An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 9600 bps — options: 2400, 4800, 9600, 19200, 38400 |
| Data · parity · stop | — · None · 1 |
| Slave ID (factory) | 1 (1~247) |
| Manual address style | 40001/30001 style (wire address + 1, first digit = table) |
- The manual lists 30001/40001-style numbers with a 'Modbus Protocol Start Address Hex' column and gives 'Amps 1 start address 0006' (30007) as an example (PDF p.14). Wire address = number − 30001 / − 40001; 6-digit numbers (461457 …) use − 400001.
- Defaults 9600 bps, no parity, 1 stop bit, address 1 (PDF p.3, pp.17-18). Requests are limited to 30 parameters (PDF p.14).
- Word order: the manual only says Hi/Lo order is set automatically to normal or reverse and cannot be configured from the menu (PDF p.3). PortDock reads ABCD when no order is given; try CDAB if values look wrong.
Registers (42)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 30001 | 0 (0x0000) | IR | Phase 1 line to neutral volts | F32 | V | R | 04 | PDF p.15 |
| 30003 | 2 (0x0002) | IR | Phase 2 line to neutral volts | F32 | V | R | 04 | PDF p.15 |
| 30005 | 4 (0x0004) | IR | Phase 3 line to neutral volts | F32 | V | R | 04 | PDF p.15 |
| 30007 | 6 (0x0006) | IR | Phase 1 current | F32 | A | R | 04 | PDF p.15 |
| 30009 | 8 (0x0008) | IR | Phase 2 current | F32 | A | R | 04 | PDF p.15 |
| 30011 | 10 (0x000A) | IR | Phase 3 current | F32 | A | R | 04 | PDF p.15 |
| 30013 | 12 (0x000C) | IR | Phase 1 active power | F32 | W | R | 04 | PDF p.15 |
| 30015 | 14 (0x000E) | IR | Phase 2 active power | F32 | W | R | 04 | PDF p.15 |
| 30017 | 16 (0x0010) | IR | Phase 3 active power | F32 | W | R | 04 | PDF p.15 |
| 30031 | 30 (0x001E) | IR | Phase 1 power factor | F32 | R | 04 | Sign shows current direction: positive forward, negative reverse PDF p.15 | |
| 30033 | 32 (0x0020) | IR | Phase 2 power factor | F32 | R | 04 | Sign shows current direction: positive forward, negative reverse PDF p.15 | |
| 30035 | 34 (0x0022) | IR | Phase 3 power factor | F32 | R | 04 | Sign shows current direction: positive forward, negative reverse PDF p.15 | |
| 30043 | 42 (0x002A) | IR | Average line to neutral volts | F32 | V | R | 04 | PDF p.15 |
| 30049 | 48 (0x0030) | IR | Sum of line currents | F32 | A | R | 04 | PDF p.15 |
| 30053 | 52 (0x0034) | IR | Total system power | F32 | W | R | 04 | PDF p.15 |
| 30057 | 56 (0x0038) | IR | Total system volt amps | F32 | VA | R | 04 | PDF p.15 |
| 30061 | 60 (0x003C) | IR | Total system VAr | F32 | VAr | R | 04 | PDF p.15 |
| 30063 | 62 (0x003E) | IR | Total system power factor | F32 | R | 04 | Sign shows current direction: positive forward, negative reverse PDF p.15 | |
| 30071 | 70 (0x0046) | IR | Frequency of supply voltages | F32 | Hz | R | 04 | PDF p.15 |
| 30073 | 72 (0x0048) | IR | Import active energy | F32 | kWh | R | 04 | PDF p.15 |
| 30075 | 74 (0x004A) | IR | Export active energy | F32 | kWh | R | 04 | PDF p.15 |
| 30201 | 200 (0x00C8) | IR | Line 1 to line 2 volts | F32 | V | R | 04 | PDF p.15 |
| 30203 | 202 (0x00CA) | IR | Line 2 to line 3 volts | F32 | V | R | 04 | PDF p.15 |
