An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Data · parity · stop | — · Even · 1 |
| Slave ID (factory) | 1 (1~247) |
| 32-bit order | ABCD |
| Manual address style | 1-based numbers (wire address + 1) |
- Addressing: coil and register numbers are 1-based. The read example (MG92B102 p.21) 01 01 00 20 00 10 reads coils 33-48, the coil write example 01 05 00 40 FF 00 writes coil 65, the register read example (p.22) 01 03 0B D5 00 02 reads 3-03 (3030 → 3029), and the write example is 01 06 03 E7 00 01 (1-00 → 999). The text «3-41 → 2809 (D51 Hex)» does not match D51h = 3409, so the frame examples were followed.
- Set 8-30 = Modbus RTU [2], 8-31 address 1-247, 8-32 2400-19200, 8-33 even parity with 1 stop bit by default (p.18). Without coil 65 changes stay in RAM, and coil 65 resets at power cycle (p.16). Indexed parameters use register 009 for the index (p.16). The 8-32 default and data bits could not be confirmed, so they are left empty.
- Scale: conversion index in the parameter list (-1 = 0.1, -2 = 0.01 ..., MG92B102 p.17). 16-10 power (index 1), 16-17 speed (index 67), 15-00 hours and similar are left out because their units could not be confirmed. 2810/2910 follow the 8-42/8-43 PCD configuration.
Registers (50)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| coil 1 | 0 (0x0000) | CO | Control word bit 00: External selection LSB | BIT | R/W | 01·05·0F | p.15 | |
| coil 2 | 1 (0x0001) | CO | Control word bit 01: External selection MSB | BIT | R/W | 01·05·0F | p.15 | |
| coil 3 | 2 (0x0002) | CO | Control word bit 02: 1 = ramp, 0 = DC brake | BIT | R/W | 01·05·0F | p.15 | |
| coil 4 | 3 (0x0003) | CO | Control word bit 03: 1 = no coasting | BIT | R/W | 01·05·0F | p.15 | |
| coil 5 | 4 (0x0004) | CO | Control word bit 04: 1 = ramp, 0 = quick stop | BIT | R/W | 01·05·0F | p.15 | |
| coil 6 | 5 (0x0005) | CO | Control word bit 05: 1 = use ramp, 0 = hold output frequency | BIT | R/W | 01·05·0F | p.15 | |
| coil 7 | 6 (0x0006) | CO | Control word bit 06: 1 = start, 0 = ramp stop | BIT | R/W | 01·05·0F | p.15 | |
| coil 8 | 7 (0x0007) | CO | Control word bit 07: 1 = reset | BIT | R/W | 01·05·0F | p.15 | |
| coil 9 | 8 (0x0008) | CO | Control word bit 08: 1 = jog | BIT | R/W | 01·05·0F | p.15 | |
| coil 10 | 9 (0x0009) | CO | Control word bit 09: 1 = ramp 2, 0 = ramp 1 | BIT | R/W | 01·05·0F | p.15 | |
| coil 11 | 10 (0x000A) | CO | Control word bit 10: 1 = data valid | BIT | R/W | 01·05·0F | p.15 | |
| coil 12 | 11 (0x000B) | CO | Control word bit 11: 1 = relay 01 active | BIT | R/W | 01·05·0F | p.15 | |
| coil 13 | 12 (0x000C) | CO | Control word bit 12: 1 = relay 02 active | BIT | R/W | 01·05·0F | p.15 | |
| coil 14 | 13 (0x000D) | CO | Control word bit 13: Set-up selection LSB | BIT | R/W | 01·05·0F | p.15 | |
| coil 17 (17-32) | 16 (0x0010) | CO | Reference, first coil (17-32 = 16-bit reference) | BIT | R/W | 01·05·0F | p.14 | |
| coil 33 (33-48) | 32 (0x0020) | CO | Status word, first coil (33-48) | BIT | R | 01 | p.14, p.21 | |
| coil 49 (49-64) | 48 (0x0030) | CO | Output frequency or feedback, first coil (49-64) | BIT | R | 01 | p.14 | |
| coil 65 | 64 (0x0040) | CO | Parameter write control: 1 = RAM and EEPROM, 0 = RAM | BIT | R/W | 01·05·0F | p.14, p.16, p.21 | |
| 2810 | 2809 (0x0AF9) | HR | PCD write: control word CTW | U16 | R/W | 03·10 | p.18 | |
| 2811 | 2810 (0x0AFA) | HR | PCD write: reference REF | U16 | R/W | 03·10 | p.18 | |
