メーカーのマニュアルから事実(アドレス・型・単位・倍率)だけを写してまとめた非公式の資料です。メーカーとは関係がなく、ファームウェアや形式によって異なることがあります。書き込み(運転指令・設定変更)の前に、必ず機器のマニュアルで確認してください。
通信の既定値
| プロトコル | Modbus RTU, Modbus ASCII |
|---|---|
| ボーレート(出荷時) | 19200 bps — 選択肢: 1200, 2400, 4800, 9600, 19200, 38400, 57600 |
| データ・パリティ・ストップ | 8 · 偶数 · 1 |
| 局番(出荷時) | 1 (1~247) |
| 1 回の要求の最大 | レジスタ 16 個 |
| マニュアルのアドレス表記 | 通信アドレスそのまま(0 始まり) |
- Addressing: read example 01 03 21 00 00 01 reads 2100H (status word 1), write example 03 06 20 00 00 01 writes 2000H (command) — the hex address in the table is the frame address (pp.138-140). Parameter Pxx.yy maps xx and yy to hex bytes: P05.05 = 0505H, P10.01 = 0A01H (p.131).
- Defaults: P14.00 address 1, P14.01 = 4 (19200 bps), P14.02 = 1 (RTU E,8,1) (pp.99-100). FC 03, 06 and 10, up to 16 words per request (p.125 onward).
- Values are scaled integers ('fieldbus ratio'), set by the decimals of the setting range or default (one decimal = ×10) (p.135). Setting the high bit of a parameter address (e.g. 8007H) writes RAM only, not EEPROM (write-only) (pp.131-132).
レジスタ (34)
«通信アドレス» は要求フレームに載る 0 始まりのアドレスです(PortDock の «0 始まり» 表記)。値 = 生の値 × 倍率。領域: HR 保持レジスタ、IR 入力レジスタ、CO コイル、DI 入力ステータス。ファンクションコードは 16 進。
レジスタ名・説明・値の意味・注意・出典の版とページは、マニュアルの表記と照らし合わせやすいよう英語のまま載せています。
34 件
表は横にスクロールできます — 最初の列(マニュアルのアドレス)は固定です。
| マニュアル | 通信アドレス | 領域 | 名前 | 型 | 単位・倍率 | R/W | FC | 説明 |
|---|---|---|---|---|---|---|---|---|
| P00.01 (0001H) | 1 (0x0001) | HR | Running command channel | U16 | R/W | 03·06·10 | 0 = Keypad · 1 = Terminal · 2 = Communication p.31~32 | |
| P00.03 (0003H) | 3 (0x0003) | HR | Max. output frequency | U16 | ×0.01 Hz | R/W | 03·06·10 | Write example: 100 Hz → 2710H (03 06 00 03 27 10) p.31~32 |
| P14.00 (0E00H) | 3584 (0x0E00) | HR | Local communication address | U16 | R/W | 03·06·10 | 範囲 1 ~ 247 p.99~101 | |
| P14.01 (0E01H) | 3585 (0x0E01) | HR | Communication baud rate | U16 | R/W | 03·06·10 | 0 = 1200 bps · 1 = 2400 bps · 2 = 4800 bps · 3 = 9600 bps · 4 = 19200 bps (default) · 5 = 38400 bps · 6 = 57600 bps p.99~101 | |
| P14.02 (0E02H) | 3586 (0x0E02) | HR | Data bit check | U16 | R/W | 03·06·10 | 6-17 are ASCII formats 0 = RTU N,8,1 · 1 = RTU E,8,1 (default) · 2 = RTU O,8,1 · 3 = RTU N,8,2 · 4 = RTU E,8,2 · 5 = RTU O,8,2 p.99~101 | |
| P14.04 (0E04H) | 3588 (0x0E04) | HR | RS485 communication timeout | U16 | ×0.1 s | R/W | 03·06·10 | 0.0 = disabled; exceeding it reports 'CE' 範囲 0 ~ 60 s p.101 |
| 2000H | 8192 (0x2000) | HR | Communication control command | U16 | R/W | 03·06·10 | With P00.01 = 2 (communication). Write example 03 06 20 00 00 01 = forward running (p.139) 1 = Forward running · 2 = Reverse running · 3 = Forward jogging · 4 = Reverse jogging · 5 = Stop · 6 = Coast to stop · 7 = Fault reset · 8 = Jogging stop p.132~134, p.139 | |
| 2001H | 8193 (0x2001) | HR | Communication setting frequency | U16 | ×0.01 Hz | R/W | 03·06·10 | 0 to Fmax p.132~134 |
| 2002H | 8194 (0x2002) | HR | PID reference | U16 | ×0.1 % | R/W | 03·06·10 | 範囲 0 ~ 100 % p.132~134 |
| 2003H | 8195 (0x2003) | HR | PID feedback | U16 | ×0.1 % | R/W | 03·06·10 | 範囲 0 ~ 100 % p.132~134 |
| 2004H | 8196 (0x2004) | HR | Torque setting (% of motor rated current) | S16 | ×0.1 % | R/W | 03·06·10 | 範囲 -300 ~ 300 % p.132~134 |
| 2005H | 8197 (0x2005) | HR | Forward upper limit frequency | U16 | ×0.01 Hz | R/W | 03·06·10 | p.132~134 |
| 2006H | 8198 (0x2006) | HR | Reverse upper limit frequency | U16 | ×0.01 Hz | R/W | 03·06·10 | p.132~134 |
| 200AH | 8202 (0x200A) | HR | Virtual input terminal command | U16 | R/W | 03·06·10 | 範囲 0 ~ 511 p.132~134 | |
