メーカーのマニュアルから事実(アドレス・型・単位・倍率)だけを写してまとめた非公式の資料です。メーカーとは関係がなく、ファームウェアや形式によって異なることがあります。書き込み(運転指令・設定変更)の前に、必ず機器のマニュアルで確認してください。
通信の既定値
| プロトコル | Modbus RTU |
|---|---|
| ボーレート(出荷時) | 19200 bps — 選択肢: 9600, 19200, 38400 |
| データ・パリティ・ストップ | 8 · 偶数 · 1 |
| 1 回の要求の最大 | レジスタ 8 個 |
| マニュアルのアドレス表記 | 通信アドレスそのまま(0 始まり) |
- Addressing: the communication number (hex, e.g. FD00, FA01) is the frame address — read example 01 03 FD 00 00 01 (output frequency, p.26), write example 01 06 FA 01 17 70 (60 Hz, p.31). Parameters use the same hex number, e.g. 0800 (f800).
- Factory protocol is the Toshiba protocol (f829 = 0); set f829 = 1 and reset for Modbus. Defaults 19200 bps (f800 = 4), even parity (f801 = 1), inverter number 0 (f802) (p.4, p.24, p.47). The inverter receives 1 stop bit and sends 2 (p.4).
- FC 03 (normally 1 word; 'direct block read' 2-8 words), 06, 10 (1 word), 17 and 2B (p.25, p.29, p.32). Communication numbers xxxA-xxxF and xxAx-xxFx do not exist and are skipped in block reads, e.g. 0009h is followed by 0010h (p.29, p.68). Missing numbers return 8000h.
レジスタ (32)
«通信アドレス» は要求フレームに載る 0 始まりのアドレスです(PortDock の «0 始まり» 表記)。値 = 生の値 × 倍率。領域: HR 保持レジスタ、IR 入力レジスタ、CO コイル、DI 入力ステータス。ファンクションコードは 16 進。
レジスタ名・説明・値の意味・注意・出典の版とページは、マニュアルの表記と照らし合わせやすいよう英語のまま載せています。
32 件
表は横にスクロールできます — 最初の列(マニュアルのアドレス)は固定です。
| マニュアル | 通信アドレス | 領域 | 名前 | 型 | 単位・倍率 | R/W | FC | 説明 |
|---|---|---|---|---|---|---|---|---|
| 0800 (f800) | 2048 (0x0800) | HR | Baud rate | U16 | R/W | 03·06·10 | Takes effect after reset or power cycle 3 = 9600 bps · 4 = 19200 bps (default) · 5 = 38400 bps p.47 | |
| 0801 (f801) | 2049 (0x0801) | HR | Parity | U16 | R/W | 03·06·10 | 0 = None · 1 = Even (default) · 2 = Odd p.47 | |
| 0802 (f802) | 2050 (0x0802) | HR | Inverter number (slave ID) | U16 | R/W | 03·06·10 | Default 0. In Modbus 0 is broadcast, so set 1-247 範囲 0 ~ 247 p.47, p.49 | |
| 0803 (f803) | 2051 (0x0803) | HR | Communication time-out time | U16 | ×0.1 s | R/W | 03·06·10 | 0.0 = disabled (default) 範囲 0 ~ 100 s p.47 |
| 0804 (f804) | 2052 (0x0804) | HR | Communication time-out action | U16 | R/W | 03·06·10 | 0 = Alarm only (default) · 1 = Trip (coast stop) · 2 = Trip (deceleration stop) p.47 | |
| 0829 (f829) | 2089 (0x0829) | HR | Communication protocol | U16 | R/W | 03·06·10 | Takes effect after reset 0 = Toshiba inverter protocol (default) · 1 = Modbus RTU p.47, p.24 | |
| FA00 | 64000 (0xFA00) | HR | Communication command 1 | U16 | W | 06·10 | E.g. 8400h = command priority + run (forward), C400h also enables frequency priority. Stored in RAM only b7 DC braking (1 = forced DC braking) · b8 Jog run · b9 Forward/reverse (0 forward, 1 reverse) · b10 Run/stop (1 = run) · b11 Coast stop command (1 = coast stop) · b12 Emergency stop (always enabled, 'E' trip) · b13 Fault reset (the inverter returns no reply) · b14 Frequency priority (1 = communication frequency enabled regardless of fmod) · b15 Command priority (1 = communication commands enabled regardless of cmod) p.52 Table 1, p.69 | |
| FA01 | 64001 (0xFA01) | HR | Frequency command (communication) | U16 | ×0.01 Hz | W | 06·10 | 0 to maximum frequency (fh). Write example 01 06 FA 01 17 70 = 60.00 Hz (p.31) p.54, p.69 |
| FA13 | 64019 (0xFA13) | HR | Motor speed command | U16 | min-1 | W | 06·10 | 範囲 0 ~ 24000 min-1 p.54, p.69 |
| FA50 | 64080 (0xFA50) | HR | Terminal board output data | U16 | W | 06·10 | b0 Specified data output 1 (output function 92/93) · b1 Specified data output 2 (output function 94/95) p.55 | |
| FB07 | 64263 (0xFB07) | HR | Inverter series type | U16 | R | 03 | 224 for VF-S15 p.70 | |
| FC90 | 64656 (0xFC90) | HR | Trip code (current) | U16 | R | 03 | See the table on p.63 for the other codes 0 = No error (nerr) · 1 = Over-current during acceleration (oc1) · 2 = Over-current during deceleration (oc2) · 3 = Over-current at constant speed (oc3) p.63, p.70 | |
