WEG CFW503 Modbus register map

Parameter number = holding register address (zero offset). Status P0680, control word P0682, speed reference P0683 (8192 = rated frequency). · Inverter (VFD)

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)19200 bps — options: 9600, 19200, 38400
Data · parity · stop8 · Even · 1
Slave ID (factory)1 (1~247)
Manual address styleWire address as is (0-based)

Registers (19)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

19

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
P0220220 (0x00DC)HRLOC/REM selection sourceU16R/W03·06·10
0 = Always LOC · 1 = Always REM · 2 = HMI key LOC (default) · 3 = HMI key REM · 4 = DIx · 5 = Serial/USB LOC · 6 = Serial/USB REM
p.4-1
P0222222 (0x00DE)HRREM reference selectionU16R/W03·06·10
Default 0. 9 uses P0683
0 = HMI keys · 1 = AI1 · 9 = Serial/USB · 11 = CO/DN/PB/Eth · 12 = SoftPLC
p.4-2
P0226226 (0x00E2)HRREM rotation selectionU16R/W03·06·10
0 = Clockwise · 1 = Counterclockwise · 2 = HMI key (FWD) (default) · 5 = Serial/USB (F) · 6 = Serial/USB (R)
p.4-3
P0227227 (0x00E3)HRREM run/stop selectionU16R/W03·06·10
0 = HMI keys (default) · 1 = DIx · 2 = Serial/USB · 4 = CO/DN/PB/Eth · 5 = SoftPLC
p.4-3
P0308308 (0x0134)HRSerial addressU16R/W03·06·10
Default 1
Range 0 ~ 255
p.4-4
P0310310 (0x0136)HRSerial baud rateU16R/W03·06·10
0 = 9600 bit/s · 1 = 19200 bit/s (default) · 2 = 38400 bit/s
p.4-5
P0311311 (0x0137)HRSerial bytes configurationU16R/W03·06·10
0 = 8 bits, no, 1 · 1 = 8 bits, even, 1 (default) · 2 = 8 bits, odd, 1 · 3 = 8 bits, no, 2 · 4 = 8 bits, even, 2 · 5 = 8 bits, odd, 2
p.4-5
P0312312 (0x0138)HRSerial protocolU16R/W03·06·10
0 = HMI-1 · 1 = SymbiNet-1 · 2 = Modbus RTU-1 (default) · 3 = BACnet-1
p.4-6
P0313313 (0x0139)HRCommunication error actionU16R/W03·06·10
0 = Inactive · 1 = Ramp stop (default) · 2 = General disable · 3 = Go to LOC · 4 = LOC keep enabled · 5 = Cause fault
p.4-7
P0314314 (0x013A)HRSerial watchdogU16R/W03·06·10
0 = disabled (default); on timeout alarm A128 and the P0313 action
Range 0 ~ 999
p.4-7
P0316316 (0x013C)HRSerial interface statusU16R03
0 = Inactive · 1 = Active · 2 = Watchdog error
p.4-8
P0680680 (0x02A8)HRLogical statusU16R03
b1 Run command · b2 Fire mode · b4 Quick stop · b5 2nd ramp · b6 Config. mode · b7 Alarm · b8 Running · b9 Enabled · b10 Forward · b11 JOG · b12 Remote · b13 Undervoltage · b14 Automatic PID · b15 Fault
p.4-8~4-9
P0681681 (0x02A9)HRSpeed at 13 bits (output frequency scale)S16R03
8192 = motor rated frequency (P0403); negative = reverse
p.4-9
P0682682 (0x02AA)HRSerial/USB controlU16R/W03·06·10
b0 Run (1) / stop (0) · b1 General enable · b2 Run forward (0 = reverse) · b3 JOG enable · b4 Remote · b5 2nd ramp · b6 Quick stop · b7 Fault reset
p.4-10~4-11
P0683683 (0x02AB)HRSerial/USB speed reference (13 bits)S16R/W03·06·10
8192 = rated frequency (P0403). E.g. 30 Hz on a 60 Hz motor = 4096
p.4-11~4-12
P0695695 (0x02B7)HRDOx valueU16R/W03·06·10
b0 DO1 · b1 DO2 · b2 DO3 · b3 DO4 · b4 DO5
p.4-12
P0696696 (0x02B8)HRAOx value 1S16R/W03·06·10
7FFFh (32767) = 100 %
p.4-13
P0697697 (0x02B9)HRAOx value 2S16R/W03·06·10
7FFFh (32767) = 100 %
p.4-13
P0698698 (0x02BA)HRAOx value 3S16R/W03·06·10
7FFFh (32767) = 100 %. On CFW503 analog output 3 is the frequency output (FO)
p.4-13

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).