Cable shields and grounding are argued differently on every site, and documents disagree too — «one end only» versus «both ends». Both have reasons, so decide by what you are trying to block and by the installation rules for the device or bus. This guide centres on RS-485 (Modbus RTU); the same thinking carries over to analog lines such as 4–20 mA.
Three conductors, three jobs
| Conductor | Job | Where it goes |
|---|---|---|
| A/B (D0/D1) twisted pair | The signal — the difference between two wires | A to A and B to B at every device |
| SG (signal ground, common, 0V, C) | Keeps the transceivers' reference voltages together | One wire linking every device's SG terminal |
| Shield (braid, foil) | Catches outside noise before it reaches the pair | Protective earth (PE) or panel ground — one end or both |
A common mistake is to use the shield as SG. The shield is a path that drains noise current to earth; SG is the signal reference. If noise current flows in the shield and you use it as the reference, the noise moves the reference. Unless the device manual says otherwise, use a cable with a twisted pair, one more conductor (or pair) for SG, and a shield, and run SG on its own wire. The Modbus serial line specification likewise calls for a balanced pair (D0, D1) and a «third wire (Common)» on RS-485.
Why SG must be connected
An RS-485 receiver reads the «difference» between the wires, but each wire must also stay within a range relative to the receiver's own ground (−7 V to +12 V for standard transceivers). Devices on different supplies have ground potential differences, and without an SG wire that difference rides on the common-mode voltage and can exceed the range. A TI note puts it this way: systems are often drawn without a separate ground wire, but the laws of physics still require a solid ground connection between drivers and receivers.
Ground loops
Tie the SG wire or the shield directly to the ground at both devices, and the potential difference between those grounds drives current through it — a ground loop. When the difference jumps, for instance as a large motor starts, the loop current couples into the signal pair as common-mode noise. TI's application notes say this is why the RS-485 standard suggests a resistor between logic ground and chassis ground (100 Ω in their figure), and that the loop still leaves the link sensitive to noise elsewhere, so for long distances and large potential differences the robust approach is an isolated transceiver (isolated DC/DC plus a digital isolator).
Shield grounded at one end
The Modbus serial line specification says that at one end of each cable the shield must be connected to protective ground, and that the Common should be connected directly to protective ground at one point only for the whole bus, generally at the master. Grounding the shield at one end creates no loop through it, and it still blocks electric-field (capacitively coupled) noise well. Ground it at the panel (master) side and, at the far device, trim and insulate the shield or land it where the device manual says.
Shield grounded at both ends
Magnetic and high-frequency noise is cancelled better when both ends of the shield are grounded, because a counter-current can flow in it. That is why the PROFIBUS (PI) guideline and some drive makers' bus cable instructions connect the shield at «both ends» over a wide area — and require an equipotential bonding conductor run close to the cable so the grounds stay at the same potential. Grounding both ends without bonding sends ground loop current through the shield. Some guidelines also describe a compromise: direct at one end, through a small capacitor at the other.
So how do you decide?
- Follow the installation rules of the device or bus first. Different buses in the same panel may need different treatment.
- Modbus RTU (RS-485) with nothing in the device manual: shield grounded at the panel end, SG run to every device on its own wire and tied to protective earth at one point only.
- Different buildings or long runs with large ground differences: consider isolated transceivers or isolated repeaters before arguing about shields.
- Keep shield pigtails short — a long twisted tail weakens shielding at high frequency. Guidelines often show a clamp that grips the shield over a wide area.
- Where the cable breaks and continues at a middle device, carry the shield through as well (even when grounded at one end, the shield should be one continuous piece).
Distance from power cables, and crossings
The biggest win is not putting drive output, motor or supply cables in the same duct as communication cables. The recommended separation differs between manufacturers' documents, from a few centimetres to tens of centimetres, so use the figure in the wiring chapter of the drive or servo manual you have. Where cables must cross, many manuals agree: do not run them alongside — cross at a right angle, briefly. In shared metal trunking, use one with a divider.
Reading the symptoms
| Symptom | Look at |
|---|---|
| CRC errors or timeouts only while a certain motor or drive runs | Shared duct with power cables, shield not connected, pigtail length |
| Only devices in another building or panel drop out or lose transceivers | Ground potential difference, SG missing — consider isolation |
| Noise got worse after grounding the shield at both ends | No equipotential bonding — loop current in the shield |
| Odd behaviour on panel fuses or earth leakage after linking SG | SG tied straight to protective earth in several places — use one |
In PortDock
- «Wiring Diagram Maker» web tool: draws RS-485 2-wire or 4-wire wiring for your device count and IDs, with a checklist for A, B, SG and shield, as SVG or PNG.
- Modbus Master counts requests, timeouts and CRC errors per table. Compare the counts over the same period before and after changing the shield or SG wiring.
- Serial: leave reception on without sending and you can see garbage bytes, with timestamps, arriving as a motor starts.
Sources
- MODBUS over Serial Line Specification and Implementation Guide V1.02 — §3.4 — balanced pair plus common, common to protective ground at one point, shield to protective ground at one end
- TI SLLA070D — RS-422 and RS-485 Standards Overview and System Configurations — §4.5 ground connections — separate ground wire, resistor between logic and chassis ground, isolation
- TI SLLA272 — The RS-485 Design Guide — §11 grounding and isolation — ground potential difference, ground loops
- PI — Functional Bonding and Shielding of PROFIBUS and PROFINET (8.102) — shield at both ends with equipotential bonding
- SEW-EURODRIVE — Shielding and routing bus cables — bus cable shield at both ends, separation from power cables, equipotential bonding