Checking a 24 V DC supply — capacity, inrush, voltage under load, 0 V common, fuses

When a 24 V supply sags, devices restart and it looks like a communication fault — capacity, inrush, voltage under load, the 0 V common, fuses and protectors.

Tools for this guideModbus Master Windows program · freePlot Windows program · free24 V DC Power Supply Sizing Calculator web · no installVoltage Drop & Wire Size Calculator web · no install

A panel's 24 V DC supply often feeds the PLC, sensors, remote I/O, communication devices and valves together. When it runs short or dips, devices restart and do not answer meanwhile, which looks like «communication dropping out». Checking the supply once is worth it before touching communication settings.

1. Capacity: total and headroom

Add up the current of everything on that supply from the manuals. Small loads such as sensors and I/O add up in numbers, and valves, relay coils, lamps and fans are easy to forget. A total close to the supply's rated current sags when it is hot or when loads coincide. Many supplies document a derating curve — less available current at higher ambient temperature — so use the temperature inside the panel.

2. Inrush

Devices with large input capacitors (HMIs, PCs, drive control supplies) draw a large current briefly when powered, and solenoid valves, relays and motors do so when switched on. If that pushes the supply into overload protection (current limiting, or switching off and retrying) or makes the voltage sag, other devices on the same supply restart. The symptom is «every time the valve operates» or «some devices do not come up at power-on».

3. Measure voltage under load

4. The 0 V common

It is easy to care about +24 V and treat 0 V as «connect it anywhere». When several devices share one 0 V wire, a large load's current in that wire drops voltage and shifts the reference of everything else on it. Take separate 0 V runs from the supply terminals for large loads (valves, motors) and for the PLC and communication devices. Whether and where 0 V is tied to protective earth (PE) follows the panel's design rules; tying it in several places makes a ground loop.

5. Fuses and circuit protectors

6. Communication errors that are really power

PatternPossible supply cause
A few seconds of timeouts each time a valve or motor switches onInrush sag → device restart
Only distant devices drop out under heavy loadVoltage drop in the wiring, shared 0 V
Some devices do not answer after power-on, fine after a power cyclePower-up order or inrush leaves them half started
Worse in the afternoon or in summerSupply derating with panel temperature
Device settings revert to defaults after an errorRestart plus settings never saved (see the commissioning guide)

Whether a device restarted can be read from an «uptime» or «power-on count» register if it has one, or seen from its display and status LEDs. If it restarted, look at power before communication.