Janitza UMG 96RM-E Modbus register map

RS485 Modbus RTU on the residual current monitoring (RCM) model. Table number = frame address. Measured values are floats (2 registers, high first): voltage 19000-19010, current 19012-19018, real power 19020-19026, frequency 19050, energy 19060-19108 · Power meter

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)115200 bps — options: 9600, 19200, 38400, 57600, 115200
Data · parity · stop8 · None · 2
Slave ID (factory)1 (1~247)
32-bit orderABCD
Manual address styleWire address as is (0-based)

Registers (42)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

42

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
00 (0x0000)HRDevice addressS16R/W03·06·10
Range 0 ~ 255
p.112
11 (0x0001)HRBaud rate for ModbusS16R/W03·06·10
0 = 9.6 kbps · 1 = 19.2 kbps · 2 = 38.4 kbps · 3 = 57.6 kbps · 4 = 115.2 kbps
p.112
1900019000 (0x4A38)HRVoltage L1-NF32 ABCDVR03·04
p.116
1900219002 (0x4A3A)HRVoltage L2-NF32 ABCDVR03·04
p.116
1900419004 (0x4A3C)HRVoltage L3-NF32 ABCDVR03·04
p.116
1900619006 (0x4A3E)HRVoltage L1-L2F32 ABCDVR03·04
p.116
1900819008 (0x4A40)HRVoltage L2-L3F32 ABCDVR03·04
p.116
1901019010 (0x4A42)HRVoltage L3-L1F32 ABCDVR03·04
p.116
1901219012 (0x4A44)HRCurrent L1F32 ABCDAR03·04
p.116
1901419014 (0x4A46)HRCurrent L2F32 ABCDAR03·04
p.116
1901619016 (0x4A48)HRCurrent L3F32 ABCDAR03·04
p.116
1901819018 (0x4A4A)HRCurrent vector sumF32 ABCDAR03·04
p.116
1902019020 (0x4A4C)HRReal power L1F32 ABCDWR03·04
p.116
1902219022 (0x4A4E)HRReal power L2F32 ABCDWR03·04
p.116
1902419024 (0x4A50)HRReal power L3F32 ABCDWR03·04
p.116
1902619026 (0x4A52)HRReal power sumF32 ABCDWR03·04
p.116
1902819028 (0x4A54)HRApparent power L1F32 ABCDVAR03·04
p.116
1903019030 (0x4A56)HRApparent power L2F32 ABCDVAR03·04
p.116
1903219032 (0x4A58)HRApparent power L3F32 ABCDVAR03·04
p.117
1903419034 (0x4A5A)HRApparent power sumF32 ABCDVAR03·04
p.117
1903619036 (0x4A5C)HRFundamental reactive power L1F32 ABCDvarR03·04
p.117
1903819038 (0x4A5E)HRFundamental reactive power L2F32 ABCDvarR03·04
p.117
1904019040 (0x4A60)HRFundamental reactive power L3F32 ABCDvarR03·04
p.117
1904219042 (0x4A62)HRFundamental reactive power sumF32 ABCDvarR03·04
p.117
1904419044 (0x4A64)HRFundamental power factor L1F32 ABCDR03·04
p.117
1904619046 (0x4A66)HRFundamental power factor L2F32 ABCDR03·04
p.117
1904819048 (0x4A68)HRFundamental power factor L3F32 ABCDR03·04
p.117
1905019050 (0x4A6A)HRMeasured frequencyF32 ABCDHzR03·04
p.117
1905219052 (0x4A6C)HRRotation field (1 right, 0 none, -1 left)F32 ABCDR03·04
p.117
1906019060 (0x4A74)HRReal energy L1..L3F32 ABCDWhR03·04
p.117
1906819068 (0x4A7C)HRReal energy consumed L1..L3, rate 1F32 ABCDWhR03·04
p.117
1907619076 (0x4A84)HRReal energy delivered L1..L3F32 ABCDWhR03·04
p.117
1908419084 (0x4A8C)HRApparent energy L1..L3F32 ABCDVAhR03·04
p.117
1909219092 (0x4A94)HRReactive energy L1..L3F32 ABCDvarhR03·04
p.117
1910019100 (0x4A9C)HRReactive energy inductive L1..L3F32 ABCDvarhR03·04
p.118
1910819108 (0x4AA4)HRReactive energy capacitive L1..L3F32 ABCDvarhR03·04
p.118
1911019110 (0x4AA6)HRTHD U L1-NF32 ABCD%R03·04
p.118
1911219112 (0x4AA8)HRTHD U L2-NF32 ABCD%R03·04
p.118
1911419114 (0x4AAA)HRTHD U L3-NF32 ABCD%R03·04
p.118
1911619116 (0x4AAC)HRTHD I L1F32 ABCD%R03·04
p.118
1911819118 (0x4AAE)HRTHD I L2F32 ABCD%R03·04
p.118
1912019120 (0x4AB0)HRTHD I L3F32 ABCD%R03·04
p.118

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.