Schneider Electric ATV31 Modbus register map

RJ45 port Modbus RTU. Logical address = frame address: command word CMD 8501, frequency reference 8502, status word ETA 3201, output frequency 3202, current 3204, ramps 9001/9002 · Inverter (VFD) · Altivar 31

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)19200 bps — options: 4800, 9600, 19200
Data · parity · stop8 · Even · 1
Slave ID (factory)1 (1~247)
Max per request29 registers
Manual address styleWire address as is (0-based)

Registers (40)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

40

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
31023102 (0x0C1E)HRSFr switching frequencyU16×0.1 kHzR/W03·06·10
Range 2 ~ 16 kHz
p.28
31033103 (0x0C1F)HRtFr maximum output frequencyU16×0.1 HzR/W03·06·10
Range 10 ~ 500 Hz
p.28
31043104 (0x0C20)HRHSP high speedU16×0.1 HzR/W03·06·10
p.24
31053105 (0x0C21)HRLSP low speedU16×0.1 HzR/W03·06·10
p.24
32013201 (0x0C81)HRETA status wordU16R03
b0 Ready to switch on · b1 Switched on · b2 Operation enabled · b3 Fault · b4 Voltage disabled · b5 Quick stop · b6 Switch on disabled · b7 Alarm · b9 0 = forced local mode (FLO) · b10 Reference reached · b11 LFRD reference exceeded · b14 Stop imposed by STOP key · b15 Reverse rotation
p.17
32023202 (0x0C82)HRrFr output frequencyS16×0.1 HzR03
Unit when CMI bit 9 = 0
p.17
32033203 (0x0C83)HRFrH frequency reference before rampU16×0.1 HzR03
p.17
32043204 (0x0C84)HRLCr motor currentU16×0.1 AR03
p.17
32053205 (0x0C85)HROtr motor torqueU16%R03
p.17
32063206 (0x0C86)HRETI extended status wordU16R03
p.18
32073207 (0x0C87)HRULn line voltageU16×0.1 VR03
p.17
32093209 (0x0C89)HRtHd drive thermal stateU16%R03
p.17
32103210 (0x0C8A)HRTDM maximum drive thermal stateU16%R03
p.17
32113211 (0x0C8B)HROPr motor powerU16%R03
p.17
32313231 (0x0C9F)HRrtH operating timeU16hR03
p.17
32503250 (0x0CB2)HRLRS1 extended status 1U16R03
p.18
32523252 (0x0CB4)HRLRS3 extended status 3U16R03
p.19
52405240 (0x1478)HRIOLR logic I/O valueU16R/W03·06·10
Only unassigned R1, R2 and LO bits can be written
p.16, p.19
52415241 (0x1479)HRAIPC potentiometer inputU16mVR03
p.19
52425242 (0x147A)HRAI1C analog input 1U16mVR03
p.19
52435243 (0x147B)HRAI2C analog input 2S16mVR03
p.19
52445244 (0x147C)HRAI3C analog input 3U16µAR03
p.19
52615261 (0x148D)HRAO1R analog output valueU16R/W03·06·10
Range 0 ~ 10000
p.16, p.19
60016001 (0x1771)HRAdd Modbus addressU16R/W03·06·10
Range 1 ~ 247
p.51
60036003 (0x1773)HRtbr baud rateU16R/W03·06·10
24 = 4800 bps · 28 = 9600 bps · 32 = 19200 bps
p.51
60046004 (0x1774)HRtFO frame formatU16R/W03·06·10
2 = 8O1 · 3 = 8E1 · 4 = 8N1 · 5 = 8N2
p.51
60056005 (0x1775)HRttO time-outU16×0.1 sR/W03·06·10
p.51
71217121 (0x1BD1)HRLFt last faultU16R03
Main codes only; see the manual for all
0 = nOF no fault saved · 5 = SLF Modbus communication fault · 9 = OCF overcurrent · 16 = OHF drive overheating · 17 = OLF motor overload · 18 = ObF DC bus overvoltage · 20 = OPF motor phase loss · 21 = PHF line phase loss · 22 = USF line undervoltage
p.20
72017201 (0x1C21)HRDP1 past fault 1U16R03
p.20
72027202 (0x1C22)HRDP2 past fault 2U16R03
p.20
72037203 (0x1C23)HRDP3 past fault 3U16R03
p.20
72047204 (0x1C24)HRDP4 past fault 4U16R03
p.20
85018501 (0x2135)HRCMD control wordU16R/W03·06·10
b0 Switch on (active at 1) · b1 Disable voltage (active at 0) · b2 Quick stop (active at 0) · b3 Enable operation (active at 1) · b7 Fault reset (rising edge) · b11 1 = reverse direction · b12 1 = stop command
p.15
85028502 (0x2136)HRLFr frequency reference via the busS16×0.1 HzR/W03·06·10
Unit when CMI bit 9 = 0
p.15
85038503 (0x2137)HRPISP PI referenceU16×0.1 %R/W03·06·10
Range 0 ~ 100 %
p.15
85048504 (0x2138)HRCMI extended control wordU16R/W03·06·10
p.16
90019001 (0x2329)HRACC acceleration timeU16×0.1 sR/W03·06·10
p.35
90029002 (0x232A)HRdEC deceleration timeU16×0.1 sR/W03·06·10
p.35
96309630 (0x259E)HRtHr motor thermal stateU16%R03
p.17
12002 (USPL), 12003 (USPH)12002 (0x2EE2)HRUSP speed in customer unitsU32 CDABR03
Low word USPL comes first
p.18

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).