An oscilloscope shows RS-485 problems best, but on site the tool in hand is usually a multimeter. It cannot show waveforms, but it tells you quite reliably «how many terminators there are», «whether the bus is biased», «whether a line is shorted to ground» and «whether a device has A/B swapped». Names here follow Modbus, A = D0 and B = D1 — some devices label A and B the other way round, so check the D+/D− marking in the manual too.
1. Power off: count terminators with A–B resistance
Turn off every device on the bus (master and adapter included) and measure the resistance between A and B at any device's terminals. Only ever measure resistance with the power off.
| Reading (approx.) | Meaning |
|---|---|
| About 60 Ω | Two 120 Ω terminators (both ends) — as it should be |
| About 120 Ω | Only one terminator — one end missing |
| About 40 Ω or less | Three or more — middle devices are terminated too |
| Hundreds of Ω to several kΩ | No termination (transceiver inputs only; about 1 kΩ if bias resistors show through the power circuit) |
| Near 0 Ω | A–B short — check wiring and terminals |
| About 75 Ω | Two 150 Ω terminators (the Modbus spec's 150 Ω) |
Terminators built as 1 nF in series with 120 Ω are invisible to a DC ohmmeter. A device with bias resistors on the bus can make the reading slightly lower through that path. If in doubt, disconnect devices one at a time and watch how the value changes.
2. Power off: shorts and breaks
- A–SG or B–SG near 0 Ω means a line is touching the common or the shield.
- Check A–shield, B–shield and SG–shield the same way.
- Continuity: with devices disconnected, briefly tie A and B together at the far end and measure A–B at the near end — you should see the cable's loop resistance (a small value). Untie them and it should read high again. Check SG the same way.
3. Power on, nobody sending: bias
Stop the master's polling so nobody transmits, and measure B − A on DC volts (black lead on A, red lead on B). With bias, B must sit above A while idle, by more than the receivers' 200 mV threshold, or garbage bytes come in.
| B − A (idle) | Meaning |
|---|---|
| +0.2 V or more | The bus is biased |
| 0 to +0.2 V | No or weak bias — check values with the calculator |
| Negative (−0.2 V or below) | This device labels A/B the other way, or the wires are swapped |
| Well above 1 V | Termination missing, or someone is transmitting continuously |
For example, with 560 Ω pull-up and pull-down from 5 V and 120 Ω at both ends, idle B − A is about 0.25 V (5 V × 60 Ω ÷ 1180 Ω). Repeat the measurement at each device's terminals: if one device alone shows the opposite sign, its A/B is swapped.
4. Power on: each line against SG (common mode)
Put the black lead on that device's SG (common) and measure A and B separately. In the example above A is about 2.37 V and B about 2.63 V, both near half the supply. Standard transceivers need each line within −7 V to +12 V of their own ground. If a distant device reads far outside that, or devices differ a lot, SG is not connected or the ground potential difference is large. Measure on AC volts as well to see whether a large AC voltage rides on the lines while machines run.
5. Readings during traffic
Measure DC volts while polling and you see the average of the data, smaller than at idle and jumping about. That only shows «something is transmitting»; it says nothing about signal quality. Take voltages at idle, and use an oscilloscope for waveforms, reflections and noise.
6. Keep the readings
Write one line per device — «A–B resistance (power off)», «B − A (idle)», «A–SG and B–SG (idle)» — and the device where values change stands out. Enter the readings in the «Multimeter Reading Checker» below to get a «no issue / worth a look / problem» verdict.
In PortDock
- «RS-485 Termination & Bias Calculator» web tool: works out what idle B − A should be for your pull-up, pull-down and terminators, to compare with your reading.
- «Wiring Diagram Maker» web tool: draw the measured bus for your device count and IDs and mark where the terminators are.
- Modbus Master: use «Pause all polling» to get an idle bus for measuring, then resume and see whether the error counts change.
- Serial: leave reception on at idle to see the garbage bytes that weak bias lets in.
Sources
- TI SLLA070D — RS-422 and RS-485 Standards Overview and System Configurations — receiver ±200 mV, common mode −7 V to +12 V, termination
- MODBUS over Serial Line Specification and Implementation Guide V1.02 — §3.4 — D0/D1 naming, 150 Ω or 1 nF + 120 Ω termination, 450–650 Ω biasing
Published 2026-10-31