An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 9600 bps — options: 9600, 19200, 38400, 57600, 115200 |
| Data · parity · stop | 8 · None · 1 |
| Slave ID (factory) | 1 (1~247) |
| 32-bit order | CDAB |
| Max per request | 50 registers |
| Manual address style | 40001/30001 style (wire address + 1, first digit = table) |
- The manual gives both the 'Modicom address' (300001 style) and the 'Physical address' (word address placed in the frame, 0000h style) (p.3). address is the physical address, which here is always Modicom − 300001.
- FC 03 and 04 give the same result (p.3); measurements are listed as input registers (FC 04). Settings are written with FC 06, one word at a time. Up to 50 words per request (p.3, p.17). Defaults: address 1, 9600 bps, no parity, 1 stop bit (p.17). With even parity the stop bits are fixed to 1.
- INT32: words LSW→MSW, bytes MSB→LSB (p.7) → CDAB. (Only an EM340 engineering sample is listed with MSW-LSW word order, p.14.)
Registers (35)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 300001 (0000h) | 0 (0x0000) | IR | V L1-N | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 2.4-1 |
| 300003 (0002h) | 2 (0x0002) | IR | V L2-N | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 2.4-1 |
| 300005 (0004h) | 4 (0x0004) | IR | V L3-N | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 2.4-1 |
| 300007 (0006h) | 6 (0x0006) | IR | V L1-L2 | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 2.4-1 |
| 300009 (0008h) | 8 (0x0008) | IR | V L2-L3 | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 2.4-1 |
| 300011 (000Ah) | 10 (0x000A) | IR | V L3-L1 | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 2.4-1 |
| 300013 (000Ch) | 12 (0x000C) | IR | A L1 | S32 CDAB | ×0.001 A | R | 04 | p.9 Table 2.4-1 |
| 300015 (000Eh) | 14 (0x000E) | IR | A L2 | S32 CDAB | ×0.001 A | R | 04 | p.9 Table 2.4-1 |
| 300017 (0010h) | 16 (0x0010) | IR | A L3 | S32 CDAB | ×0.001 A | R | 04 | p.9 Table 2.4-1 |
| 300019 (0012h) | 18 (0x0012) | IR | W L1 | S32 CDAB | ×0.1 W | R | 04 | p.9 Table 2.4-1 |
| 300021 (0014h) | 20 (0x0014) | IR | W L2 | S32 CDAB | ×0.1 W | R | 04 | p.9 Table 2.4-1 |
| 300023 (0016h) | 22 (0x0016) | IR | W L3 | S32 CDAB | ×0.1 W | R | 04 | p.9 Table 2.4-1 |
| 300037 (0024h) | 36 (0x0024) | IR | V L-N sys | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 2.4-1 |
| 300039 (0026h) | 38 (0x0026) | IR | V L-L sys | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 2.4-1 |
| 300041 (0028h) | 40 (0x0028) | IR | W sys | S32 CDAB | ×0.1 W | R | 04 | p.9 Table 2.4-1 |
| 300043 (002Ah) | 42 (0x002A) | IR | VA sys | S32 CDAB | ×0.1 VA | R | 04 | p.9 Table 2.4-1 |
| 300045 (002Ch) | 44 (0x002C) | IR | var sys | S32 CDAB | ×0.1 var | R | 04 | p.9 Table 2.4-1 |
| 300047 (002Eh) | 46 (0x002E) | IR | PF L1 | S16 | ×0.001 | R | 04 | p.9 Table 2.4-1 |
| 300048 (002Fh) | 47 (0x002F) | IR | PF L2 | S16 | ×0.001 | R | 04 | p.9 Table 2.4-1 |
| 300049 (0030h) | 48 (0x0030) | IR | PF L3 | S16 | ×0.001 | R | 04 | p.9 Table 2.4-1 |
| 300050 (0031h) | 49 (0x0031) | IR | PF sys | S16 | ×0.001 | R | 04 | Negative = exported active power, positive = imported p.9 Table 2.4-1 |
| 300051 (0032h) | 50 (0x0032) | IR | Phase sequence | S16 | R | 04 | Meaningful only in a 3-phase system 0 = L1-L2-L3 · 1 = L1-L3-L2 p.9 Table 2.4-1 | |
| 300052 (0033h) | 51 (0x0033) | IR | Hz | S16 | ×0.1 Hz | R | 04 | p.9 Table 2.4-1 |
| 300053 (0034h) | 52 (0x0034) | IR | kWh (+) TOT | S32 CDAB | ×0.1 kWh | R | 04 | p.9 Table 2.4-1 |
| 300055 (0036h) | 54 (0x0036) | IR | kvarh (+) TOT | S32 CDAB | ×0.1 kvarh | R | 04 | p.9 Table 2.4-1 |
| 300057 (0038h) | 56 (0x0038) | IR | kW dmd | S32 CDAB | ×0.1 W | R | 04 | p.9 Table 2.4-1 |
| 300059 (003Ah) | 58 (0x003A) | IR | kW dmd peak | S32 CDAB | ×0.1 W | R | 04 | p.9 Table 2.4-1 |
| 300061 (003Ch) | 60 (0x003C) | IR | kWh (+) PARTIAL | S32 CDAB | ×0.1 kWh | R | 04 | p.9 Table 2.4-1 |
| 300079 (004Eh) | 78 (0x004E) | IR | kWh (-) TOT | S32 CDAB | ×0.1 kWh | R | 04 | p.9 Table 2.4-1 |
| 300081 (0050h) | 80 (0x0050) | IR | kvarh (-) TOT | S32 CDAB | ×0.1 kvarh | R | 04 | p.9 Table 2.4-1 |
| 304099 (1002h) | 4098 (0x1002) | HR | Measuring system | U16 | R/W | 03·06 | 0 = 3Pn (3-phase with neutral) · 1 = 3P (3-phase without neutral) · 2 = 2P (2-phase with neutral) p.15 Table 2.9-2 | |
| 308193 (2000h) | 8192 (0x2000) | HR | RS485 instrument address | U16 | R/W | 03·06 | Default 1 Range 1 ~ 247 p.17 Table 2.9-7 | |
| 308194 (2001h) | 8193 (0x2001) | HR | RS485 baud rate | U16 | R/W | 03·06 | 1 = 9.6 kbps (default) · 2 = 19.2 kbps · 3 = 38.4 kbps · 4 = 57.6 kbps · 5 = 115.2 kbps p.17 Table 2.9-7 | |
| 308195 (2002h) | 8194 (0x2002) | HR | RS485 parity | U16 | R/W | 03·06 | 1 = No parity (default) · 2 = Even parity p.17 Table 2.9-7 | |
| 316385 (4000h) | 16384 (0x4000) | HR | Reset partial and tariff meters and demand | U16 | W | 06 | 1 = Execute p.17 Table 2.9-8 |
Notes
- Some values (kWh (−) per phase, run hours etc.) exist only on the ET series or EM330; unavailable values read 0 (p.9).
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- carlo-gavazzi/em300.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- EM300 Series and ET300 Series Communication Protocol — Carlo Gavazzi, Version 2 Revision 17 (2021-07-05) · 1.2 Modbus functions pp.3-5, 2.1 data format p.7, Table 2.4-1 p.9, 2.9 parameter tables pp.15-17 · checked 2026-11-01