An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 19200 bps — options: 9600, 19200, 38400 |
| Data · parity · stop | 8 · Even · 1 |
| Max per request | 1 registers |
| Manual address style | Wire address as is (0-based) |
- Addressing: the hex communication number is the frame address — read example 01 03 FD 00 00 01 (p.30), write example 01 06 FA 01 17 70 (p.31).
- VF-AS1 Modbus RTU supports only FC 03 (one word per request) and 06 (pp.29-30). Factory protocol is Toshiba's; for 2-wire RS485 set f807 = 1 and reset (p.40).
- Defaults 19200 bps (f800 = 1), even parity (f801 = 1), inverter number 0 (p.40). 2-wire (f800, FA00, FA01) and 4-wire (f820, FA04, FA05) are set separately. No communication for about 2 s after power-on (p.29).
Registers (32)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 0800 (f800) | 2048 (0x0800) | HR | Baud rate (2-wire RS485) | U16 | R/W | 03·06 | 0 = 9600 bps · 1 = 19200 bps (default) · 2 = 38400 bps p.40 | |
| 0801 (f801) | 2049 (0x0801) | HR | Parity (2-wire RS485) | U16 | R/W | 03·06 | 0 = None · 1 = Even (default) · 2 = Odd p.40 | |
| 0802 (f802) | 2050 (0x0802) | HR | Inverter number (common) | U16 | R/W | 03·06 | Default 0; use 1-247 for Modbus Range 0 ~ 247 p.40 | |
| 0803 (f803) | 2051 (0x0803) | HR | Communication time-out time (common) | U16 | s | R/W | 03·06 | 0 = off (default) Range 0 ~ 100 s p.40 |
| 0807 (f807) | 2055 (0x0807) | HR | Protocol selection (2-wire RS485) | U16 | R/W | 03·06 | 0 = TOSHIBA (default) · 1 = MODBUS-RTU p.40 | |
| 0820 (f820) | 2080 (0x0820) | HR | Communication speed (4-wire RS485) | U16 | R/W | 03·06 | 0 = 9600 bps · 1 = 19200 bps (default) · 2 = 38400 bps p.40 | |
| FA00 | 64000 (0xFA00) | HR | Command 1 (2-wire RS485) | U16 | W | 06 | b7 DC braking (1 = forced DC braking) · b8 Jog run · b9 Forward/reverse (0 forward, 1 reverse) · b10 Run/stop (1 = run) · b11 Coast stop command (1 = coast stop) · b12 Emergency stop (always enabled, 'E' trip) · b13 Fault reset (the inverter returns no reply) · b14 Frequency priority (1 = communication frequency enabled regardless of fmod) · b15 Command priority (1 = communication commands enabled regardless of cmod) p.46 Table 1, p.65 | |
| FA01 | 64001 (0xFA01) | HR | Frequency command (2-wire RS485) | U16 | ×0.01 Hz | W | 06 | Write example 01 06 FA 01 17 70 = 60.00 Hz (p.31) p.65, p.31 |
| FA04 | 64004 (0xFA04) | HR | Command 1 (4-wire RS485) | U16 | W | 06 | b7 DC braking (1 = forced DC braking) · b8 Jog run · b9 Forward/reverse (0 forward, 1 reverse) · b10 Run/stop (1 = run) · b11 Coast stop command (1 = coast stop) · b12 Emergency stop (always enabled, 'E' trip) · b13 Fault reset (the inverter returns no reply) · b14 Frequency priority (1 = communication frequency enabled regardless of fmod) · b15 Command priority (1 = communication commands enabled regardless of cmod) p.46 Table 1, p.65 | |
| FA05 | 64005 (0xFA05) | HR | Frequency command (4-wire RS485) | U16 | ×0.01 Hz | W | 06 | p.65 |
| FB07 | 64263 (0xFB07) | HR | Inverter series type | U16 | R | 03 | 176 for VF-AS1 p.67 | |
| FC90 | 64656 (0xFC90) | HR | Trip code | U16 | R | 03 | p.67 | |
| FD00 | 64768 (0xFD00) | HR | Output frequency | U16 | ×0.01 Hz | R | 03 | Read example 01 03 FD 00 00 01 → 17 70 = 60.00 Hz (p.30) p.67, p.30 |
| FD01 | 64769 (0xFD01) | HR | Inverter operating status 1 | U16 | R | 03 | b0 Failure FL (1 = output in progress) · b1 Failure (1 = tripped, incl. retry and trip retention) · b2 Alarm (1 = alarm issued) · b7 DC braking (1 = forced DC braking) · b8 Jog run · b9 Forward/reverse (0 forward, 1 reverse) · b10 Run/stop (1 = run) · b11 Coast stop (1 = ST=OFF) · b12 Emergency stop status · b13 Standby (incl. ST=ON and RUN=ON) · b14 Standby (initialised, not stopped by fault or alarm) p.54 | |
| FD02 | 64770 (0xFD02) | HR | Frequency command value | U16 | ×0.01 Hz | R | 03 | p.67 |
| FD03 | 64771 (0xFD03) | HR | Output current | U16 | ×0.01 % | R | 03 | p.67 |
| FD04 | 64772 (0xFD04) | HR | Input voltage (DC detection) | U16 | ×0.01 % | R | 03 | p.67 |
| FD05 | 64773 (0xFD05) | HR | Output voltage | U16 | ×0.01 % | R | 03 | p.67 |
| FD06 | 64774 (0xFD06) | HR | Input terminal information | U16 | R | 03 | p.67 | |
| FD07 | 64775 (0xFD07) | HR | Output terminal information | U16 | R | 03 | p.67 | |
| FD16 | 64790 (0xFD16) | HR | Speed feedback (real time) | U16 | ×0.01 Hz | R | 03 | p.67 |
| FD22 | 64802 (0xFD22) | HR | PID feedback value | U16 | ×0.01 Hz | R | 03 | p.67 |
| FD23 | 64803 (0xFD23) | HR | Motor overload factor (OL2) | U16 | ×0.01 % | R | 03 | p.67 |
| FD24 | 64804 (0xFD24) | HR | Inverter overload factor (OL1) | U16 | ×0.01 % | R | 03 | p.67 |
| FD26 | 64806 (0xFD26) | HR | Motor load factor | U16 | % | R | 03 | p.67 |
| FD27 | 64807 (0xFD27) | HR | Inverter load factor | U16 | % | R | 03 | p.67 |
| FD29 | 64809 (0xFD29) | HR | Input power | U16 | ×0.01 kW | R | 03 | p.67 |
| FD30 | 64816 (0xFD30) | HR | Output power | U16 | ×0.01 kW | R | 03 | p.67 |
| FE10 | 65040 (0xFE10) | HR | Past trip 1 (latest) | U16 | R | 03 | p.67 | |
| FE14 | 65044 (0xFE14) | HR | Cumulative operation time | U16 | h | R | 03 | p.67 |
| FE35 | 65077 (0xFE35) | HR | RR/S4 input | U16 | ×0.01 % | R | 03 | p.67 |
| FE36 | 65078 (0xFE36) | HR | VI/II input | U16 | ×0.01 % | R | 03 | p.67 |
Notes
- Printed page = PDF page − 1.
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- toshiba/vf-as1.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- TOSVERT VF-AS1 Series RS485 Communication Function Instruction Manual — Toshiba, E6581315 (PDF 2020-06) · 2 transmission specs printed p.4, 5 Modbus RTU pp.29-31, 7 communication parameters p.40, 8 commands and monitoring pp.46-54, command and monitor parameters pp.65-67 · checked 2026-11-01