An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 9600 bps — options: 2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200 |
| Data · parity · stop | 8 · None · 1 |
| Slave ID (factory) | 1 (1~247) |
| 32-bit order | ABCD |
| Max per request | 16 registers |
| Manual address style | 1-based numbers (wire address + 1) |
- Addressing: register start number in the frame = register number - 1 (11.2.2). The read example (PDF p.341) 01 03 00 11 00 06 95 CD reads 6 registers from 0012h (latest trip information).
- Factory settings: C071 05 = 9600 bps, C072 address 1, C074 00 = no parity, C075 01 = 1 stop bit (PDF p.454). Function codes 01h, 03h, 05h, 06h, 08h, 0Fh and 10h; up to 16 registers or 32 coils (PDF pp.335-336).
Registers (53)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 0001h | 0 (0x0000) | CO | Run command (1 run, 0 stop) | BIT | R/W | 01·05·0F | PDF p.430 | |
| 0002h | 1 (0x0001) | CO | Rotation direction command (1 reverse, 0 forward) | BIT | R/W | 01·05·0F | PDF p.430 | |
| 0003h | 2 (0x0002) | CO | External trip (EXT) | BIT | R/W | 01·05·0F | PDF p.430 | |
| 0004h | 3 (0x0003) | CO | Trip reset (RS) | BIT | R/W | 01·05·0F | PDF p.430 | |
| 0007h | 6 (0x0006) | CO | Intelligent input terminal [1] | BIT | R/W | 01·05·0F | PDF p.430 | |
| 0008h | 7 (0x0007) | CO | Intelligent input terminal [2] | BIT | R/W | 01·05·0F | PDF p.430 | |
| 0009h | 8 (0x0008) | CO | Intelligent input terminal [3] | BIT | R/W | 01·05·0F | PDF p.430 | |
| 000Ah | 9 (0x0009) | CO | Intelligent input terminal [4] | BIT | R/W | 01·05·0F | PDF p.430 | |
| 000Bh | 10 (0x000A) | CO | Intelligent input terminal [5] | BIT | R/W | 01·05·0F | PDF p.430 | |
| 000Ch | 11 (0x000B) | CO | Intelligent input terminal [6] | BIT | R/W | 01·05·0F | PDF p.430 | |
| 000Dh | 12 (0x000C) | CO | Intelligent input terminal [7] | BIT | R/W | 01·05·0F | PDF p.430 | |
| 000Fh | 14 (0x000E) | CO | Operation status | BIT | R | 01 | PDF p.430 | |
| 0010h | 15 (0x000F) | CO | Rotation direction | BIT | R | 01 | PDF p.430 | |
| 0011h | 16 (0x0010) | CO | Inverter ready | BIT | R | 01 | PDF p.430 | |
| 0013h | 18 (0x0012) | CO | RUN (running) | BIT | R | 01 | PDF p.430 | |
| 0014h | 19 (0x0013) | CO | FA1 constant speed reached | BIT | R | 01 | PDF p.430 | |
| 0015h | 20 (0x0014) | CO | FA2 set frequency overreached | BIT | R | 01 | PDF p.430 | |
| 0016h | 21 (0x0015) | CO | OL overload notice | BIT | R | 01 | PDF p.430 | |
| 0018h | 23 (0x0017) | CO | AL alarm signal | BIT | R | 01 | PDF p.430 | |
| 001Ah | 25 (0x0019) | CO | OTQ over-torque | BIT | R | 01 | PDF p.430 | |
| 001Ch | 27 (0x001B) | CO | UV undervoltage | BIT | R | 01 | PDF p.430 | |
| 001Dh | 28 (0x001C) | CO | TRQ torque limited | BIT | R | 01 | PDF p.430 | |
| 0028h | 39 (0x0027) | CO | ZS zero speed detection | BIT | R | 01 | PDF p.430 | |
| 0001h (high), 0002h (low) | 0 (0x0000) | HR | Frequency setting or monitor (F001) | U32 ABCD | ×0.01 Hz | R/W | 03·10 | PDF p.437 |
| 0003h | 2 (0x0002) | HR | Inverter state A | U16 | R | 03 | 0 = Initial status · 2 = Stopping · 3 = Running · 4 = Free-run stop · 5 = Jogging · 6 = DC braking · 7 = Retrying · 8 = Tripping · 9 = Undervoltage PDF p.432 | |
| 0004h | 3 (0x0003) | HR | Inverter status B | U16 | R | 03 | 0 = Stop · 1 = Running · 2 = Trip PDF p.432 | |
