CT Ratio, Secondary Current & Burden Calculator

Primary ↔ secondary current by CT ratio, and total burden (VA, Ω) from round-trip leads and the meter against the CT rating. For 1 A and 5 A secondaries.

Conversion
CT ratio
Secondary at this primary
Of rated primary
Primary at this secondary

Secondary burden

Round-trip lead resistance
Lead burden
Meter input (Ω)
Total burden (resistive part)
Of CT rated burden
Secondary terminal voltage at rated current

Ratio correction factor (actual ÷ marked)

RCF
Ratio error (RCF − 1)
Multiply readings by

The defaults (200/5 A, 10 m one way, 2.5 mm², meter 1 VA, rated 5 VA) are an example. Enter the meter's input burden and the CT's rated burden from their datasheet and nameplate.

Results update as you type. Everything runs in your browser; nothing you type is sent anywhere.

Never open the secondary

Opening a CT secondary while current flows forces all the primary current through the exciting branch and produces very high voltage peaks at the secondary terminals. A voltmeter may barely show them, but they can break down insulation and are dangerous to people; ABB's guide says an open secondary should be treated as a serious accident and, where larger CTs may be opened, a protective circuit should be permanently connected to the secondary terminals (p.26). The same guide notes that the secondary circuit is grounded to keep the voltage at meters safe (p.5).

Formulas

  • CT ratio = rated primary ÷ rated secondary (e.g. 200/5 → 40)
  • Secondary = primary ÷ ratio, primary = secondary × ratio
  • Burden VA = I² × R, meter Ω = meter VA ÷ (rated secondary)²
  • Round-trip lead = ρ × (2 × one-way length) ÷ area, copper ρ20 = 1/58 Ω·mm²/m
  • RCF = actual ratio ÷ marked ratio; RCF > 1 means the meter reads low → reading × RCF

Lead burden by size and distance (copper, 20 °C)

SizeOne wayRound-trip ΩVA at 5 AVA at 1 A
1.5 mm²5 m0.1152.870.115
1.5 mm²10 m0.2305.750.230
1.5 mm²20 m0.46011.490.460
1.5 mm²50 m1.14928.741.149
2.5 mm²5 m0.0691.720.069
2.5 mm²10 m0.1383.450.138
2.5 mm²20 m0.2766.900.276
2.5 mm²50 m0.69017.240.690
4 mm²5 m0.0431.080.043
4 mm²10 m0.0862.160.086
4 mm²20 m0.1724.310.172
4 mm²50 m0.43110.780.431

On the same wire a 1 A secondary has 1/25 of the burden (I²R) of a 5 A one. The longer the run, the more it matters.

Standard burdens (IEEE C57.13, 5 A secondary) — ABB guide p.13

DesignationImpedance ΩVA at 5 APower factor
B-0.10.12.50.9
B-0.20.25.00.9
B-0.50.512.50.9
B-0.90.922.50.9
B-1.81.845.00.9

The metering burdens from the same guide (IEEE, 60 Hz). For a CT not rated 5 A, multiply the ohms by (5 ÷ rated current)²; the VA at rated current stays the same — 2.5 VA on a 1 A CT is 2.5 Ω. IEC rated burdens and accuracy-class error limits are not shown: we have not checked the IEC 61869-2 text.

Where it is used

  • Setting a power meter's CT ratio: enter the rated primary and secondary (e.g. 200/5) and the meter shows the real current. In the LS ELECTRIC GIMAC1000 and Rootech Accura device maps, measurements already include the PT/CT ratio, so do not multiply values read over Modbus again.
  • Choosing a CT: see what percentage of the rated primary your normal load is («Of rated primary» above). An oversized CT gives a small secondary current at the bottom of the meter's range.
  • Long secondary runs easily push lead burden past the CT's rating. Use thicker wire, put the meter closer, or use a 1 A secondary CT.

FAQ

What does a 200/5 CT ratio mean?

200 A in the primary gives 5 A in the secondary; the ratio is 40. 150 A primary gives 3.75 A secondary.

How do I calculate CT burden?

Add every resistance in the secondary circuit and multiply by the square of the rated secondary current (VA = I² × R). Convert the meter's input burden (VA) to ohms, and count the leads both ways. 2.5 mm² copper, 10 m one way, is about 0.138 Ω round trip: about 3.45 VA at 5 A.

How do I check CT ratio error?

Divide the actual ratio (primary and secondary measured together) by the marked ratio: that is the ratio correction factor (RCF). As in ABB's example, 20.2 : 1 actual against 20 : 1 marked is RCF 1.01, a 1 % ratio error, and the meter reads 1 % low.

1 A or 5 A secondary?

ABB's guide gives typical CT outputs of 1–5 A (p.4). On the same wire a 1 A secondary has 1/25 of the lead burden of 5 A, which helps on long runs. Check which input your meter takes first.

Guide on CT ratio settings, burden and open secondaries: CT ratio, secondary current and burden basics. For kVA and power factor from a meter's current and power, use the Three-Phase Power Calculator. For wire resistance and voltage drop by size, use the Voltage Drop & Wire Size Calculator.

Basis

CT ratio, RCF, standard burdens and the open-secondary warning follow ABB «Instrument Transformers — Technical Information and Application Guide» (1VAP420003-TG, December 2004 Rev. A) pp.4, 5, 10, 13, 26. VA = I²R is a definition; copper resistivity follows IEC 60028 (1/58 Ω·mm²/m, 0.00393 /°C) as in the voltage drop calculator. Meter input burdens come from each meter's datasheet.

ABB guide PDF (ABB Library)