| FC91 | 64657 (0xFC91) | HR | Alarm information 1 | U16 | R | 03 | b0 Over-current alarm · b1 Inverter overload alarm · b2 Motor overload alarm · b3 Overheat alarm · b4 Overvoltage alarm · b5 Undervoltage alarm · b7 Low current alarm · b8 Over-torque alarm · b12 Serial communication alarm p.61 | |
| FD00 | 64768 (0xFD00) | HR | Output frequency | U16 | ×0.01 Hz | R | 03 | Read example 01 03 FD 00 00 01 → 17 70 = 60.00 Hz (p.26). Value just before a trip: FE00 p.56, p.70 |
| FD01 | 64769 (0xFD01) | HR | Status information 1 | U16 | R | 03 | b0 Failure FL (1 = output in progress) · b1 Failure (1 = tripped, incl. retry and trip retention) · b2 Alarm (1 = alarm issued) · b3 Main circuit undervoltage (1 = undervoltage) · b7 DC braking (1 = forced DC braking) · b8 Jog run · b9 Forward/reverse (0 forward, 1 reverse) · b10 Run/stop (1 = run) · b11 Coast stop (1 = ST=OFF) · b12 Emergency stop status · b13 Standby (incl. ST=ON and RUN=ON) · b14 Standby (initialised, not stopped by fault or alarm) p.59 | |
| FD02 | 64770 (0xFD02) | HR | Frequency command value | U16 | ×0.01 Hz | R | 03 | p.70 |
| FD03 | 64771 (0xFD03) | HR | Output current (% of rating) | U16 | ×0.01 % | R | 03 | p.56, p.70 |
| FD04 | 64772 (0xFD04) | HR | Input voltage (DC detection, % of rating) | U16 | ×0.01 % | R | 03 | p.56, p.70 |
| FD05 | 64773 (0xFD05) | HR | Output voltage (% of rating) | U16 | ×0.01 % | R | 03 | p.56, p.70 |
| FD06 | 64774 (0xFD06) | HR | Input terminal status | U16 | R | 03 | b0 F terminal · b1 R terminal · b2 RES terminal · b3 S1 terminal · b4 S2 terminal · b5 S3 terminal p.57 | |
| FD07 | 64775 (0xFD07) | HR | Output terminal status | U16 | R | 03 | b0 RY-RC · b1 OUT · b2 FL p.58 | |
| FD22 | 64802 (0xFD22) | HR | PID feedback value | U16 | ×0.01 Hz | R | 03 | p.70 |
| FD29 | 64809 (0xFD29) | HR | Input power | U16 | ×0.01 kW | R | 03 | p.70 |
| FD30 | 64816 (0xFD30) | HR | Output power | U16 | ×0.01 kW | R | 03 | p.70 |
| FD45 | 64837 (0xFD45) | HR | Operating command mode status | U16 | R | 03 | 0 = Terminal block · 1 = Panel keypad · 2 = RS485 communication · 3 = CANopen communication · 4 = Communication option p.62 | |
| FD90 | 64912 (0xFD90) | HR | Output motor speed | U16 | min-1 | R | 03 | Number of poles from f856 p.61, p.71 |
| FE10 | 65040 (0xFE10) | HR | Past trip 1 (latest) | U16 | R | 03 | p.70 | |
| FE14 | 65044 (0xFE14) | HR | Cumulative operation time | U16 | h | R | 03 | p.70 |
| FE35 | 65077 (0xFE35) | HR | Terminal VIA input | U16 | ×0.01 % | R | 03 | 範囲 0 ~ 100 % p.58 |
| FE36 | 65078 (0xFE36) | HR | Terminal VIB input | S16 | ×0.01 % | R | 03 | 範囲 -100 ~ 100 % p.58 |
| FE70 | 65136 (0xFE70) | HR | Rated current | U16 | ×0.1 A | R | 03 | p.71 |
| FE71 | 65137 (0xFE71) | HR | Rated voltage | U16 | ×0.1 V | R | 03 | p.71 |
注意
- No communication for about 1 s after power-on (p.24). Do not write the same EEPROM parameter more than 10,000 times (p.31).
- Printed page = PDF page − 1.
PortDock ですぐ読み出す
- 無料の PortDock Modbus Master をインストールし、機器と同じ通信設定で接続します。
- 中央の表のツールバーの «機器プロファイル…» でこの機器を選び «読み込む» — ポーリング表・セル名・型・局番が入ります(通信の既定値も合わせられます)。
- セル名に単位・倍率(例 «×0.01 Hz»)が付きます。画面の値は生の値なので、倍率を掛けて読みます。
- 機器なしで自分のプログラムを試験するには、PortDock Modbus Slave の «機器を模擬…» で同じマップ(例の値)を立ち上げます。
RS-485 の配線は 配線図作成ツール で、この機器の名前・局番・ボーレート・パリティを入れた図を描けます(端子番号はマニュアルで確認)。
JSON をダウンロード
- toshiba/vf-s15.json (GitHub の原本) · このサイトのコピー · 修正履歴
- schema.json — 形式の説明(JSON Schema)。table・address(0 始まり)・type・order は PortDock の CSV と同じです。
- ライセンス: CC BY 4.0 — 使うときは出典を明記してください:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
とこのページの URL。LICENSE · データ一式・版・変更点(英語) - 誤りを見つけたら、マニュアルのページを添えて GitHub の Issue でお知らせください。
出典
- TOSVERT VF-S15 Series RS485 Communication Function Instruction Manual — Toshiba, E6581913 (PDF created 2019-04, modified 2022-04) · 2 transmission specs printed p.4, 5 Modbus RTU pp.24-32, 7 communication parameters p.47, 8 commands and monitoring pp.52-63, 9 parameter data pp.68-71 · 確認日 2026-11-01