An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 9600 bps — options: 1200, 2400, 4800, 9600, 19200 |
| Data · parity · stop | 8 · None · — |
| Slave ID (factory) | 1 (1~247) |
| Manual address style | 40001/30001 style (wire address + 1, first digit = table) |
- The manual lists 30001/40001-style numbers with a 'Modbus Protocol Start Address Hex' column and gives 'Amps 1 start address 0006' (30007) as an example (PDF p.11). Wire address = number − 30001 / − 40001; 6-digit numbers (461457 …) use − 400001.
- Defaults 9600 bps, no parity, 8 data bits, address 1 (PDF p.3, p.8, pp.11-12). Requests are limited to 30 parameters; more returns an exception (PDF p.11).
- Word order: the manual only says Hi/Lo order is set automatically to normal or reverse and cannot be configured from the menu (PDF p.3). PortDock reads ABCD when no order is given; try CDAB if values look wrong.
Registers (21)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 30013 | 12 (0x000C) | IR | Phase 1 active power | F32 | W | R | 04 | PDF p.11 |
| 30015 | 14 (0x000E) | IR | Phase 2 active power | F32 | W | R | 04 | PDF p.11 |
| 30017 | 16 (0x0010) | IR | Phase 3 active power | F32 | W | R | 04 | PDF p.11 |
| 30053 | 52 (0x0034) | IR | Total system power | F32 | W | R | 04 | PDF p.11 |
| 30073 | 72 (0x0048) | IR | Total import kWh | F32 | kWh | R | 04 | PDF p.11 |
| 30075 | 74 (0x004A) | IR | Total export kWh | F32 | kWh | R | 04 | PDF p.11 |
| 30343 | 342 (0x0156) | IR | Total kWh | F32 | kWh | R | 04 | Import + export PDF p.11 |
| 30385 | 384 (0x0180) | IR | Resettable total active energy | F32 | kWh | R | 04 | Import + export PDF p.11 |
| 30389 | 388 (0x0184) | IR | Resettable import active energy | F32 | kWh | R | 04 | PDF p.11 |
| 30391 | 390 (0x0186) | IR | Resettable export active energy | F32 | kWh | R | 04 | PDF p.11 |
| 31281 | 1280 (0x0500) | IR | Total import active power | F32 | W | R | 04 | PDF p.11 |
| 31283 | 1282 (0x0502) | IR | Total export active power | F32 | W | R | 04 | PDF p.11 |
| 40019 | 18 (0x0012) | HR | Parity / stop bits | F32 | R/W | 03·10 | 0 = 1 stop bit, no parity (default) · 1 = 1 stop bit, even parity · 2 = 1 stop bit, odd parity · 3 = 2 stop bits, no parity PDF p.11-12 | |
| 40021 | 20 (0x0014) | HR | Modbus address | F32 | R/W | 03·10 | Default 1 Range 1 ~ 247 PDF p.12 | |
| 40025 | 24 (0x0018) | HR | Password | F32 | R/W | 03·10 | Read returns the password; write changes it. Default setup password 1000 (PDF p.7) PDF p.12 | |
| 40029 | 28 (0x001C) | HR | Network baud rate | F32 | R/W | 03·10 | 0 = 2400 bps · 1 = 4800 bps · 2 = 9600 bps (default) · 5 = 1200 bps PDF p.12 | |
| 40059 | 58 (0x003A) | HR | Time for scrolling display | F32 | s | R/W | 03·10 | Default 5; 0 turns scrolling off Range 0 ~ 30 s PDF p.12 |
| 40061 | 60 (0x003C) | HR | Time of back light | F32 | min | R/W | 03·10 | Default 60; 0 keeps the backlight on Range 0 ~ 120 min PDF p.12 |
| 461457 | 61456 (0xF010) | HR | Reset | U16 | W | 10 | 2-byte hex (F0 10) 3 = Reset resettable energy PDF p.12 | |
| 464515 | 64514 (0xFC02) | HR | Meter code | U16 | R | 03 | SDM72D-M-1 = 0084h PDF p.12 | |
| 464645 | 64644 (0xFC84) | HR | Software version | U16 | R | 03 | Display XX.YY: first byte XX, second byte YY PDF p.13 |
Notes
- Left out: 464513 serial number (unsigned int32 — word order not stated). 30007 Amps 1 appears only in the example, not in the table, so it is not included. The table's 'Parameter Number' column is not an address.
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- eastron/sdm72d-m-1.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- Eastron SDM72D-M-1 User Manual V1.4 — Zhejiang Eastron Electronic Co., Ltd., User Manual V1.4 (2023); file name eastronsdm72d-m-1usermanualv1.4.pdf (posted 2024-08-21 on eastrongroup.com) · PDF p.3 communication spec, pp.7-8 setup screens, pp.10-11 input registers, pp.11-13 holding registers (no printed page numbers) · checked 2026-10-31