Enclosure Heat & Fan Sizing Calculator
Sum device heat loss, get natural dissipation from enclosure size and installation, then fan airflow (m³/h, altitude-corrected) and cooler or heater output.
Formulas
- Effective area A = Σ(face area × surface factor b) — exposed top 1.4, covered top 0.7, exposed sides (front, rear, sides) 0.9, rear against a wall 0.5, faces joined to another enclosure 0.5, floor 0 (IEC TR 60890 Table 3)
- Natural dissipation Pc = k × A × ΔT, ΔT = Ti − Tu, sheet steel k = 5.5 W/m²K
- Fan airflow V (m³/h) = f × (Pt − Pc) ÷ ΔT, f = 3.1 (sea level) … 5.2 (3500 m)
- Cooling unit output Pn = Pt − Pc (with a hotter ambient Pc is negative, so the heat coming in is added)
- Heater output Pv = k × A × (Ti − min ambient)
Formula by installation (W, H, D in m)
| 1. Single enclosure, free-standing on all sides | A = 1.8·H·(W+D) + 1.4·W·D |
| 2. Single enclosure, wall-mounted | A = 1.4·W·(H+D) + 1.8·D·H |
| 3. First or last in a row, free-standing | A = 1.8·W·H + 1.4·W·D + 1.4·D·H |
| 4. First or last in a row, wall-mounted | A = 1.4·H·(W+D) + 1.4·W·D |
| 5. Middle of a row, free-standing | A = 1.8·W·H + 1.4·W·D + D·H |
| 6. Middle of a row, wall-mounted | A = 1.4·W·(H+D) + D·H |
| 7. Middle of a row, wall-mounted, top covered | A = 1.4·W·H + 0.7·W·D + D·H |
Fan factor f by altitude
| Altitude (m) | f (m³·K/Wh) |
|---|---|
| 0 | 3.1 |
| 500 | 3.3 |
| 1000 | 3.5 |
| 1500 | 3.8 |
| 2000 | 4.1 |
| 2500 | 4.4 |
| 3000 | 4.8 |
| 3500 | 5.2 |
Between rows the higher value (more air) is used. Thinner air carries less heat per cubic metre.
How to read it
- Enter each device's «power loss» or «heat dissipation» from its manual. For power supplies use the loss (output × (1/efficiency − 1)), not the output; for drives use the manual's loss figure.
- Use the summer maximum for the ambient, and for the internal limit the allowed ambient of the most sensitive device (often 40, 45 or 55 °C in the manual).
- The fan airflow must be the real airflow with filters and grilles fitted — use the «with filter» airflow from the filter fan catalogue and allow for clogging. Air in at the bottom, out at the top (Rittal).
- If the ambient is above the internal limit, or only slightly below, a fan alone will not do — look at a cooling unit or heat exchanger. Where there is dust or oil, a heat exchanger or cooling unit keeps outside air out.
- This is an estimate that assumes well-mixed air. Sunlight, enclosure colour and hot spots from device layout are not included, so leave margin.
For heater current and wiring, use the heater power calculator. For the cable to the power supply, use the voltage drop calculator.
FAQ
What do I enter as equipment heat?
The «power loss / heat dissipation (W)» from the manual, not the rated output (kW). Drives lose a few percent of their rating as heat, and power supplies lose what their efficiency leaves. Add «×4» for several identical devices.
What if the outside air is hotter than the allowed inside temperature?
ΔT is negative, so heat flows in instead of out and fan ventilation cannot cool the cabinet. Look at the cooler output Pn.
Why does altitude matter?
Thinner air at altitude removes less heat for the same airflow. The fan factor f grows from 3.1 at 0 m to 5.2 at 3500 m, so more airflow is needed.