An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 19200 bps — options: 9600, 19200, 38400 |
| Data · parity · stop | 8 · Even · 1 |
| Slave ID (factory) | 1 (1~247) |
| Manual address style | Wire address as is (0-based) |
- Addressing: every parameter is a 16-bit holding register with zero offset — parameter number = register address (P0100 = 100 = 0064h, P0680 = 680) (5.2.1, p.5-1). Some masters add a 40000 base.
- Defaults: P0308 = 1, P0310 = 1 (19200 bps), P0311 = 1 (8E1), P0312 = 2 (Modbus RTU) (pp.4-4 to 4-6). FC 01, 02, 03, 04, 05, 06, 0F, 10 and 2B (Table 5.1). Values are integers without decimals; decimal places are in the programming manual (p.5-2).
Registers (19)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| P0220 | 220 (0x00DC) | HR | LOC/REM selection source | U16 | R/W | 03·06·10 | 0 = Always LOC · 1 = Always REM · 2 = HMI key LOC (default) · 3 = HMI key REM · 4 = DIx · 5 = Serial/USB LOC · 6 = Serial/USB REM p.4-1 | |
| P0222 | 222 (0x00DE) | HR | REM reference selection | U16 | R/W | 03·06·10 | Default 0. 9 uses P0683 0 = HMI keys · 1 = AI1 · 9 = Serial/USB · 11 = CO/DN/PB/Eth · 12 = SoftPLC p.4-2 | |
| P0226 | 226 (0x00E2) | HR | REM rotation selection | U16 | R/W | 03·06·10 | 0 = Clockwise · 1 = Counterclockwise · 2 = HMI key (FWD) (default) · 5 = Serial/USB (F) · 6 = Serial/USB (R) p.4-3 | |
| P0227 | 227 (0x00E3) | HR | REM run/stop selection | U16 | R/W | 03·06·10 | 0 = HMI keys (default) · 1 = DIx · 2 = Serial/USB · 4 = CO/DN/PB/Eth · 5 = SoftPLC p.4-3 | |
| P0308 | 308 (0x0134) | HR | Serial address | U16 | R/W | 03·06·10 | Default 1 Range 0 ~ 255 p.4-4 | |
| P0310 | 310 (0x0136) | HR | Serial baud rate | U16 | R/W | 03·06·10 | 0 = 9600 bit/s · 1 = 19200 bit/s (default) · 2 = 38400 bit/s p.4-5 | |
| P0311 | 311 (0x0137) | HR | Serial bytes configuration | U16 | R/W | 03·06·10 | 0 = 8 bits, no, 1 · 1 = 8 bits, even, 1 (default) · 2 = 8 bits, odd, 1 · 3 = 8 bits, no, 2 · 4 = 8 bits, even, 2 · 5 = 8 bits, odd, 2 p.4-5 | |
| P0312 | 312 (0x0138) | HR | Serial protocol | U16 | R/W | 03·06·10 | 0 = HMI-1 · 1 = SymbiNet-1 · 2 = Modbus RTU-1 (default) · 3 = BACnet-1 p.4-6 | |
| P0313 | 313 (0x0139) | HR | Communication error action | U16 | R/W | 03·06·10 | 0 = Inactive · 1 = Ramp stop (default) · 2 = General disable · 3 = Go to LOC · 4 = LOC keep enabled · 5 = Cause fault p.4-7 | |
| P0314 | 314 (0x013A) | HR | Serial watchdog | U16 | R/W | 03·06·10 | 0 = disabled (default); on timeout alarm A128 and the P0313 action Range 0 ~ 999 p.4-7 | |
| P0316 | 316 (0x013C) | HR | Serial interface status | U16 | R | 03 | 0 = Inactive · 1 = Active · 2 = Watchdog error p.4-8 | |
| P0680 | 680 (0x02A8) | HR | Logical status | U16 | R | 03 | b1 Run command · b2 Fire mode · b4 Quick stop · b5 2nd ramp · b6 Config. mode · b7 Alarm · b8 Running · b9 Enabled · b10 Forward · b11 JOG · b12 Remote · b13 Undervoltage · b14 Automatic PID · b15 Fault p.4-8~4-9 | |
| P0681 | 681 (0x02A9) | HR | Speed at 13 bits (output frequency scale) | S16 | R | 03 | 8192 = motor rated frequency (P0403); negative = reverse p.4-9 | |
| P0682 | 682 (0x02AA) | HR | Serial/USB control | U16 | R/W | 03·06·10 | b0 Run (1) / stop (0) · b1 General enable · b2 Run forward (0 = reverse) · b3 JOG enable · b4 Remote · b5 2nd ramp · b6 Quick stop · b7 Fault reset p.4-10~4-11 | |
| P0683 | 683 (0x02AB) | HR | Serial/USB speed reference (13 bits) | S16 | R/W | 03·06·10 | 8192 = rated frequency (P0403). E.g. 30 Hz on a 60 Hz motor = 4096 p.4-11~4-12 | |
| P0695 | 695 (0x02B7) | HR | DOx value | U16 | R/W | 03·06·10 | b0 DO1 · b1 DO2 · b2 DO3 · b3 DO4 · b4 DO5 p.4-12 | |
| P0696 | 696 (0x02B8) | HR | AOx value 1 | S16 | R/W | 03·06·10 | 7FFFh (32767) = 100 % p.4-13 | |
| P0697 | 697 (0x02B9) | HR | AOx value 2 | S16 | R/W | 03·06·10 | 7FFFh (32767) = 100 % p.4-13 | |
| P0698 | 698 (0x02BA) | HR | AOx value 3 | S16 | R/W | 03·06·10 | 7FFFh (32767) = 100 %. On CFW503 analog output 3 is the frequency output (FO) p.4-13 |
Notes
- To control via the network set the sources in P0220-P0228 to Serial/USB (p.4-1 onward). Monitoring parameters (output current etc.) are left out because their decimals are not in this document. Pages are printed '4-1' style (PDF p.15 = 4-1).
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- weg/cfw503.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- Modbus RTU CFW503 User's Guide — WEG, 10012735606 Revision 00 (05/2025) · 4 parameters printed pp.4-1 to 4-13, 5 Modbus RTU slave pp.5-1 to 5-2 · checked 2026-11-01