Fine on the bench, CRC errors and timeouts on site? Line up error times with machine activity, then check wiring near drives, ferrites, routing, isolation.

Tools for this guideModbus Master Windows program · freePlot Windows program · freeRS-485 Termination & Bias Calculator web · no installSerial Timing Calculator web · no install

«It was fine on the bench, but once the machine runs it drops out now and then» is the usual shape of a field communication problem. Noise is invisible, so before clipping on ferrites by instinct, collect «when» the errors happen — that cuts the list of likely causes sharply.

1. Is it noise at all?

PatternLikely causes
Never answered even onceSettings or wiring rather than noise — ID, baud, parity, A/B (see the no-reply guide)
Always the same device, at the same rateThat device's termination, wiring, duplicate ID, poll spacing
Errors bunch up while machines run or at certain timesNoise, or voltage dips on a shared supply
Many CRC errors, corrupted bytesNoise, termination, bias, baud vs length
Everything times out for a while, then recoversDevice restart (power), adapter dropout, transceiver protection from ground differences

2. Record when errors happen

Keep the time of each error down to the second. Then find out what moved at the same time — a drive starting or stopping, a servo accelerating, a welder, a heater, a big solenoid — from the machine's log or the operator, and line them up. A handful of matches is often enough to see a rule like «every time the conveyor drive starts». Also check whether errors cluster by time of day (shift change, lunch, night runs).

Where possible, put the load on the same time axis. If you can read the drive's output frequency or current over Modbus, log it too; if a device streams values over serial, plot them in Plot. Errors bunched in «acceleration» or «high current» stretches point at that machine's wiring first.

3. Near drives and servos, look here first

Drives and servo amplifiers switch their output voltage rapidly (PWM), pushing high-frequency current through the motor cable and earth. When a communication cable runs nearby, check in this order.

4. On the communication cable

5. Things that look like noise

6. Change one thing, compare numbers

Apply several fixes at once and you will not know which one worked. Change one thing, then compare CRC errors and timeouts per request over the same period under the same operating conditions. A table of what changed, when, and the error counts lets the next person carry on.