Removing a device from a bus — moving the terminator, dropping it from polling, leftover cable, shield

Taking a device out: move the terminator if it was at the end, drop it from polling (or it times out every cycle), tidy leftover cable, keep the shield intact.

Tools for this guideModbus Master Windows program · freeNet Scan Windows program · freeWiring Diagram Maker web · no installSystem Diagram Editor web · no install

Removing a device looks easier than adding one, but the remaining devices can slow down or drop out afterwards. The removed device may have been the end of the bus, provided the bias, carried the shield and SG through its terminals, or the master may still be asking for it.

Safety: work on power terminals or the main circuit (AC 230/400 V) is done by a qualified person following site rules (permit, lock-out, tag-out) — isolate, then verify absence of voltage with a tester. A drive keeps voltage on its internal capacitors after isolation, so wait the discharge time given in its manual (usually several minutes).

1. Before removing: what the device was doing

2. Drop it from the master's polling

Remove the device but leave the master settings as they are, and the master keeps asking for that ID every cycle and waiting. With no reply, each cycle grows by «timeout × (1 + retries)». With a 1000 ms timeout and 1 retry, for instance, about 2 s is added per cycle, every other device updates that much later, and the PLC or HMI keeps a communication alarm up. Before removing the device (or right after), delete or disable it in the polling lists and tags of the PLC, HMI and SCADA, and tidy the program logic that used its values.

3. Move the terminator

If the removed device was at the end of the bus, turn on the terminator at the device that is now the end. Otherwise the bus has only one terminator (A–B about 120 Ω). Removing an end device but leaving its cable can also turn that cable into a long unterminated stub — cut the leftover cable back so the bus ends at the new end device. If the device provided bias, check that the bus is still biased in one other place (usually at the master).

4. Leftover cable and stubs

5. Ground and shield

If the shield was grounded through the device housing or panel ground, removing the device can take away the shield's ground point. Check that the shield is still grounded where planned (one end or both) and that it is not broken at any new joint.

6. Record the IP and ID, update documents

7. Checks afterwards

In PortDock

Sources