24 V DC Power Supply Sizing Calculator
Size a 24 V DC supply from the current, inrush and duty of PLCs, HMIs, sensors, valves, relays: total, rating with headroom, inrush check, protector channels.
Formulas
- Row current = qty × current × duty
- Total = sum of rows, power = total × supply voltage
- Rating needed = total ÷ (1 − headroom) (25 % headroom uses up to 75 % of the rating)
- Peak at power-on = Σ qty × max(inrush, current)
- Chosen rating: the smallest common size ≥ rating needed whose rating × peak % ≥ the power-on peak
Common sizes: 1.3 · 2.5 · 3.8 · 5 · 10 · 20 · 40 A — values often seen on DIN-rail 24 V supplies; they differ by maker and series.
What this does not cover
- Inrush duration: inrush is usually very short, so the supply's output capacitors may absorb it — or the supply may enter overload protection. Check the supply's peak rating, its duration and overload behaviour (current limit, hiccup) in the manual.
- Temperature derating: supplies deliver less current when the panel is hot (derating curve). Add headroom for it.
- Duty is an estimate. If valves can all switch on together (homing, releasing an emergency stop), use 100 %.
- Protector trip behaviour: whether a channel trips on inrush depends on the protector's manual (delay, adjustable types).
FAQ
How much headroom?
Typically 20–30 %. Add more for a hot panel or planned expansion. This calculator uses «load up to (100 − headroom) % of the rating».
What if I don't know the inrush?
Leave it blank and the steady current is used. For HMIs and PCs with large input capacitors, and for solenoids and relays, look for an inrush figure in the manual.
When is it better to use two supplies?
Feeding loads that cause dips when switching (valves, motors) separately from the PLC and communication keeps a dip on one side from restarting the other. The channel suggestion uses the same grouping.
Use with: Voltage drop & wire size calculator · 24 V DC supply check guide · 4–20 mA loop load calculator