Eastron SDM630-TCP Modbus register map

Ethernet Modbus TCP (port 502). Measurements are Float input registers (FC04, two registers each); settings are holding registers (FC03 read, FC10 write). · Power meter

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus TCP
Slave ID (factory)1 (1~247)
TCP port502
Manual address style40001/30001 style (wire address + 1, first digit = table)

Registers (33)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

33

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
0300010 (0x0000)IRPhase 1 line to neutral voltsF32VR04
PDF p.24
0300032 (0x0002)IRPhase 2 line to neutral voltsF32VR04
PDF p.24
0300054 (0x0004)IRPhase 3 line to neutral voltsF32VR04
PDF p.24
0300076 (0x0006)IRPhase 1 currentF32AR04
PDF p.24
0300098 (0x0008)IRPhase 2 currentF32AR04
PDF p.24
03001110 (0x000A)IRPhase 3 currentF32AR04
PDF p.24
03001312 (0x000C)IRPhase 1 powerF32WR04
PDF p.24
03001514 (0x000E)IRPhase 2 powerF32WR04
PDF p.24
03001716 (0x0010)IRPhase 3 powerF32WR04
PDF p.24
03003130 (0x001E)IRPhase 1 power factorF32R04
PDF p.24
03003332 (0x0020)IRPhase 2 power factorF32R04
PDF p.24
03003534 (0x0022)IRPhase 3 power factorF32R04
PDF p.24
03004342 (0x002A)IRAverage line to neutral voltsF32VR04
PDF p.24
03004948 (0x0030)IRSum of line currentsF32AR04
PDF p.24
03005352 (0x0034)IRTotal system powerF32WR04
PDF p.24
03005756 (0x0038)IRTotal system volt ampsF32VAR04
PDF p.24
03006160 (0x003C)IRTotal system VArF32VArR04
PDF p.24
03006362 (0x003E)IRTotal system power factorF32R04
PDF p.25
03007170 (0x0046)IRFrequency of supply voltagesF32HzR04
PDF p.25
03007372 (0x0048)IRImport Wh since last resetF32kWhR04
PDF p.25
03007574 (0x004A)IRExport Wh since last resetF32kWhR04
PDF p.25
03007776 (0x004C)IRImport VArh since last resetF32kVArhR04
PDF p.25
03007978 (0x004E)IRExport VArh since last resetF32kVArhR04
PDF p.25
03008584 (0x0054)IRTotal system power demandF32WR04
PDF p.25
03008786 (0x0056)IRMaximum total system power demandF32WR04
PDF p.25
030201200 (0x00C8)IRLine 1 to line 2 voltsF32VR04
PDF p.25
030203202 (0x00CA)IRLine 2 to line 3 voltsF32VR04
PDF p.25
030205204 (0x00CC)IRLine 3 to line 1 voltsF32VR04
PDF p.25
030343342 (0x0156)IRTotal kWhF32kWhR04
PDF p.25
030345344 (0x0158)IRTotal kvarhF32kVArhR04
PDF p.25
400032 (0x0002)HRDemand periodF32minR/W03·10
0 = 0 (shows present value) · 5 = 5 · 8 = 8 · 10 = 10 · 15 = 15 · 20 = 20 · 30 = 30 · 60 = 60 (default)
PDF p.27
4001110 (0x000A)HRSystem typeF32R/W03·10
1 = 1P2W · 2 = 3P3W · 3 = 3P4W
PDF p.27
4002120 (0x0014)HRNetwork nodeF32R/W03·10
Default 1; effective after restart
Range 1 ~ 247
PDF p.28

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

Download JSON

Sources