Multimeter Reading Checker
RS-485 A–B resistance and idle voltage, 4–20 mA (NE 43), 24 V drop, NPN/PNP output, RS-232 TX, ground difference — enter a reading, get a verdict and why.
Values you enter are calculated inside this browser and sent nowhere. Values are the commonly used standard figures — if the device manual says otherwise, the manual wins. Mind the power state and electric shock while measuring.
RS-485 A–B resistance (power off)
How to measure — Power off every device, leave the wiring as it is, and measure resistance (Ω) across A–B at any device. Enter the device count and bias resistors to compare with expected values.
Basis — Two 120 Ω terminations in parallel make 60 Ω. A receiver is typically 12 kΩ (one unit load); bias resistors can appear in series through a powered-off supply. Modbus spec: termination at both ends only (150 Ω, or 1 nF + 120 Ω in series). RC termination (1 nF in series) blocks DC, so a multimeter cannot see it.
RS-485 idle A–B voltage (bias)
How to measure — With power on and polling stopped (nobody transmitting), put red on B (D1·+) and black on A (D0·−) and measure DC volts.
Basis — TIA/EIA-485: receivers have a defined state beyond ±200 mV differential. Positive while idle means «1» (mark).
RS-485 A/B to SG voltage (common mode)
How to measure — Power on, then measure DC volts ① from A to SG (common · 0 V) and ② from B to SG. Entering only one is fine.
Basis — TIA/EIA-485: receiver common-mode range −7 to +12 V; usually between 0 and 5 V.
4–20 mA loop current
How to measure — Break the loop at one point and insert the meter in series on its mA jack — or divide the voltage across the receiver resistor (e.g. 250 Ω) by its value.
Basis — NAMUR NE 43: measurement 3.8–20.5 mA, failure signal ≤ 3.6 mA or ≥ 21 mA. 4 mA = 0 %, 20 mA = 100 %.
24 V supply — voltage at the device under load
How to measure — With loads such as valves and relays switched on, measure +24V–0V at the far device, not at the supply.
Basis — IEC 61131-2: 24 V DC supplies are generally allowed −15 % to +20 % (20.4–28.8 V). A drop of 5 % or less leaves margin.
NPN/PNP sensor output voltage
How to measure — With the sensor connected to the PLC input, measure DC volts between the output (usually black) and 0 V (blue), once with the sensor ON and once OFF.
Basis — IEC 61131-2 24 V DC inputs: ON ≥ 15 V (type 1) or ≥ 11 V (types 2/3), OFF ≤ 5 V. For NPN, input voltage = supply − output.
RS-232 TX idle voltage
How to measure — While nothing is sent, measure DC volts between pin 3 (TXD) and pin 5 (GND) of the PC-side DB9. Some adapters only drive TX once the port is open.
Basis — TIA-232: idle (mark) output −5 to −15 V, receiver threshold ±3 V, max ±25 V. +3.3/+5 V indicates a TTL UART.
Ground-to-ground voltage
How to measure — Measure between the PC's USB shell (or PC ground) and the device SG/PE, in both DC (V⎓) and AC (V~). Enter the larger.
Basis — Rule of thumb: under 1 V is comfortable; a few volts shrinks the RS-485 common-mode margin and drives current through non-isolated USB and RS-232.
To start from a symptom and find out what to measure, use the field troubleshooting wizard. To draw the wiring, use the wiring diagram maker. To size termination and bias resistors, use the RS-485 termination and bias calculator.
FAQ
Can I measure A–B resistance with power on?
No. Power off every device first. With power on the meter shows wrong values and the device or meter can be damaged.
I fitted termination but it reads «no termination»
RC termination (1 nF + 120 Ω in series) blocks DC with its capacitor, so a multimeter cannot see it. Choose RC in the «Terminator» field, or look at the end devices' termination switches and parts. Some devices also switch in internal termination only when powered.
Does «No issue found (in this measurement)» mean communication will work?
It means this one reading shows no problem. For other possible causes — settings, slave IDs, polarity, noise — continue with the troubleshooting helper.
Sources
- MODBUS over serial line specification and implementation guide V1.02 (2006) — §3.4.5, §3.4.6
- Texas Instruments, RS-422 and RS-485 Standards Overview and System Configurations (SLLA070D, 2010)
- Vaisala PR-33 — Default mA output value (NAMUR NE 43)
- Endress+Hauser RMA42 Operating Instructions (BA00287R) — NE 43
- IEC 61131-2 — Programmable controllers: equipment requirements (24 V DC supply, digital input types)
- TIA-232-F — Interface for serial binary data interchange (signal levels)