Siemens SINAMICS V20 Modbus register map

The RS485 factory protocol is USS; set P2023 = 2 and power-cycle for Modbus. Holding registers only (FC 03, 06, 16), 40001-style numbers. Control via 40100 STW / 40101 HSW or the per-bit commands 40004-40007. · Inverter (VFD)

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)9600 bps — options: 9600, 19200, 38400, 57600, 76800, 93750, 115200
Data · parity · stop8 · Even · 1
Slave ID (factory)1 (1~247)
Max per request125 registers
Manual address style40001/30001 style (wire address + 1, first digit = table)

Registers (42)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

42

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
400010 (0x0000)HRWatchdog timeU16msR/W03·06·10
Range 0 ~ 65535 ms
p.177
400032 (0x0002)HRFrequency setpoint (HSW)U16×0.01 %R/W03·06·10
Range 0 ~ 100 %
p.177
400043 (0x0003)HRRun enable (STW:3)U16R/W03·06·10
0 = 0 · 1 = 1
p.177
400054 (0x0004)HRForward/reverse command (STW:11)U16R/W03·06·10
0 = 0 · 1 = 1
p.177
400065 (0x0005)HRStart command (STW:0)U16R/W03·06·10
0 = 0 · 1 = 1
p.177
400076 (0x0006)HRFault acknowledgement (STW:7)U16R/W03·06·10
0 = 0 · 1 = 1
p.177
400109 (0x0009)HRCurrent limit (P0640)U16×0.1 %R/W03·06·10
Range 10 ~ 400 %
p.177
4001110 (0x000A)HRAcceleration time (P1120)U16×0.01 sR/W03·06·10
Range 0 ~ 650 s
p.177
4001211 (0x000B)HRDeceleration time (P1121)U16×0.01 sR/W03·06·10
Range 0 ~ 650 s
p.177
4001615 (0x000F)HRReference frequency (P2000)U16×0.01 HzR/W03·06·10
Range 1 ~ 550 Hz
p.177
4002423 (0x0017)HRFrequency output (r0024)S16×0.01 HzR03
p.178
4002524 (0x0018)HRSpeed (r0022)S16rpmR03
p.178
4002625 (0x0019)HRCurrent filtered (r0027)U16×0.01 AR03
p.178
4002726 (0x001A)HRTorque (r0031)S16×0.01 NmR03
p.178
4002827 (0x001B)HRActual power (r0032)U16×0.01 kWR03
p.178
4002928 (0x001C)HRTotal kWh (r0039)U16kWhR03
p.178
4003029 (0x001D)HRDC bus voltage (r0026)U16VR03
p.178
4003130 (0x001E)HRReference (r0020)S16×0.01 HzR03
p.178
4003332 (0x0020)HRVoltage output (r0025)U16VR03
p.178
4003433 (0x0021)HRForward/reverse (ZSW:14)U16R03
FWD / REV
p.178
4003534 (0x0022)HRStop/run (ZSW:2)U16R03
STOP / RUN
p.178
4003837 (0x0025)HREnabled (ZSW:0)U16R03
ON / OFF
p.178
4003938 (0x0026)HRReady to run (ZSW:1)U16R03
READY / OFF
p.178
4005453 (0x0035)HRFault (ZSW:3)U16R03
FAULT / OFF
p.178
4005554 (0x0036)HRLast fault (r0947[0])U16R03
Range 0 ~ 32767
p.178
4005958 (0x003A)HRWarning (ZSW:7)U16R03
WARN / OK
p.178
4006059 (0x003B)HRLast warning (r2110)U16R03
Range 0 ~ 32767
p.178
4010099 (0x0063)HRControl word STW (PZD 1)U16R/W03·06·10
Bit meanings: r0054 (parameter list)
p.178
40101100 (0x0064)HRSpeed setpoint HSW (PZD 2)U16R/W03·06·10
p.179
40110109 (0x006D)HRStatus word ZSW (PZD 1)U16R03
Bit meanings: r0052 (parameter list)
p.179
40111110 (0x006E)HRActual speed HIW (PZD 2)U16R03
p.179
40240239 (0x00EF)HRDigital input 1 (r0722.0)U16R03
HIGH / LOW
p.179
40241240 (0x00F0)HRDigital input 2 (r0722.1)U16R03
HIGH / LOW
p.179
40260259 (0x0103)HRAnalog input 1 (r0754[0])S16×0.01 %R03
Range -300 ~ 300 %
p.179
40300299 (0x012B)HRInverter model (r0201)U16R03
p.179
40301300 (0x012C)HRInverter version (r0018)U16×0.01R03
p.179
40342341 (0x0155)HRFrequency output (r0024)S16×0.01 HzR03
p.179
40345344 (0x0158)HRCurrent filtered (r0027)U16×0.01 AR03
p.179
40347346 (0x015A)HRActual power (r0032)U16×0.01 kWR03
p.179
40400399 (0x018F)HRFault 1 (r0947[0])U16R03
Range 0 ~ 32767
p.179
40408407 (0x0197)HRWarning (r2110[0])U16R03
Range 0 ~ 32767
p.180
40499498 (0x01F2)HRParameter error codeU16R03
Range 0 ~ 254
p.180

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).

Download JSON

Sources