An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus TCP |
|---|---|
| Slave ID (factory) | 1 (1~247) |
| TCP port | 502 |
| Manual address style | 40001/30001 style (wire address + 1, first digit = table) |
- The manual lists 030001/40001-style numbers with a 'Start Address Hex' column (030001 ↔ 00 00, 030007 ↔ 00 06) (PDF pp.24-28). Wire address = number − 30001 / − 40001.
- Defaults: IP 192.168.1.200, mask 255.255.255.0, gateway 192.168.1.1, DHCP off, port 502 (PDF pp.9-10, 21-22). Node address (40021) default 1 (PDF p.28). Float word order is not given in this manual (PortDock reads ABCD when no order is given).
Registers (33)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 030001 | 0 (0x0000) | IR | Phase 1 line to neutral volts | F32 | V | R | 04 | PDF p.24 |
| 030003 | 2 (0x0002) | IR | Phase 2 line to neutral volts | F32 | V | R | 04 | PDF p.24 |
| 030005 | 4 (0x0004) | IR | Phase 3 line to neutral volts | F32 | V | R | 04 | PDF p.24 |
| 030007 | 6 (0x0006) | IR | Phase 1 current | F32 | A | R | 04 | PDF p.24 |
| 030009 | 8 (0x0008) | IR | Phase 2 current | F32 | A | R | 04 | PDF p.24 |
| 030011 | 10 (0x000A) | IR | Phase 3 current | F32 | A | R | 04 | PDF p.24 |
| 030013 | 12 (0x000C) | IR | Phase 1 power | F32 | W | R | 04 | PDF p.24 |
| 030015 | 14 (0x000E) | IR | Phase 2 power | F32 | W | R | 04 | PDF p.24 |
| 030017 | 16 (0x0010) | IR | Phase 3 power | F32 | W | R | 04 | PDF p.24 |
| 030031 | 30 (0x001E) | IR | Phase 1 power factor | F32 | R | 04 | PDF p.24 | |
| 030033 | 32 (0x0020) | IR | Phase 2 power factor | F32 | R | 04 | PDF p.24 | |
| 030035 | 34 (0x0022) | IR | Phase 3 power factor | F32 | R | 04 | PDF p.24 | |
| 030043 | 42 (0x002A) | IR | Average line to neutral volts | F32 | V | R | 04 | PDF p.24 |
| 030049 | 48 (0x0030) | IR | Sum of line currents | F32 | A | R | 04 | PDF p.24 |
| 030053 | 52 (0x0034) | IR | Total system power | F32 | W | R | 04 | PDF p.24 |
| 030057 | 56 (0x0038) | IR | Total system volt amps | F32 | VA | R | 04 | PDF p.24 |
| 030061 | 60 (0x003C) | IR | Total system VAr | F32 | VAr | R | 04 | PDF p.24 |
| 030063 | 62 (0x003E) | IR | Total system power factor | F32 | R | 04 | PDF p.25 | |
| 030071 | 70 (0x0046) | IR | Frequency of supply voltages | F32 | Hz | R | 04 | PDF p.25 |
| 030073 | 72 (0x0048) | IR | Import Wh since last reset | F32 | kWh | R | 04 | PDF p.25 |
| 030075 | 74 (0x004A) | IR | Export Wh since last reset | F32 | kWh | R | 04 | PDF p.25 |
| 030077 | 76 (0x004C) | IR | Import VArh since last reset | F32 | kVArh | R | 04 | PDF p.25 |
| 030079 | 78 (0x004E) | IR | Export VArh since last reset | F32 | kVArh | R | 04 | PDF p.25 |
| 030085 | 84 (0x0054) | IR | Total system power demand | F32 | W | R | 04 | PDF p.25 |
| 030087 | 86 (0x0056) | IR | Maximum total system power demand | F32 | W | R | 04 | PDF p.25 |
| 030201 | 200 (0x00C8) | IR | Line 1 to line 2 volts | F32 | V | R | 04 | PDF p.25 |
| 030203 | 202 (0x00CA) | IR | Line 2 to line 3 volts | F32 | V | R | 04 | PDF p.25 |
| 030205 | 204 (0x00CC) | IR | Line 3 to line 1 volts | F32 | V | R | 04 | PDF p.25 |
| 030343 | 342 (0x0156) | IR | Total kWh | F32 | kWh | R | 04 | PDF p.25 |
| 030345 | 344 (0x0158) | IR | Total kvarh | F32 | kVArh | R | 04 | PDF p.25 |
| 40003 | 2 (0x0002) | HR | Demand period | F32 | min | R/W | 03·10 | 0 = 0 (shows present value) · 5 = 5 · 8 = 8 · 10 = 10 · 15 = 15 · 20 = 20 · 30 = 30 · 60 = 60 (default) PDF p.27 |
| 40011 | 10 (0x000A) | HR | System type | F32 | R/W | 03·10 | 1 = 1P2W · 2 = 3P3W · 3 = 3P4W PDF p.27 | |
| 40021 | 20 (0x0014) | HR | Network node | F32 | R/W | 03·10 | Default 1; effective after restart Range 1 ~ 247 PDF p.28 |
Notes
- The high byte of 'Start Address Hex' is printed separately at the line end (PDF pp.24-26); only entries whose number and low byte agree are included. 30255 (named total PF but unit Degrees), phase angles, per-phase energies and CO2 are left out.
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
Download JSON
- eastron/sdm630-tcp.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- Eastron SDM630-TCP User Manual V2.01 — Zhejiang Eastron Electronic Co., Ltd., V2.01 (2025); file name eastronsdm630-tcpusermanualv2.01.pdf (posted 2025-04-27 on eastrongroup.com) · PDF pp.9-10 communication spec, pp.21-22 TCP setup, pp.24-27 input registers, pp.27-28 holding registers (printed page = PDF page − 7) · checked 2026-10-31