PortDock

Hitachi WJ200 Modbus register map

Built-in RS485 Modbus RTU. Coil 0001h run command, register 0001h F001 frequency source, 1001h d001 output frequency, 1011h output voltage, 1012h power. Frame address = number - 1 · Inverter (VFD)

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)9600 bps — options: 2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200
Data · parity · stop8 · None · 1
Slave ID (factory)1 (1~247)
32-bit orderABCD
Max per request16 registers
Manual address style1-based numbers (wire address + 1)

Registers (63)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

63

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
0001h0 (0x0000)CORun command (1 run, 0 stop)BITR/W01·05·0F
PDF p.355
0002h1 (0x0001)CORotation direction command (1 reverse, 0 forward)BITR/W01·05·0F
PDF p.355
0003h2 (0x0002)COExternal trip (EXT)BITR/W01·05·0F
PDF p.355
0004h3 (0x0003)COTrip reset (RS)BITR/W01·05·0F
PDF p.355
0007h6 (0x0006)COIntelligent input terminal [1]BITR/W01·05·0F
PDF p.355
0008h7 (0x0007)COIntelligent input terminal [2]BITR/W01·05·0F
PDF p.355
0009h8 (0x0008)COIntelligent input terminal [3]BITR/W01·05·0F
PDF p.355
000Ah9 (0x0009)COIntelligent input terminal [4]BITR/W01·05·0F
PDF p.355
000Bh10 (0x000A)COIntelligent input terminal [5]BITR/W01·05·0F
PDF p.355
000Ch11 (0x000B)COIntelligent input terminal [6]BITR/W01·05·0F
PDF p.355
000Dh12 (0x000C)COIntelligent input terminal [7]BITR/W01·05·0F
PDF p.355
000Fh14 (0x000E)COOperation statusBITR01
PDF p.355
0010h15 (0x000F)CORotation directionBITR01
PDF p.355
0011h16 (0x0010)COInverter readyBITR01
PDF p.355
0013h18 (0x0012)CORUN (running)BITR01
PDF p.355
0014h19 (0x0013)COFA1 constant speed reachedBITR01
PDF p.355
0015h20 (0x0014)COFA2 set frequency overreachedBITR01
PDF p.355
0016h21 (0x0015)COOL overload noticeBITR01
PDF p.355
0018h23 (0x0017)COAL alarm signalBITR01
PDF p.355
001Ah25 (0x0019)COOTQ over-torqueBITR01
PDF p.355
001Ch27 (0x001B)COUV undervoltageBITR01
PDF p.355
001Dh28 (0x001C)COTRQ torque limitedBITR01
PDF p.355
0028h39 (0x0027)COZS zero speed detectionBITR01
PDF p.355
0001h (high), 0002h (low)0 (0x0000)HRFrequency source (F001)U32 ABCD×0.01 HzR/W03·10
Range 0 ~ 400 Hz
PDF p.357
0003h2 (0x0002)HRInverter status AU16R03
0 = Initial status · 2 = Stopping · 3 = Running · 4 = Free-run stop · 5 = Jogging · 6 = DC braking · 7 = Retrying · 8 = Tripping · 9 = Undervoltage
PDF p.357
0004h3 (0x0003)HRInverter status BU16R03
0 = Stopping · 1 = Running · 2 = Tripping
PDF p.357
0005h4 (0x0004)HRInverter status CU16R03
PDF p.357
0006h5 (0x0005)HRPID feedbackU16×0.01 %R/W03·06·10
Range 0 ~ 100 %
PDF p.357
0011h16 (0x0010)HRTrip counter (d080)U16R03
PDF p.358
0012h17 (0x0011)HRTrip 1 factor (d081)U16R03
PDF p.358
0013h18 (0x0012)HRTrip 1 inverter statusU16R03
PDF p.358