| 200DH | 8205 (0x200D) | HR | AO output setting 1 | S16 | ×0.1 % | R/W | 03·06·10 | 範囲 -100 ~ 100 % p.132~134 |
| 2100H | 8448 (0x2100) | HR | Status word 1 | U16 | R | 03 | 0002H is printed with the same text as 0001H ('Forward running'), so it is omitted. Read example 01 03 21 00 00 01 → 00 03 = stop (pp.138-139) 1 = Forward running · 3 = Stop · 4 = Fault · 5 = POFF state · 6 = Pre-exciting p.132~134, p.138 | |
| 2101H | 8449 (0x2101) | HR | Status word 2 | U16 | R | 03 | bit1-2 motor 1-4; bit5-6 = 00 keypad, 01 terminal, 10 communication control b0 Bus voltage established · b3 Synchronous motor (0 = asynchronous) · b4 Overload pre-alarm p.132~134 | |
| 2102H | 8450 (0x2102) | HR | Fault code | U16 | R | 03 | Codes follow the P07.27 fault type list 0 = No fault · 4 = Overcurrent during acceleration (OC1) · 5 = Overcurrent during deceleration (OC2) · 6 = Overcurrent at constant speed (OC3) · 7 = Overvoltage during acceleration (OV1) · 8 = Overvoltage during deceleration (OV2) · 9 = Overvoltage at constant speed (OV3) · 10 = Bus undervoltage (UV) · 11 = Motor overload (OL1) · 12 = VFD overload (OL2) · 18 = RS485 communication fault (CE) p.132~134, p.73 | |
| 2103H | 8451 (0x2103) | HR | VFD identifying code | U16 | R | 03 | GD20 = 0x0106 p.132~134 | |
| 3000H | 12288 (0x3000) | HR | Running frequency (output frequency) | U16 | ×0.01 Hz | R | 03 | p.132~134 |
| 3001H | 12289 (0x3001) | HR | Set frequency | U16 | ×0.01 Hz | R | 03 | p.132~134 |
| 3002H | 12290 (0x3002) | HR | Bus voltage | U16 | ×0.1 V | R | 03 | p.132~134 |
| 3003H | 12291 (0x3003) | HR | Output voltage | U16 | V | R | 03 | p.132~134 |
| 3004H | 12292 (0x3004) | HR | Output current | U16 | ×0.1 A | R | 03 | p.132~134 |
| 3005H | 12293 (0x3005) | HR | Rotating speed | U16 | rpm | R | 03 | p.132~134 |
| 3006H | 12294 (0x3006) | HR | Output power | S16 | ×0.1 % | R | 03 | 範囲 -300 ~ 300 % p.132~134 |
| 3007H | 12295 (0x3007) | HR | Output torque | S16 | ×0.1 % | R | 03 | 範囲 -250 ~ 250 % p.132~134 |
| 3008H | 12296 (0x3008) | HR | PID setting | S16 | ×0.1 % | R | 03 | 範囲 -100 ~ 100 % p.132~134 |
| 3009H | 12297 (0x3009) | HR | PID feedback | S16 | ×0.1 % | R | 03 | 範囲 -100 ~ 100 % p.132~134 |
| 300AH | 12298 (0x300A) | HR | Input state | U16 | R | 03 | 範囲 0 ~ 511 p.132~134 | |
| 300BH | 12299 (0x300B) | HR | Output state | U16 | R | 03 | 範囲 0 ~ 511 p.132~134 | |
| 300CH | 12300 (0x300C) | HR | AI 1 | U16 | ×0.01 V | R | 03 | 範囲 0 ~ 10 V p.132~134 |
| 300DH | 12301 (0x300D) | HR | AI 2 | U16 | ×0.01 V | R | 03 | 範囲 0 ~ 10 V p.132~134 |
| 300EH | 12302 (0x300E) | HR | AI 3 | S16 | ×0.01 V | R | 03 | 範囲 -10 ~ 10 V p.132~134 |
注意
- Printed page = PDF page − 5.
PortDock ですぐ読み出す
- 無料の PortDock Modbus Master をインストールし、機器と同じ通信設定で接続します。
- 中央の表のツールバーの «機器プロファイル…» でこの機器を選び «読み込む» — ポーリング表・セル名・型・局番が入ります(通信の既定値も合わせられます)。
- セル名に単位・倍率(例 «×0.01 Hz»)が付きます。画面の値は生の値なので、倍率を掛けて読みます。
- 機器なしで自分のプログラムを試験するには、PortDock Modbus Slave の «機器を模擬…» で同じマップ(例の値)を立ち上げます。
RS-485 の配線は 配線図作成ツール で、この機器の名前・局番・ボーレート・パリティを入れた図を描けます(端子番号はマニュアルで確認)。
JSON をダウンロード
- invt/gd20.json (GitHub の原本) · このサイトのコピー · 修正履歴
- schema.json — 形式の説明(JSON Schema)。table・address(0 始まり)・type・order は PortDock の CSV と同じです。
- ライセンス: CC BY 4.0 — 使うときは出典を明記してください:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
とこのページの URL。LICENSE · データ一式・版・変更点(英語) - 誤りを見つけたら、マニュアルのページを添えて GitHub の Issue でお知らせください。
出典
- Goodrive20 Series VFD Manual (GD20 VFD Manual) — INVT, V2.1 (2025-09) · P00 printed pp.31-32, P07.27 p.73, P14 pp.99-101, 7 communication protocol pp.117-140 (address table 7.4.2 pp.132-134, examples 7.5 pp.138-140) · 確認日 2026-11-01