| 2910 | 2909 (0x0B5D) | HR | PCD read: status word STW | U16 | R | 03 | p.18 | |
| 2911 | 2910 (0x0B5E) | HR | PCD read: main actual value MAV | U16 | R | 03 | p.18 | |
| 3-02 (3020) | 3019 (0x0BCB) | HR | Minimum reference | S32 ABCD | ×0.001 | R/W | 03·10 | PDF p.279 |
| 3-03 (3030) | 3029 (0x0BD5) | HR | Maximum reference | S32 ABCD | ×0.001 | R/W | 03·10 | PDF p.279 |
| 3-41 (3410) | 3409 (0x0D51) | HR | Ramp 1 ramp up time | U32 ABCD | ×0.01 s | R/W | 03·10 | PDF p.280 |
| 3-42 (3420) | 3419 (0x0D5B) | HR | Ramp 1 ramp down time | U32 ABCD | ×0.01 s | R/W | 03·10 | PDF p.280 |
| 8-30 (8300) | 8299 (0x206B) | HR | Protocol | U16 | R/W | 03·06·10 | 0 = FC · 2 = Modbus RTU PDF p.286 | |
| 8-31 (8310) | 8309 (0x2075) | HR | Address | U16 | R/W | 03·06·10 | Range 1 ~ 247 PDF p.286 | |
| 8-32 (8320) | 8319 (0x207F) | HR | FC port baud rate | U16 | R/W | 03·06·10 | PDF p.286 | |
| 8-33 (8330) | 8329 (0x2089) | HR | Parity / stop bits | U16 | R/W | 03·06·10 | 0 = Even parity, 1 stop bit · 1 = Odd parity, 1 stop bit · 2 = No parity, 1 stop bit PDF p.286 | |
| 16-00 (16000) | 15999 (0x3E7F) | HR | Control word | U16 | R | 03 | PDF p.294 | |
| 16-01 (16010) | 16009 (0x3E89) | HR | Reference [unit] | S32 ABCD | ×0.001 | R | 03 | PDF p.294 |
| 16-02 (16020) | 16019 (0x3E93) | HR | Reference % | S16 | ×0.1 % | R | 03 | PDF p.294 |
| 16-03 (16030) | 16029 (0x3E9D) | HR | Status word | U16 | R | 03 | PDF p.294 | |
| 16-05 (16050) | 16049 (0x3EB1) | HR | Main actual value [%] | S16 | ×0.01 % | R | 03 | PDF p.294 |
| 16-09 (16090) | 16089 (0x3ED9) | HR | Custom readout | S32 ABCD | ×0.01 | R | 03 | PDF p.294 |
| 16-12 (16120) | 16119 (0x3EF7) | HR | Motor voltage | U16 | ×0.1 V | R | 03 | PDF p.294 |
| 16-13 (16130) | 16129 (0x3F01) | HR | Frequency | U16 | ×0.1 Hz | R | 03 | PDF p.294 |
| 16-14 (16140) | 16139 (0x3F0B) | HR | Motor current | S32 ABCD | ×0.01 A | R | 03 | PDF p.294 |
| 16-15 (16150) | 16149 (0x3F15) | HR | Frequency [%] | S16 | ×0.01 % | R | 03 | PDF p.294 |
| 16-16 (16160) | 16159 (0x3F1F) | HR | Torque [Nm] | S16 | ×0.1 Nm | R | 03 | PDF p.294 |
| 16-18 (16180) | 16179 (0x3F33) | HR | Motor thermal | U16 | % | R | 03 | PDF p.294 |
| 16-22 (16220) | 16219 (0x3F5B) | HR | Torque [%] | S16 | % | R | 03 | PDF p.294 |
| 16-30 (16300) | 16299 (0x3FAB) | HR | DC link voltage | U16 | V | R | 03 | PDF p.294 |
| 16-35 (16350) | 16349 (0x3FDD) | HR | Inverter thermal | U16 | % | R | 03 | PDF p.294 |
| 16-36 (16360) | 16359 (0x3FE7) | HR | Inverter nominal current | U32 ABCD | ×0.01 A | R | 03 | PDF p.294 |
| 16-37 (16370) | 16369 (0x3FF1) | HR | Inverter maximum current | U32 ABCD | ×0.01 A | R | 03 | PDF p.294 |
| 16-60 (16600) | 16599 (0x40D7) | HR | Digital input | U16 | R | 03 | PDF p.295 | |
| 16-62 (16620) | 16619 (0x40EB) | HR | Analog input 53 | S32 ABCD | ×0.001 | R | 03 | PDF p.295 |
| 16-64 (16640) | 16639 (0x40FF) | HR | Analog input 54 | S32 ABCD | ×0.001 | R | 03 | PDF p.295 |
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- danfoss/fc302.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- Modbus RTU Operating Instructions — Danfoss A/S, MG92B102 · Addressing pp.13-16, conversion p.17, settings and PCD p.18, frame examples pp.21-22 · checked 2026-11-05
- VLT AutomationDrive FC 301/302 Programming Guide — Danfoss A/S, AU275636650261en-US3101, Software 7.62 / 8.10 · Parameter lists PDF pp.279-295 · checked 2026-11-05