| 30205 | 204 (0x00CC) | IR | Line 3 to line 1 volts | F32 | V | R | 04 | PDF p.15 |
| 30225 | 224 (0x00E0) | IR | Neutral current | F32 | A | R | 04 | PDF p.15 |
| 30343 | 342 (0x0156) | IR | Total kWh | F32 | kWh | R | 04 | Import + export PDF p.16 |
| 30345 | 344 (0x0158) | IR | Total kvarh | F32 | kVArh | R | 04 | Import + export PDF p.16 |
| 30385 | 384 (0x0180) | IR | Resettable total active energy | F32 | kWh | R | 04 | PDF p.16 |
| 30397 | 396 (0x018C) | IR | Net kWh (import − export) | F32 | kWh | R | 04 | PDF p.16 |
| 34877 | 4876 (0x130C) | IR | T1 total active energy | F32 | kWh | R | 04 | PDF p.16 |
| 34879 | 4878 (0x130E) | IR | T2 total active energy | F32 | kWh | R | 04 | PDF p.16 |
| 40001 | 0 (0x0000) | HR | Demand time | F32 | min | R | 03 | PDF p.17 |
| 40003 | 2 (0x0002) | HR | Demand period | F32 | min | R/W | 03·10 | Default 15 Range 0 ~ 60 min PDF p.17 |
| 40013 | 12 (0x000C) | HR | Pulse 1 width | F32 | ms | R/W | 03·10 | This table gives default 200, the specification (PDF p.3) gives 100 60 = 60 ms · 100 = 100 ms · 200 = 200 ms PDF p.17 |
| 40019 | 18 (0x0012) | HR | Parity / stop | F32 | R/W | 03·10 | 0 = 1 stop bit, no parity (default) · 1 = 1 stop bit, even parity · 2 = 1 stop bit, odd parity · 3 = 2 stop bits, no parity PDF p.17-18 | |
| 40021 | 20 (0x0014) | HR | Modbus address | F32 | R/W | 03·10 | Default 1 Range 1 ~ 247 PDF p.18 | |
| 40023 | 22 (0x0016) | HR | Pulse 1 rate | F32 | R/W | 03·10 | 1 = 0.01 kWh/imp (default) · 2 = 0.1 kWh/imp · 3 = 1 kWh/imp · 4 = 10 kWh/imp · 5 = 100 kWh/imp PDF p.18 | |
| 40029 | 28 (0x001C) | HR | Network baud rate | F32 | R/W | 03·10 | 0 = 2400 bps · 1 = 4800 bps · 2 = 9600 bps (default) · 3 = 19200 bps · 4 = 38400 bps PDF p.18 | |
| 40033 | 32 (0x0020) | HR | CT primary | F32 | A | R/W | 03·10 | Default 5; requires access (40015) to write Range 5 ~ 9999 A PDF p.18 |
| 40087 | 86 (0x0056) | HR | Pulse 1 energy type | F32 | R/W | 03·10 | 1 = Import active energy · 2 = Total active energy · 4 = Export active energy (default) · 5 = Import reactive energy · 6 = Total reactive energy · 8 = Export reactive energy PDF p.19 | |
| 461457 | 61456 (0xF010) | HR | Reset historical data | U16 | W | 10 | 2-byte hex (F0 10) 0 = Reset maximum demand · 3 = Reset energy info PDF p.19 | |
| 464515 | 64514 (0xFC02) | HR | Meter code | U16 | R | 03 | SDM72CTM-2T = 0100h PDF p.19 |
Notes
- Left out: Int64 energies (310017-, byte/word order not given), per-phase VA/VAr, maximum demands (35529/35533 list kWh as unit), 40015 access authority (KPPA) and 40025 password, 464513 serial number (unsigned int32).
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- eastron/sdm72ct-m.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- Eastron SDM72CT-M User Manual (SDM72CT-M-2T) — Zhejiang Eastron Electronic Co., Ltd., User Manual V1.0 (2023); file name sdm72ct-m-2tusermanual.pdf (posted 2025-07-15 on eastrongroup.com) · PDF p.3 communication spec, pp.14-16 input registers, pp.16-19 holding registers (printed = PDF page) · checked 2026-10-31