Schneider Electric ATV71 Modbus register map

Integrated Modbus RTU. Logical address = frame address: control word 8501/8601, frequency reference 8502, status word 3201/8603, output frequency 3202, current 3204, fault code 7121 · Inverter (VFD) · Altivar 71

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)19200 bps
Data · parity · stop8 · Even · 1
Max per request63 registers
Manual address styleWire address as is (0-based)

Registers (36)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

36

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
31023102 (0x0C1E)HRSFr switching frequencyU16×0.1 kHzR/W03·06·10
Modbus manual read example: 4 kHz = 16#0028
p.30
31033103 (0x0C1F)HRtFr maximum output frequencyU16×0.1 HzR/W03·06·10
Read example: 60 Hz = 16#0258
p.30
31043104 (0x0C20)HRHSP high speedU16×0.1 HzR/W03·06·10
Read example: 50 Hz = 16#01F4
p.30
31053105 (0x0C21)HRLSP low speedU16×0.1 HzR/W03·06·10
p.30
3201 (16#0C81)3201 (0x0C81)HRETA status word (frequency side)U16R03
Bits per the I/O profile. The same value is also at 8603
b1 Ready · b2 Running · b3 Fault · b4 Power section line supply present · b7 Alarm · b9 Command via a network · b10 Reference reached · b11 Reference outside limits · b14 Stop via STOP key · b15 Reverse rotation at output
p.86
3202 (16#0C82)3202 (0x0C82)HRrFr output frequencyS16×0.1 HzR03
p.94
3203 (16#0C83)3203 (0x0C83)HRFrH frequency reference before rampS16×0.1 HzR03
p.98
3204 (16#0C84)3204 (0x0C84)HRLCr motor currentU16×0.1 AR03
p.96
3205 (16#0C85)3205 (0x0C85)HROtr output torqueS16×0.1 %R03
Relative to nominal motor torque
p.95
3206 (16#0C86)3206 (0x0C86)HRETI extended status wordU16R03
p.88
3207 (16#0C87)3207 (0x0C87)HRULn power supply voltageU16×0.1 VR03
p.101
3208 (16#0C88)3208 (0x0C88)HRUOP motor voltageU16VR03
p.96
3209 (16#0C89)3209 (0x0C89)HRtHd drive thermal stateU16%R03
p.101
3211 (16#0C8B)3211 (0x0C8B)HROPr motor powerS16%R03
p.96
3231 (16#0C9F)3231 (0x0C9F)HRrtH total motor operating timeU16R03
Unit is given by UNT (3234)
p.102
3234 (16#0CA2)3234 (0x0CA2)HRUNT units of APH, PTH and RTHU16R03
p.96
3250 (16#0CB2)3250 (0x0CB2)HRExtended status word 1U16R03
p.88
3251 (16#0CB3)3251 (0x0CB3)HRExtended status word 2U16R03
p.89
3252 (16#0CB4)3252 (0x0CB4)HRExtended status word 3U16R03
p.89
5202 (16#1452)5202 (0x1452)HRLogic inputs statesU16R03
p.104
5212 (16#145C)5212 (0x145C)HRLogic outputs statesU16R/W03·06·10
p.104
5242 (16#147A)5242 (0x147A)HRAnalog input 1 physical valueS16×0.001 VR03
p.105
5244 (16#147C)5244 (0x147C)HRAnalog input 3 physical valueS16×0.001 mAR03
p.105
7121 (16#1BD1)7121 (0x1BD1)HRLFt Altivar fault codeU16R03
p.110
8501 (16#2135)8501 (0x2135)HRCMD control word (frequency side)U16R/W03·06·10
Also at 8601. Sits next to 8502 for block writes
p.81
8502 (16#2136)8502 (0x2136)HRLFr frequency referenceS16×0.1 HzR/W03·06·10
p.84
8503 (16#2137)8503 (0x2137)HRPID regulator setpointS16R/W03·06·10
p.85
8504 (16#2138)8504 (0x2138)HRCMI extended control wordU16R/W03·06·10
p.83
8601 (16#2199)8601 (0x2199)HRCMd control word (speed side)U16R/W03·06·10
p.81
8602 (16#219A)8602 (0x219A)HRSpeed setpointS16rpmR/W03·06·10
p.84
8603 (16#219B)8603 (0x219B)HRETA status word (speed side)U16R03
p.86
8604 (16#219C)8604 (0x219C)HROutput velocityS16rpmR03
p.94
8605 (16#219D)8605 (0x219D)HRSpeed reference before rampS16rpmR03
p.98
9001 (16#2329)9001 (0x2329)HRACC acceleration timeU16R/W03·06·10
Modbus manual write example: value 16#000D is described as ACC = 13 s
p.31
9630 (16#259E)9630 (0x259E)HRtHr motor thermal stateU16%R03
p.101
14114 (16#3722)14114 (0x3722)HRtHb DBR thermal stateU16%R03
p.101

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).