PortDock

Hitachi WJ-C1 Modbus register map

Successor to the WJ200. Built-in RS485 Modbus RTU. Coil 0001h run command, register 0001h F001 frequency, 1001h d001 output frequency, 1003h output current, 1011h output voltage. Frame address = number - 1 · Inverter (VFD) · WJ Series C1

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)9600 bps — options: 2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200
Data · parity · stop8 · None · 1
Slave ID (factory)1 (1~247)
32-bit orderABCD
Max per request16 registers
Manual address style1-based numbers (wire address + 1)

Registers (53)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

53

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
0001h0 (0x0000)CORun command (1 run, 0 stop)BITR/W01·05·0F
PDF p.430
0002h1 (0x0001)CORotation direction command (1 reverse, 0 forward)BITR/W01·05·0F
PDF p.430
0003h2 (0x0002)COExternal trip (EXT)BITR/W01·05·0F
PDF p.430
0004h3 (0x0003)COTrip reset (RS)BITR/W01·05·0F
PDF p.430
0007h6 (0x0006)COIntelligent input terminal [1]BITR/W01·05·0F
PDF p.430
0008h7 (0x0007)COIntelligent input terminal [2]BITR/W01·05·0F
PDF p.430
0009h8 (0x0008)COIntelligent input terminal [3]BITR/W01·05·0F
PDF p.430
000Ah9 (0x0009)COIntelligent input terminal [4]BITR/W01·05·0F
PDF p.430
000Bh10 (0x000A)COIntelligent input terminal [5]BITR/W01·05·0F
PDF p.430
000Ch11 (0x000B)COIntelligent input terminal [6]BITR/W01·05·0F
PDF p.430
000Dh12 (0x000C)COIntelligent input terminal [7]BITR/W01·05·0F
PDF p.430
000Fh14 (0x000E)COOperation statusBITR01
PDF p.430
0010h15 (0x000F)CORotation directionBITR01
PDF p.430
0011h16 (0x0010)COInverter readyBITR01
PDF p.430
0013h18 (0x0012)CORUN (running)BITR01
PDF p.430
0014h19 (0x0013)COFA1 constant speed reachedBITR01
PDF p.430
0015h20 (0x0014)COFA2 set frequency overreachedBITR01
PDF p.430
0016h21 (0x0015)COOL overload noticeBITR01
PDF p.430
0018h23 (0x0017)COAL alarm signalBITR01
PDF p.430
001Ah25 (0x0019)COOTQ over-torqueBITR01
PDF p.430
001Ch27 (0x001B)COUV undervoltageBITR01
PDF p.430
001Dh28 (0x001C)COTRQ torque limitedBITR01
PDF p.430
0028h39 (0x0027)COZS zero speed detectionBITR01
PDF p.430
0001h (high), 0002h (low)0 (0x0000)HRFrequency setting or monitor (F001)U32 ABCD×0.01 HzR/W03·10
PDF p.437
0003h2 (0x0002)HRInverter state AU16R03
0 = Initial status · 2 = Stopping · 3 = Running · 4 = Free-run stop · 5 = Jogging · 6 = DC braking · 7 = Retrying · 8 = Tripping · 9 = Undervoltage
PDF p.432
0004h3 (0x0003)HRInverter status BU16R03
0 = Stop · 1 = Running · 2 = Trip
PDF p.432
0005h4 (0x0004)HRInverter status CU16R03
PDF p.432
0006h5 (0x0005)HRPID feedbackU16×0.01 %R/W03·06·10
Range 0 ~ 100 %
PDF p.432
0011h16 (0x0010)HRTrip count (d080)U16R03
PDF p.435
0900h2303 (0x08FF)HRWrite EEPROMU16W06·10
PDF p.432
1001h (high), 1002h (low)4096 (0x1000)HROutput frequency (d001)U32 ABCD×0.01 HzR03
PDF p.434
1003h4098 (0x1002)HROutput current (d002)U16×0.01 AR03
PDF p.434
1004h4099 (0x1003)HRRotation direction (d003)U16R03
0 = Stopping · 1 = Forward rotation · 2 = Reverse rotation
PDF p.434
1005h (high), 1006h (low)4100 (0x1004)HRPID feedback (d004)U32 ABCD×0.1R03
PDF p.434
1007h4102 (0x1006)HRInput terminal monitor (d005)U16R03
PDF p.434
1008h4103 (0x1007)HROutput terminal monitor (d006)U16R03
PDF p.434
100Bh (high), 100Ch (low)4106 (0x100A)HRDetect speed (d008)S32 ABCD×0.01 HzR03
PDF p.434
1010h4111 (0x100F)HROutput torque (d012)S16%R03
PDF p.434
1011h4112 (0x1010)HROutput voltage (d013)U16×0.1 VR03
PDF p.434
1012h4113 (0x1011)HRInput power (d014)U16×0.1 kWR03
PDF p.434
101Dh4124 (0x101C)HRLife assessment monitor (d022)U16R03
PDF p.435
1057h4182 (0x1056)HRInverter mode (d060)U16R03
PDF p.435
1103h (high), 1104h (low)4354 (0x1102)HRAcceleration time 1 (F002)U32 ABCD×0.01 sR/W03·10
PDF p.437
1105h (high), 1106h (low)4356 (0x1104)HRDeceleration time 1 (F003)U32 ABCD×0.01 sR/W03·10
PDF p.437
1107h4358 (0x1106)HRKeypad RUN direction (F004)U16R/W03·06·10
PDF p.437
1201h4608 (0x1200)HRFrequency source (A001)U16R/W03·06·10
PDF p.438
1202h4609 (0x1201)HRRun command source (A002)U16R/W03·06·10
1 = Control terminal · 2 = Digital operator · 3 = Modbus · 4 = Option
PDF p.438
1203h4610 (0x1202)HRBase frequency (A003)U16×0.1 HzR/W03·06·10
PDF p.438
1204h4611 (0x1203)HRMaximum frequency (A004)U16×0.1 HzR/W03·06·10
PDF p.438
144Bh5194 (0x144A)HRBaud rate (C071)U16R/W03·06·10
3 = 2400 bps · 4 = 4800 bps · 5 = 9600 bps · 6 = 19200 bps · 7 = 38400 bps · 8 = 57600 bps · 9 = 76800 bps · 10 = 115200 bps
PDF p.454
144Ch5195 (0x144B)HRNode address (C072)U16R/W03·06·10
Range 1 ~ 247
PDF p.454
144Eh5197 (0x144D)HRParity (C074)U16R/W03·06·10
0 = No parity · 1 = Even · 2 = Odd
PDF p.454
144Fh5198 (0x144E)HRStop bit (C075)U16R/W03·06·10
1 = 1 bit · 2 = 2 bits
PDF p.454

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).

Download JSON