Siemens SENTRON PAC3200 Modbus register map

PAC RS485 expansion module, Modbus RTU. Offset = frame address. Measured values are floats (2 registers, high word first): voltage 1-11, current 13-17, active power 25-29, frequency 55, total active power 65. Energy is double (4 registers) 801-837 · Power meter · PAC RS485

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)19200 bps — options: 4800, 9600, 19200, 38400
Data · parity · stop8 · None · 2
Slave ID (factory)126 (1~247)
32-bit orderABCD
Max per request125 registers
Manual address styleWire address as is (0-based)

Registers (67)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

67

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
11 (0x0001)HRVoltage Va-nF32 ABCDVR03·04
p.34
33 (0x0003)HRVoltage Vb-nF32 ABCDVR03·04
p.34
55 (0x0005)HRVoltage Vc-nF32 ABCDVR03·04
p.34
77 (0x0007)HRVoltage Va-bF32 ABCDVR03·04
p.34
99 (0x0009)HRVoltage Vb-cF32 ABCDVR03·04
p.34
1111 (0x000B)HRVoltage Vc-aF32 ABCDVR03·04
p.34
1313 (0x000D)HRCurrent aF32 ABCDAR03·04
p.34
1515 (0x000F)HRCurrent bF32 ABCDAR03·04
p.34
1717 (0x0011)HRCurrent cF32 ABCDAR03·04
p.34
1919 (0x0013)HRApparent power aF32 ABCDVAR03·04
p.34
2121 (0x0015)HRApparent power bF32 ABCDVAR03·04
p.34
2323 (0x0017)HRApparent power cF32 ABCDVAR03·04
p.34
2525 (0x0019)HRActive power aF32 ABCDWR03·04
p.34
2727 (0x001B)HRActive power bF32 ABCDWR03·04
p.34
2929 (0x001D)HRActive power cF32 ABCDWR03·04
p.34
3131 (0x001F)HRReactive power aF32 ABCDvarR03·04
p.34
3333 (0x0021)HRReactive power bF32 ABCDvarR03·04
p.34
3535 (0x0023)HRReactive power cF32 ABCDvarR03·04
p.34
3737 (0x0025)HRPower factor aF32 ABCDR03·04
p.34
3939 (0x0027)HRPower factor bF32 ABCDR03·04
p.34
4141 (0x0029)HRPower factor cF32 ABCDR03·04
p.34
4343 (0x002B)HRTHD-R voltage aF32 ABCD%R03·04
p.34
4545 (0x002D)HRTHD-R voltage bF32 ABCD%R03·04
p.34
4747 (0x002F)HRTHD-R voltage cF32 ABCD%R03·04
p.34
4949 (0x0031)HRTHD-R current aF32 ABCD%R03·04
p.34
5151 (0x0033)HRTHD-R current bF32 ABCD%R03·04
p.34
5353 (0x0035)HRTHD-R current cF32 ABCD%R03·04
p.34
5555 (0x0037)HRFrequencyF32 ABCDHzR03·04
p.34
5757 (0x0039)HRAverage voltage Vph-nF32 ABCDVR03·04
p.34
5959 (0x003B)HRAverage voltage Vph-phF32 ABCDVR03·04
p.35
6161 (0x003D)HRAverage currentF32 ABCDAR03·04
p.35
6363 (0x003F)HRTotal apparent powerF32 ABCDVAR03·04
p.35
6565 (0x0041)HRTotal active powerF32 ABCDWR03·04
p.35
6767 (0x0043)HRTotal reactive powerF32 ABCDvarR03·04
p.35
6969 (0x0045)HRTotal power factorF32 ABCDR03·04
p.35
7171 (0x0047)HRAmplitude unbalance voltageF32 ABCD%R03·04
p.35
7373 (0x0049)HRAmplitude unbalance currentF32 ABCD%R03·04
p.35
207207 (0x00CF)HRStatus of the digital outputsU32 ABCDR03·04
p.36
209209 (0x00D1)HRStatus of the digital inputsU32 ABCDR03·04
p.36
211211 (0x00D3)HRActive tariffU32 ABCDR03·04
0 = Tariff 1 · 1 = Tariff 2
p.36
213213 (0x00D5)HRWorking hours counterU32 ABCDsR/W03·04·10
p.36
215215 (0x00D7)HRUniversal counterU32 ABCDR/W03·04·10
p.36
501501 (0x01F5)HRDemand active power, importF32 ABCDWR03·04
p.37
503503 (0x01F7)HRDemand reactive power, importF32 ABCDvarR03·04
p.37
801801 (0x0321)HRActive energy import T1F64 ABCDWhR/W03·04·10
p.37
805805 (0x0325)HRActive energy import T2F64 ABCDWhR/W03·04·10
p.37
809809 (0x0329)HRActive energy export T1F64 ABCDWhR/W03·04·10
p.37
813813 (0x032D)HRActive energy export T2F64 ABCDWhR/W03·04·10
p.37
817817 (0x0331)HRReactive energy import T1F64 ABCDvarhR/W03·04·10
p.37
821821 (0x0335)HRReactive energy import T2F64 ABCDvarhR/W03·04·10
p.37
825825 (0x0339)HRReactive energy export T1F64 ABCDvarhR/W03·04·10
p.37
829829 (0x033D)HRReactive energy export T2F64 ABCDvarhR/W03·04·10
p.37
833833 (0x0341)HRApparent energy T1F64 ABCDVAhR/W03·04·10
p.37
837837 (0x0345)HRApparent energy T2F64 ABCDVAhR/W03·04·10
p.37
5000150001 (0xC351)HRConnection typeU32 ABCDR/W03·04·10
0 = 3P4W · 1 = 3P3W · 2 = 3P4WB · 3 = 3P3WB
p.40
5000550005 (0xC355)HRPrimary voltageU32 ABCDVR/W03·04·10
Range 1 ~ 999999 V
p.40
5000750007 (0xC357)HRSecondary voltageU32 ABCDVR/W03·04·10
Range 1 ~ 690 V
p.40
5001150011 (0xC35B)HRPrimary currentU32 ABCDAR/W03·04·10
Range 1 ~ 99999 A
p.40
5001350013 (0xC35D)HRSecondary currentU32 ABCDAR/W03·04·10
Range 1 ~ 5 A
p.40
5002150021 (0xC365)HRDemand periodU32 ABCDminR/W03·04·10
Range 1 ~ 60 min
p.41
6000260002 (0xEA62)HRReset maximum valuesU16W06·10
p.51
6000360003 (0xEA63)HRReset minimum valuesU16W06·10
p.51
6000460004 (0xEA64)HRReset energy counterU16W06·10
p.51
6000660006 (0xEA66)HRSwitching tariffU16W06·10
p.51, p.76
6301963019 (0xF62B)HRModbus addressU32 ABCDR/W03·04·10
Range 1 ~ 247
p.53
6302163021 (0xF62D)HRBaud rateU32 ABCDR/W03·04·10
0 = 4800 bps · 1 = 9600 bps · 2 = 19200 bps · 3 = 38400 bps
p.53
6302363023 (0xF62F)HRData, parity and stop bitsU32 ABCDR/W03·04·10
0 = 8N2 · 1 = 8E1 · 2 = 8O1 · 3 = 8N1
p.53

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).