MC Protocol (SLMP) Frame Decoder

Paste an MC protocol (SLMP) 3E or 4E frame as HEX or ASCII to decode the header, command, device, points, values and end code. It can build requests too.

Examples

Everything is decoded in your browser; nothing you paste is sent anywhere.

Build a request

Builds batch read/write requests (0401/1401, subcommands 0000/0001) for the own station (00, FF, 03FF, 00) with monitoring timer 0010.

FAQ

How does it tell binary from ASCII?

If the text reads as HEX and the first two bytes are 50 00 (3E request), D0 00 (3E reply), 54 00 (4E request) or D4 00 (4E reply), it is binary; if the characters start with 5000, D000, 5400 or D400, it is ASCII. When both fit, as with «500000FF…», it picks the one whose header length field matches what actually follows. An ASCII frame written as HEX (35 30 30 30 …) is decoded as ASCII too.

Why does the reply have no device numbers?

An MC protocol reply carries only the values after the end code. Which device they belong to is in the request, so put the request in «Matching request» to see D100, D101 … next to the values. Without it the data is split into 16-bit words.

In binary 03FF shows up as FF 03

Binary code sends numbers low byte first (little-endian). I/O number 03FF is FF 03, length 12 is 0C 00, command 0401 is 01 04. ASCII code writes hex characters high digit first, so it stays «03FF».

What is «End code PortDock PLC Simulator would return»?

The request checked against PortDock PLC Simulator's handling rules (point limits, device codes, data length). Numbers beyond the device size (C056), «Own station requests only» (C05F) and Execute Monitor before any registration (C05D, from 0.6.0) depend on the app's state and are not checked here. A real PLC may answer differently depending on model and settings.

End codes (described by this decoder)

CodeNameWhen PortDock PLC Simulator answers with it
C050ASCII conversion errora non-hex character in ASCII code, or A–F in a decimal device number
C051points out of range (words)batch read/write word points are 0 or above 960
C052points out of range (bits)batch read/write bit points are 0 or above 7168 (binary) / 3584 (ASCII)
C053random points out of range (bits)random write bit points are 0 or above 188 (94 for subcommand 0003)
C054random points out of range (words)random read/write word and double-word points are 0 or above the limit
C056address out of rangea number beyond the device size (points)
C057request length mismatchthe header's request data length differs from what actually follows
C059wrong command/subcommanda command or subcommand that is not implemented
C05Bdevice cannot be accessedan unknown device code, or a word device in bit units
C05Crequest data errorloopback data count outside 1–960, or a wrong mode value in a remote operation
C05Dmonitor not registeredExecute Monitor (0802) before Entry Monitor Device (0801)
C05Fwrong access destinationa request for another station («Own station requests only» on)
C060bit request errora bit write value other than 0 or 1
C061data length mismatchcommand data shorter or longer than the point count

Names are shortened from MELSEC iQ-R Ethernet User's Manual (Application) SH-081257ENG 3.5 «List of Error Codes». Which condition gets which code was chosen by PortDock PLC Simulator; a real PLC or module may differ.

Device codes

DeviceNameBinary codeNumberingType
XInput9Chexbit
YOutput9Dhexbit
MInternal relay90decimalbit
LLatch relay92decimalbit
FAnnunciator93decimalbit
BLink relayA0hexbit
SMSpecial relay91decimalbit
DData registerA8decimalword
WLink registerB4hexword
RFile registerAFdecimalword
ZRFile register (serial numbers)B0hexword
SDSpecial registerA9decimalword
TSTimer contactC1decimalbit
TCTimer coilC0decimalbit
TNTimer current valueC2decimalword
CSCounter contactC4decimalbit
CCCounter coilC3decimalbit
CNCounter current valueC5decimalword

References

Built from Mitsubishi Electric's public manuals (SLMP and MC protocol); not affiliated with Mitsubishi Electric.

For a field-by-field walkthrough see Reading an MC protocol 3E binary frame; for end codes see MC protocol end codes: what to check.

To test your own program's communication without a PLC, use PortDock PLC Simulator — Testing MC protocol communication without a PLC.

To look at a whole Wireshark or pktmon capture (request/response pairs, response times, missing replies) use the Industrial pcap Analyzer. Clicking a row there opens that frame in this decoder.