PortDock

4–20 mA basics and troubleshooting — 2-wire, 4-wire, live zero, open loop

Why the signal starts at 4 mA, 2-wire vs 4-wire wiring, scaling, and how NAMUR NE 43 failure currents (3.6, 21 mA) tell open loops from sensor faults.

4–20 mA is how pressure, flow and temperature transmitters send a measurement as current. Current is the same everywhere in a series loop, so long wires and their resistance do not change the reading as long as the supply voltage is sufficient. The low end, 4 mA, is 0 %; the high end, 20 mA, is 100 %.

Live zero: why 4 mA

Because 4 mA flows even at 0 %, «measurement is zero» and «no current» (open loop, power off) can be told apart. A 0–20 mA signal puts 0 % at 0 mA and cannot. And since current always flows, a 2-wire transmitter can draw its own operating power from the same two wires that carry the signal.

Scaling formula

value = low + (current − 4) ÷ 16 × (high − low)
Current%0–10 bar transmitterVoltage across 250 Ω
4 mA00 bar1 V
8 mA252.5 bar2 V
12 mA505 bar3 V
16 mA757.5 bar4 V
20 mA10010 bar5 V

A device with voltage inputs only can take 4–20 mA as 1–5 V across a 250 Ω resistor (Ohm's law). PLC analog inputs convert the current to integer counts — the SIMATIC S7-1500 maps low–high to 0–27648 and the MELSEC iQ-R to 0–32000 (per the manufacturers' manuals). If counts look wrong, convert them back to mA first.

2-wire, 3-wire and 4-wire

TypeWiringPower
2-wire (loop-powered)Two wires carry both power and signalA DC supply somewhere in the loop runs the transmitter
3-wireSupply +, common, signal outputSupply and signal share the common wire
4-wire (active output)Two power wires + two signal wiresSeparately powered; the transmitter drives the current itself

The first wiring question is «who powers the loop?». A 2-wire transmitter cannot drive current on its own, so the loop needs a supply somewhere. Check in the manual whether the receiving input supplies power or only measures current. A 2-wire transmitter on an unpowered input leaves the loop with no supply at all; a 4-wire (active) transmitter on a powered input puts two sources in the loop.

2-wire: a series loop from the loop supply + through the transmitter and the input card's 250 Ω back to supply −. 4-wire: the transmitter has its own power and drives current from +OUT/−OUT into the input's 250 Ω. 1–5 V across 250 Ω
In a 2-wire loop one supply drives the transmitter and the input in series; a 4-wire transmitter has its own power and drives the current itself. 4–20 mA gives 1–5 V across 250 Ω.

When the loop voltage is too low

In a 2-wire loop the supply must exceed «the transmitter's minimum operating voltage + 20 mA × loop resistance (input resistance + wire resistance + any indicators)». If it does not, the current stops rising near the top of the range. For example, 20 mA through a 250 Ω input drops 5 V across that resistor alone. The transmitter's minimum voltage is in its manual.

Failure signals: NAMUR NE 43

Transmitters following NAMUR recommendation NE 43 output measurements only within 3.8–20.5 mA and signal a detected failure with 3.6 mA or less, or 21 mA or more. Whether a failure drives the output low or high is set in the transmitter; its manual explains how.

Current receivedMeaningCheck first
Near 0 mANo current flowsOpen loop, loop supply off or fuse, reversed polarity on a 2-wire device
≤ 3.6 mANE 43 failure signal (low)Transmitter diagnostics, broken sensor
3.6–3.8 mAOutside the NE 43 measurement rangeProcess below the low end, zero
3.8–4 mABelow the low end, inside the measurement rangeZero adjustment
20–20.5 mAAbove the high end, inside the measurement rangeRange setting
20.5–21 mAOutside the NE 43 measurement rangeProcess above the high end
≥ 21 mANE 43 failure signal (high)Transmitter diagnostics, short between signal wires

Finding an open loop on site

In PortDock

Published 2026-10-22