| 0005h | 4 (0x0004) | HR | Inverter status C | U16 | R | 03 | PDF p.432 | |
| 0006h | 5 (0x0005) | HR | PID feedback | U16 | ×0.01 % | R/W | 03·06·10 | Range 0 ~ 100 % PDF p.432 |
| 0011h | 16 (0x0010) | HR | Trip count (d080) | U16 | R | 03 | PDF p.435 | |
| 0900h | 2303 (0x08FF) | HR | Write EEPROM | U16 | W | 06·10 | PDF p.432 | |
| 1001h (high), 1002h (low) | 4096 (0x1000) | HR | Output frequency (d001) | U32 ABCD | ×0.01 Hz | R | 03 | PDF p.434 |
| 1003h | 4098 (0x1002) | HR | Output current (d002) | U16 | ×0.01 A | R | 03 | PDF p.434 |
| 1004h | 4099 (0x1003) | HR | Rotation direction (d003) | U16 | R | 03 | 0 = Stopping · 1 = Forward rotation · 2 = Reverse rotation PDF p.434 | |
| 1005h (high), 1006h (low) | 4100 (0x1004) | HR | PID feedback (d004) | U32 ABCD | ×0.1 | R | 03 | PDF p.434 |
| 1007h | 4102 (0x1006) | HR | Input terminal monitor (d005) | U16 | R | 03 | PDF p.434 | |
| 1008h | 4103 (0x1007) | HR | Output terminal monitor (d006) | U16 | R | 03 | PDF p.434 | |
| 100Bh (high), 100Ch (low) | 4106 (0x100A) | HR | Detect speed (d008) | S32 ABCD | ×0.01 Hz | R | 03 | PDF p.434 |
| 1010h | 4111 (0x100F) | HR | Output torque (d012) | S16 | % | R | 03 | PDF p.434 |
| 1011h | 4112 (0x1010) | HR | Output voltage (d013) | U16 | ×0.1 V | R | 03 | PDF p.434 |
| 1012h | 4113 (0x1011) | HR | Input power (d014) | U16 | ×0.1 kW | R | 03 | PDF p.434 |
| 101Dh | 4124 (0x101C) | HR | Life assessment monitor (d022) | U16 | R | 03 | PDF p.435 | |
| 1057h | 4182 (0x1056) | HR | Inverter mode (d060) | U16 | R | 03 | PDF p.435 | |
| 1103h (high), 1104h (low) | 4354 (0x1102) | HR | Acceleration time 1 (F002) | U32 ABCD | ×0.01 s | R/W | 03·10 | PDF p.437 |
| 1105h (high), 1106h (low) | 4356 (0x1104) | HR | Deceleration time 1 (F003) | U32 ABCD | ×0.01 s | R/W | 03·10 | PDF p.437 |
| 1107h | 4358 (0x1106) | HR | Keypad RUN direction (F004) | U16 | R/W | 03·06·10 | PDF p.437 | |
| 1201h | 4608 (0x1200) | HR | Frequency source (A001) | U16 | R/W | 03·06·10 | PDF p.438 | |
| 1202h | 4609 (0x1201) | HR | Run command source (A002) | U16 | R/W | 03·06·10 | 1 = Control terminal · 2 = Digital operator · 3 = Modbus · 4 = Option PDF p.438 | |
| 1203h | 4610 (0x1202) | HR | Base frequency (A003) | U16 | ×0.1 Hz | R/W | 03·06·10 | PDF p.438 |
| 1204h | 4611 (0x1203) | HR | Maximum frequency (A004) | U16 | ×0.1 Hz | R/W | 03·06·10 | PDF p.438 |
| 144Bh | 5194 (0x144A) | HR | Baud rate (C071) | U16 | R/W | 03·06·10 | 3 = 2400 bps · 4 = 4800 bps · 5 = 9600 bps · 6 = 19200 bps · 7 = 38400 bps · 8 = 57600 bps · 9 = 76800 bps · 10 = 115200 bps PDF p.454 | |
| 144Ch | 5195 (0x144B) | HR | Node address (C072) | U16 | R/W | 03·06·10 | Range 1 ~ 247 PDF p.454 | |
| 144Eh | 5197 (0x144D) | HR | Parity (C074) | U16 | R/W | 03·06·10 | 0 = No parity · 1 = Even · 2 = Odd PDF p.454 | |
| 144Fh | 5198 (0x144E) | HR | Stop bit (C075) | U16 | R/W | 03·06·10 | 1 = 1 bit · 2 = 2 bits PDF p.454 |
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- hitachi/wj-c1.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- WJ Series C1 User's Guide — Hitachi, NT361X · Communication settings PDF p.332, frame example PDF p.341, coil and register lists (chapter 18) PDF pp.430-454 · checked 2026-11-05