0014h (high), 0015h (low)19 (0x0013)HRTrip 1 frequencyU32 ABCD×0.01 HzR03
PDF p.358
004Eh77 (0x004D)HRProgramming error (d090)U16R03
PDF p.359
0900h2303 (0x08FF)HRWriting to EEPROMU16W06·10
PDF p.359
0902h2305 (0x0901)HREEPROM write modeU16W06·10
0 = Invalid · 1 = Valid
PDF p.359
1001h (high), 1002h (low)4096 (0x1000)HROutput frequency (d001)U32 ABCD×0.01 HzR03
PDF p.361
1004h4099 (0x1003)HRRotation direction (d003)U16R03
0 = Stopping · 1 = Forward rotation · 2 = Reverse rotation
PDF p.361
1005h (high), 1006h (low)4100 (0x1004)HRPID feedback (d004)U32 ABCD×0.1R03
PDF p.361
1007h4102 (0x1006)HRIntelligent input terminal status (d005)U16R03
PDF p.361
1008h4103 (0x1007)HRIntelligent output terminal status (d006)U16R03
PDF p.361
100Bh (high), 100Ch (low)4106 (0x100A)HRActual frequency (d008)S32 ABCD×0.01 HzR03
PDF p.361
1010h4111 (0x100F)HRTorque (d012)S16%R03
PDF p.361
1011h4112 (0x1010)HROutput voltage (d013)U16×0.1 VR03
PDF p.361
1012h4113 (0x1011)HRPower (d014)U16×0.1 kWR03
PDF p.361
1015h (high), 1016h (low)4116 (0x1014)HRElapsed RUN time (d016)U32 ABCDhR03
PDF p.361
1017h (high), 1018h (low)4118 (0x1016)HRElapsed power-on time (d017)U32 ABCDhR03
PDF p.361
1019h4120 (0x1018)HRHeat sink temperature (d018)S16×0.1 ℃R03
PDF p.361
101Dh4124 (0x101C)HRLife-check monitor (d022)U16R03
b0 Capacitor on main circuit board · b1 Cooling fan
PDF p.361
1026h4133 (0x1025)HRDC voltage (d102)U16×0.1 VR03
PDF p.361
1027h4134 (0x1026)HRBRD load factor (d103)U16×0.1 %R03
PDF p.361
1028h4135 (0x1027)HRElectronic thermal overload (d104)U16×0.1 %R03
PDF p.361
1057h4182 (0x1056)HRInverter mode (d060)U16R03
PDF p.361
1103h (high), 1104h (low)4354 (0x1102)HRAcceleration time (F002)U32 ABCD×0.01 sR/W03·10
PDF p.362
1105h (high), 1106h (low)4356 (0x1104)HRDeceleration time (F003)U32 ABCD×0.01 sR/W03·10
PDF p.362
1107h4358 (0x1106)HRKeypad Run key routing (F004)U16R/W03·06·10
0 = Forward · 1 = Reverse
PDF p.362
1201h4608 (0x1200)HRFrequency source (A001)U16R/W03·06·10
PDF p.362
1202h4609 (0x1201)HRRun command source (A002)U16R/W03·06·10
1 = Control terminal · 2 = Digital operator · 3 = Modbus · 4 = Option
PDF p.362
1203h4610 (0x1202)HRBase frequency (A003)U16×0.1 HzR/W03·06·10
PDF p.362
1204h4611 (0x1203)HRMaximum frequency (A004)U16×0.1 HzR/W03·06·10
PDF p.362
144Bh5194 (0x144A)HRCommunication speed (C071)U16R/W03·06·10
3 = 2400 bps · 4 = 4800 bps · 5 = 9600 bps · 6 = 19200 bps · 7 = 38400 bps · 8 = 57600 bps · 9 = 76800 bps · 10 = 115200 bps
PDF p.373
144Ch5195 (0x144B)HRModbus address (C072)U16R/W03·06·10
Range 1 ~ 247
PDF p.373
144Eh5197 (0x144D)HRCommunication parity (C074)U16R/W03·06·10
0 = No parity · 1 = Even · 2 = Odd
PDF p.373
144Fh5198 (0x144E)HRCommunication stop bit (C075)U16R/W03·06·10
1 = 1 bit · 2 = 2 bits
PDF p.373

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).

Download JSON