Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 19200 bps — options: 4800, 9600, 19200 |
| Data · parity · stop | 8 · Even · 1 |
| Slave ID (factory) | 1 (1~247) |
| Max per request | 29 registers |
| Manual address style | Wire address as is (0-based) |
- Addressing: the read example (Modbus manual p.9) sends 02 03 0C1E 0004 276C to read W3102-W3105 (16#0C1E-); the write example (p.9) is 02 06 2329 000D 9270 for W9001 (16#2329). Manual number = frame address (0-based).
- Factory settings: Add 1, tbr 19200 bps, tFO 8E1, ttO 10 s (variables manual p.51). The remote display terminal only works with 19200 bps and 8E1.
- Function codes 03 (up to 29 words), 06, 16 (up to 27 words) and 43 (identification) (Modbus manual p.9).
Registers (40)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 3102 | 3102 (0x0C1E) | HR | SFr switching frequency | U16 | ×0.1 kHz | R/W | 03·06·10 | Range 2 ~ 16 kHz p.28 |
| 3103 | 3103 (0x0C1F) | HR | tFr maximum output frequency | U16 | ×0.1 Hz | R/W | 03·06·10 | Range 10 ~ 500 Hz p.28 |
| 3104 | 3104 (0x0C20) | HR | HSP high speed | U16 | ×0.1 Hz | R/W | 03·06·10 | p.24 |
| 3105 | 3105 (0x0C21) | HR | LSP low speed | U16 | ×0.1 Hz | R/W | 03·06·10 | p.24 |
| 3201 | 3201 (0x0C81) | HR | ETA status word | U16 | R | 03 | b0 Ready to switch on · b1 Switched on · b2 Operation enabled · b3 Fault · b4 Voltage disabled · b5 Quick stop · b6 Switch on disabled · b7 Alarm · b9 0 = forced local mode (FLO) · b10 Reference reached · b11 LFRD reference exceeded · b14 Stop imposed by STOP key · b15 Reverse rotation p.17 | |
| 3202 | 3202 (0x0C82) | HR | rFr output frequency | S16 | ×0.1 Hz | R | 03 | Unit when CMI bit 9 = 0 p.17 |
| 3203 | 3203 (0x0C83) | HR | FrH frequency reference before ramp | U16 | ×0.1 Hz | R | 03 | p.17 |
| 3204 | 3204 (0x0C84) | HR | LCr motor current | U16 | ×0.1 A | R | 03 | p.17 |
| 3205 | 3205 (0x0C85) | HR | Otr motor torque | U16 | % | R | 03 | p.17 |
| 3206 | 3206 (0x0C86) | HR | ETI extended status word | U16 | R | 03 | p.18 | |
| 3207 | 3207 (0x0C87) | HR | ULn line voltage | U16 | ×0.1 V | R | 03 | p.17 |
| 3209 | 3209 (0x0C89) | HR | tHd drive thermal state | U16 | % | R | 03 | p.17 |
| 3210 | 3210 (0x0C8A) | HR | TDM maximum drive thermal state | U16 | % | R | 03 | p.17 |
| 3211 | 3211 (0x0C8B) | HR | OPr motor power | U16 | % | R | 03 | p.17 |
| 3231 | 3231 (0x0C9F) | HR | rtH operating time | U16 | h | R | 03 | p.17 |
| 3250 | 3250 (0x0CB2) | HR | LRS1 extended status 1 | U16 | R | 03 | p.18 | |
| 3252 | 3252 (0x0CB4) | HR | LRS3 extended status 3 | U16 | R | 03 | p.19 | |
| 5240 | 5240 (0x1478) | HR | IOLR logic I/O value | U16 | R/W | 03·06·10 | Only unassigned R1, R2 and LO bits can be written p.16, p.19 | |
| 5241 | 5241 (0x1479) | HR | AIPC potentiometer input | U16 | mV | R | 03 | p.19 |
| 5242 | 5242 (0x147A) | HR | AI1C analog input 1 | U16 | mV | R | 03 | p.19 |
| 5243 | 5243 (0x147B) | HR | AI2C analog input 2 | S16 | mV | R | 03 | p.19 |
| 5244 | 5244 (0x147C) | HR | AI3C analog input 3 | U16 | µA | R | 03 | p.19 |
| 5261 | 5261 (0x148D) | HR | AO1R analog output value | U16 | R/W | 03·06·10 | Range 0 ~ 10000 p.16, p.19 | |
| 6001 | 6001 (0x1771) | HR | Add Modbus address | U16 | R/W | 03·06·10 | Range 1 ~ 247 p.51 | |
| 6003 | 6003 (0x1773) | HR | tbr baud rate | U16 | R/W | 03·06·10 | 24 = 4800 bps · 28 = 9600 bps · 32 = 19200 bps p.51 | |
| 6004 | 6004 (0x1774) | HR | tFO frame format | U16 | R/W | 03·06·10 | 2 = 8O1 · 3 = 8E1 · 4 = 8N1 · 5 = 8N2 p.51 | |
| 6005 | 6005 (0x1775) | HR | ttO time-out | U16 | ×0.1 s | R/W | 03·06·10 | p.51 |
| 7121 | 7121 (0x1BD1) | HR | LFt last fault | U16 | R | 03 | Main codes only; see the manual for all 0 = nOF no fault saved · 5 = SLF Modbus communication fault · 9 = OCF overcurrent · 16 = OHF drive overheating · 17 = OLF motor overload · 18 = ObF DC bus overvoltage · 20 = OPF motor phase loss · 21 = PHF line phase loss · 22 = USF line undervoltage p.20 | |
| 7201 | 7201 (0x1C21) | HR | DP1 past fault 1 | U16 | R | 03 | p.20 | |
| 7202 | 7202 (0x1C22) | HR | DP2 past fault 2 | U16 | R | 03 | p.20 | |
| 7203 | 7203 (0x1C23) | HR | DP3 past fault 3 | U16 | R | 03 | p.20 | |
| 7204 | 7204 (0x1C24) | HR | DP4 past fault 4 | U16 | R | 03 | p.20 | |
| 8501 | 8501 (0x2135) | HR | CMD control word | U16 | R/W | 03·06·10 | b0 Switch on (active at 1) · b1 Disable voltage (active at 0) · b2 Quick stop (active at 0) · b3 Enable operation (active at 1) · b7 Fault reset (rising edge) · b11 1 = reverse direction · b12 1 = stop command p.15 | |
| 8502 | 8502 (0x2136) | HR | LFr frequency reference via the bus | S16 | ×0.1 Hz | R/W | 03·06·10 | Unit when CMI bit 9 = 0 p.15 |
| 8503 | 8503 (0x2137) | HR | PISP PI reference | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 100 % p.15 |
| 8504 | 8504 (0x2138) | HR | CMI extended control word | U16 | R/W | 03·06·10 | p.16 | |
| 9001 | 9001 (0x2329) | HR | ACC acceleration time | U16 | ×0.1 s | R/W | 03·06·10 | p.35 |
| 9002 | 9002 (0x232A) | HR | dEC deceleration time | U16 | ×0.1 s | R/W | 03·06·10 | p.35 |
| 9630 | 9630 (0x259E) | HR | tHr motor thermal state | U16 | % | R | 03 | p.17 |
| 12002 (USPL), 12003 (USPH) | 12002 (0x2EE2) | HR | USP speed in customer units | U32 CDAB | R | 03 | Low word USPL comes first p.18 |
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- schneider-electric/atv31.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/