A panel's 24 V DC supply often feeds the PLC, sensors, remote I/O, communication devices and valves together. When it runs short or dips, devices restart and do not answer meanwhile, which looks like «communication dropping out». Checking the supply once is worth it before touching communication settings.
1. Capacity: total and headroom
Add up the current of everything on that supply from the manuals. Small loads such as sensors and I/O add up in numbers, and valves, relay coils, lamps and fans are easy to forget. A total close to the supply's rated current sags when it is hot or when loads coincide. Many supplies document a derating curve — less available current at higher ambient temperature — so use the temperature inside the panel.
2. Inrush
Devices with large input capacitors (HMIs, PCs, drive control supplies) draw a large current briefly when powered, and solenoid valves, relays and motors do so when switched on. If that pushes the supply into overload protection (current limiting, or switching off and retrying) or makes the voltage sag, other devices on the same supply restart. The symptom is «every time the valve operates» or «some devices do not come up at power-on».
3. Measure voltage under load
- No-load voltage almost always reads about 24 V. With the machine running, measure at the «supply terminals» and at the «terminals of a distant device» and compare; the difference is the voltage drop in the wiring.
- Take the device's allowed range from its supply specification. Many PLC manuals give 20.4–28.8 V (24 V −15 % to +20 %) for 24 V DC inputs, but some makers state −10 % (21.6 V) as the lower limit, so use that device's figure.
- A multimeter misses short dips. If it has MIN/MAX recording, turn it on and operate the valves and motors. Ripple and dips of a few milliseconds need an oscilloscope.
- Turning up the supply's output adjust (+V ADJ) to cover the drop is temporary. The drop changes with load current, so fix it with wire size, layout or separate supplies.
4. The 0 V common
It is easy to care about +24 V and treat 0 V as «connect it anywhere». When several devices share one 0 V wire, a large load's current in that wire drops voltage and shifts the reference of everything else on it. Take separate 0 V runs from the supply terminals for large loads (valves, motors) and for the PLC and communication devices. Whether and where 0 V is tied to protective earth (PE) follows the panel's design rules; tying it in several places makes a ground loop.
5. Fuses and circuit protectors
- Switched-mode supplies limit their short-circuit current or switch off and retry, so a large breaker may not trip promptly on a short. Read the supply's overload behaviour together with the trip curve of the breaker or fuse.
- Split one supply into branches, each with a fuse or electronic circuit protector, so a short on one branch leaves the others (especially PLC and communication) running.
- Size each branch protector so it does not trip on that branch's inrush — if it does, choose a delayed or adjustable type.
- Electronic protectors that log trips tell you when they tripped, which is handy to line up with communication error times.
6. Communication errors that are really power
| Pattern | Possible supply cause |
|---|---|
| A few seconds of timeouts each time a valve or motor switches on | Inrush sag → device restart |
| Only distant devices drop out under heavy load | Voltage drop in the wiring, shared 0 V |
| Some devices do not answer after power-on, fine after a power cycle | Power-up order or inrush leaves them half started |
| Worse in the afternoon or in summer | Supply derating with panel temperature |
| Device settings revert to defaults after an error | Restart plus settings never saved (see the commissioning guide) |
Whether a device restarted can be read from an «uptime» or «power-on count» register if it has one, or seen from its display and status LEDs. If it restarted, look at power before communication.
In PortDock
- «Voltage Drop & Wire Size Calculator» web tool: voltage at the device from current, length and wire size.
- «4–20 mA Loop Load Calculator» web tool: voltage left for 2-wire transmitters fed from the same 24 V.
- Modbus Master: log a device's uptime or voltage registers (if any) with «Value log (CSV)» next to the timeout times. The moment uptime goes back to 0 is when it restarted.
- Plot: if a meter or board streams the voltage over serial, graph it and record CSV.
Sources
- Schneider Electric — Modicon M262 DC power supply characteristics — supply voltage range 20.4–28.8 Vdc
- SEW-EURODRIVE — DC 24 V supply — −10 %/+20 % tolerance according to EN 61131-2
Published 2026-10-31