Danfoss FC 51 Modbus register map

Control via coils: 1-16 control word, 17-32 speed reference, 33-48 status word, 49-64 output frequency (FC profile). Parameters are holding registers '10 × parameter number' (e.g. 3-03 → 3030, wire address 3029). · Inverter (VFD) · VLT Micro Drive FC 51

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Data · parity · stop8 · Even · 1
Manual address style1-based numbers (wire address + 1)

Registers (31)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

31

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
coil 10 (0x0000)COControl word bit 0: Preset reference LSBBITR/W01·05·0F
p.74 Table 8.15·8.16
coil 21 (0x0001)COControl word bit 1: Preset reference MSBBITR/W01·05·0F
p.74 Table 8.15·8.16
coil 32 (0x0002)COControl word bit 2: No DC brakeBITR/W01·05·0F
0 = DC brake · 1 = No DC brake
p.74 Table 8.15·8.16
coil 43 (0x0003)COControl word bit 3: No coast stopBITR/W01·05·0F
0 = Coast stop · 1 = No coast stop
p.74 Table 8.15·8.16
coil 54 (0x0004)COControl word bit 4: No quick stopBITR/W01·05·0F
0 = Quick stop · 1 = No quick stop
p.74 Table 8.15·8.16
coil 65 (0x0005)COControl word bit 5: No freeze frequencyBITR/W01·05·0F
0 = Freeze frequency · 1 = No freeze frequency
p.74 Table 8.15·8.16
coil 76 (0x0006)COControl word bit 6: StartBITR/W01·05·0F
0 = Ramp stop · 1 = Start
p.74 Table 8.15·8.16
coil 87 (0x0007)COControl word bit 7: ResetBITR/W01·05·0F
0 = No reset · 1 = Reset
p.74 Table 8.15·8.16
coil 98 (0x0008)COControl word bit 8: JogBITR/W01·05·0F
0 = No jog · 1 = Jog
p.74 Table 8.15·8.16
coil 109 (0x0009)COControl word bit 9: Ramp 2BITR/W01·05·0F
0 = Ramp 1 · 1 = Ramp 2
p.74 Table 8.15·8.16
coil 1110 (0x000A)COControl word bit 10: Data validBITR/W01·05·0F
0 = Data not valid · 1 = Data valid
p.74 Table 8.15·8.16
coil 1211 (0x000B)COControl word bit 11: Relay 1 onBITR/W01·05·0F
0 = Relay 1 off · 1 = Relay 1 on
p.74 Table 8.15·8.16
coil 1312 (0x000C)COControl word bit 12: Relay 2 onBITR/W01·05·0F
0 = Relay 2 off · 1 = Relay 2 on
p.74 Table 8.15·8.16
coil 1413 (0x000D)COControl word bit 13: Set-up LSBBITR/W01·05·0F
p.74 Table 8.15·8.16
coil 1615 (0x000F)COControl word bit 15: ReversingBITR/W01·05·0F
0 = No reversing · 1 = Reversing
p.74 Table 8.15·8.16
coil 3332 (0x0020)COStatus word bit 0: Control readyBITR01
0 = Control not ready · 1 = Control ready
p.74 Table 8.15·8.17
coil 3433 (0x0021)COStatus word bit 1: Frequency converter readyBITR01
0 = Frequency converter not ready · 1 = Frequency converter ready
p.74 Table 8.15·8.17
coil 3534 (0x0022)COStatus word bit 2: Safety closedBITR01
0 = Coast stop · 1 = Safety closed
p.74 Table 8.15·8.17
coil 3635 (0x0023)COStatus word bit 3: AlarmBITR01
0 = No alarm · 1 = Alarm
p.74 Table 8.15·8.17
coil 4039 (0x0027)COStatus word bit 7: WarningBITR01
0 = No warning · 1 = Warning
p.74 Table 8.15·8.17
coil 4140 (0x0028)COStatus word bit 8: At referenceBITR01
0 = Not at reference · 1 = At reference
p.74 Table 8.15·8.17
coil 4241 (0x0029)COStatus word bit 9: Auto modeBITR01
0 = Hand mode · 1 = Auto mode
p.74 Table 8.15·8.17
coil 4342 (0x002A)COStatus word bit 10: In frequency rangeBITR01
0 = Out of frequency range · 1 = In frequency range
p.74 Table 8.15·8.17
coil 4443 (0x002B)COStatus word bit 11: RunningBITR01
0 = Stopped · 1 = Running
p.74 Table 8.15·8.17
coil 4645 (0x002D)COStatus word bit 13: Voltage warningBITR01
0 = No voltage warning · 1 = Voltage warning
p.74 Table 8.15·8.17
coil 4746 (0x002E)COStatus word bit 14: Current limitBITR01
0 = Not in current limit · 1 = Current limit
p.74 Table 8.15·8.17
coil 4847 (0x002F)COStatus word bit 15: Thermal warningBITR01
0 = No thermal warning · 1 = Thermal warning
p.74 Table 8.15·8.17
coil 6564 (0x0040)COParameter write controlBITR/W01·05
0 = RAM only · 1 = RAM and EEPROM
p.74 Table 8.15
400076 (0x0006)HRLast fault codeU16R03
p.75 Table 8.18
400087 (0x0007)HRLast error registerU16R03
Address of the register where the last error occurred
p.75 Table 8.18
400098 (0x0008)HRIndex pointerU16R/W03·06
Set the array index before reading or writing an array parameter (p.76, 8.9.3)
p.75 Table 8.18

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).