Three-Phase Power Calculator (kVA, kW, kvar, A, PF)

Three- or single-phase: from voltage, one of amps, kW or kVA, and power factor, get apparent, real and reactive power and current. Power factor from kW and kVA.

Results
Line current
Apparent power S
Real power P
Reactive power Q
Phase angle φ

The defaults (three-phase 380 V, 30 A, power factor 0.85) are an example. Real power factor changes with load, so enter meter or nameplate values.

Find the power factor

Results update as you type. Everything runs in your browser; nothing you type is sent anywhere.

Formulas

  • Three-phase: S = √3 × V × I, single-phase: S = V × I (V line-to-line for three-phase)
  • P = S × cos φ, Q = S × sin φ = √(S² − P²)
  • Power factor cos φ = P ÷ S = P ÷ √(P² + Q²)
  • I = S ÷ (√3 × V) (three-phase), I = S ÷ V (single-phase)

kVA, kW and kvar

  • Real power P (kW) turns into work (heat, rotation); reactive power Q (kvar), such as a motor's magnetization, flows back and forth without doing work; apparent power S (kVA) is their combined size, voltage × current. ABB's Motor guide describes P and Q together making up S, and calls the ratio of kW to kVA the power factor.
  • Cables, breakers and transformers are sized by current, so look at kVA (or amps), not kW. The same kW at a lower power factor needs more current: 100 kW at 400 V is 144 A at power factor 1 and 180 A at 0.8.
  • To raise the power factor with capacitors, see the power factor correction capacitor calculator.

kVA ↔ current (three-phase, independent of power factor)

kVA220 V380 V400 V440 V
12.621.521.441.31
513.127.607.226.56
1026.215.214.413.1
3078.745.643.339.4
50131.276.072.265.6
100262.4151.9144.3131.2
300787.3455.8433.0393.6
5001312.2759.7721.7656.1
10002624.31519.31443.41312.2

For motors

A motor nameplate's kW is shaft output; the electrical input is larger by the efficiency. To get current from output kW, use the motor current calculator, which includes efficiency. This calculator converts electrical-side kW, kVA and amps, such as meter readings.

FAQ

How do I convert kVA to kW?

kW = kVA × power factor. At 0.8, 100 kVA is 80 kW. Without the power factor, kVA alone does not give kW.

How many amps is 1 kVA at 380 V three-phase?

1000 ÷ (1.732 × 380) ≈ 1.52 A. The kVA-to-current relation does not involve the power factor.

Can I get the power factor from kW and amps?

With the voltage, yes: power factor = kW × 1000 ÷ (√3 × V × I). Entering kW and kVA (= √3 × V × I ÷ 1000) under «Find the power factor» gives the same.

What is 2.2 kVA at 220 V single-phase?

2200 ÷ 220 = 10 A (set the supply to single-phase).

To get current from motor output (kW, HP) and efficiency, use the Motor Current Calculator. To raise the power factor with capacitors, use the Power Factor Correction Capacitor Calculator. For a power meter's CT ratio, secondary current and burden, use the CT Ratio & Burden Calculator. For heater kW and heater current, use the Heater Power Calculator.