse (100 → 0.01). Some values appear twice (e.g. 40055 and 40400 last fault, 40024 and 40342 output frequency). Texts like 'HIGH/LOW' are the two states of one bit.
- The newer compact instructions (12/2024) list 40026, 40100, 40322, 40342-40348, 40400 etc. with the same numbers and scaling (p.31). The 05/2022 full instructions could not be downloaded (403), so the 01/2018 edition is used.
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- siemens/sinamics-v20.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.