Communication failures rarely come out of nowhere. Terminals loosen a little at a time, a panel filter clogs and the temperature rises, errors go from a few a day to dozens — and then someone calls to say «communication is down». The point of routine checks is to see that trend first. Set the interval on site from how critical the machine is and its environment (dust, vibration, heat), measure the same items the same way each time and compare with last time.
Safety: work on power terminals or the main circuit (AC 230/400 V) is done by a qualified person following site rules (permit, lock-out, tag-out) — isolate, then verify absence of voltage with a tester. A drive keeps voltage on its internal capacitors after isolation, so wait the discharge time given in its manual (usually several minutes).
1. Terminals, connectors, cables
- Tightness of communication terminals (A/B, SG, shield) and device power terminals — screw terminals work loose on machines that vibrate. Use the terminal block maker's torque.
- Connector (DB9, RJ45, M12) screws and latches; no cable pulling on a connector.
- Damaged, kinked or crushed sheaths, wear in moving parts (cable carriers), and no new cable routed into a power duct.
- The shield is still grounded where it was decided (one end or both), no corrosion at ground terminals.
- On RS-485, measure A–B resistance once during a power-off maintenance window (about 60 Ω with two terminators) and A/B to SG for shorts, so the next check can compare.
2. Error-rate trend
Look at «how many requests out of how many fail» rather than «does it communicate». If the master (PLC, HMI or PC program) keeps statistics, write down timeouts and CRC errors per device at every check. The values saved at commissioning are the baseline. If errors have grown, narrow down which device and from what time (while the machine runs?) first. On Ethernet, also check a managed switch's per-port error counters (CRC, collisions) and that link speed and duplex have not changed.
3. Panel environment — fans, filters, temperature
- Panel fans run and filters are not clogged — a clogged filter raises the temperature inside and shortens the life of devices and power supplies.
- Measure the temperature inside the panel and compare with the devices' operating range. Measuring once at the hottest time (a summer afternoon) is worthwhile.
- Water, condensation, dust build-up, door gaskets.
- Measure the 24 V supply output under load and compare with the last value.
4. UPS
- UPS status and alarm history, battery replacement date (the maker's recommended interval) and self-test results.
- The equipment on the UPS is still what was planned — devices added later increase the load and shorten the runtime in an outage.
- If the PC shuts down on a UPS signal, that link (USB, serial or network) still works.
5. Equipment PC — disks, crashes, shutdowns
A PC that runs a machine stays on for years, so disk wear and unexpected shutdowns pile up. The Windows event logs record blue screens (stop codes), sudden power loss (Kernel-Power 41) and unexpected shutdowns (6008). NVMe disks keep their own wear, spare capacity and media error counts. Writing these down at each check lets you see «crashes have increased since last month» or «wear is climbing fast» in advance. If wear is high or media errors appear, first make sure the backups are current before replacing anything.
6. Are the backups current?
- The PLC program, HMI project, device parameters and PC program settings were backed up after the last change.
- Backups are not kept only on that PC (a copy elsewhere).
- A backup actually opens — try it once on another PC.
7. Time synchronisation
If the PC, PLC and HMI clocks disagree, their records cannot be lined up when something fails. Check that time synchronisation (Windows Time service) is on for the equipment PC, when it last synced, and how many seconds the PLC and HMI clocks differ from the PC. On an isolated network, check that a time server on site is used.
8. Keep a record
One sheet per check: date, who checked, the measured values for each item (error counts, temperature, voltage, resistance) and what was done (tightened, cleaned, replaced). Mark the items whose values changed since last time so the next person knows where to start. How to record a fault when one happens is in «Logging communication faults and keeping a maintenance log».
In PortDock
- Port Inspector «This PC»: Fast Startup, power saving, update restarts, time sync and recent unexpected shutdowns and hardware errors, and (from 0.10.0) blue screen stop codes and disk health (NVMe), without admin rights. Save the result at each check to compare.
- Modbus Master: per-table statistics (requests, timeouts, CRC, response time) and (from 0.10.0) «Possible causes…» — poll for a while at each check and write down the error rate.
- Net Scan: save the device list as CSV, and at the next check compare for missing devices, new devices and possible IP conflicts.
- «Commissioning Checklist Maker» web tool: pick device types for a step-by-step checklist — ticks and notes saved, print or CSV.
- «Blue Screen (BSOD) Stop Code Lookup» web tool: possible causes and checks for a stop code you found in the logs.
Sources
- TI SLLA272 — The RS-485 Design Guide — termination, biasing, grounding — what the measured values mean
- SEW-EURODRIVE — Shielding and routing bus cables — bus cable shielding and separation from power cables
- Microsoft Learn — Windows Time service tools and settings — w32tm for sync status and time source
Published 2026-10-31