Eastron SDM72D-M-1 Modbus register map

Simple three-phase meter for active power and energy (import, export, resettable partial). Measurements are Float input registers (FC04); settings are holding registers (FC03 read, FC10 write, one parameter per message). · Power meter

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)9600 bps — options: 1200, 2400, 4800, 9600, 19200
Data · parity · stop8 · None · —
Slave ID (factory)1 (1~247)
Manual address style40001/30001 style (wire address + 1, first digit = table)

Registers (21)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

21

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
3001312 (0x000C)IRPhase 1 active powerF32WR04
PDF p.11
3001514 (0x000E)IRPhase 2 active powerF32WR04
PDF p.11
3001716 (0x0010)IRPhase 3 active powerF32WR04
PDF p.11
3005352 (0x0034)IRTotal system powerF32WR04
PDF p.11
3007372 (0x0048)IRTotal import kWhF32kWhR04
PDF p.11
3007574 (0x004A)IRTotal export kWhF32kWhR04
PDF p.11
30343342 (0x0156)IRTotal kWhF32kWhR04
Import + export
PDF p.11
30385384 (0x0180)IRResettable total active energyF32kWhR04
Import + export
PDF p.11
30389388 (0x0184)IRResettable import active energyF32kWhR04
PDF p.11
30391390 (0x0186)IRResettable export active energyF32kWhR04
PDF p.11
312811280 (0x0500)IRTotal import active powerF32WR04
PDF p.11
312831282 (0x0502)IRTotal export active powerF32WR04
PDF p.11
4001918 (0x0012)HRParity / stop bitsF32R/W03·10
0 = 1 stop bit, no parity (default) · 1 = 1 stop bit, even parity · 2 = 1 stop bit, odd parity · 3 = 2 stop bits, no parity
PDF p.11-12
4002120 (0x0014)HRModbus addressF32R/W03·10
Default 1
Range 1 ~ 247
PDF p.12
4002524 (0x0018)HRPasswordF32R/W03·10
Read returns the password; write changes it. Default setup password 1000 (PDF p.7)
PDF p.12
4002928 (0x001C)HRNetwork baud rateF32R/W03·10
0 = 2400 bps · 1 = 4800 bps · 2 = 9600 bps (default) · 5 = 1200 bps
PDF p.12
4005958 (0x003A)HRTime for scrolling displayF32sR/W03·10
Default 5; 0 turns scrolling off
Range 0 ~ 30 s
PDF p.12
4006160 (0x003C)HRTime of back lightF32minR/W03·10
Default 60; 0 keeps the backlight on
Range 0 ~ 120 min
PDF p.12
46145761456 (0xF010)HRResetU16W10
2-byte hex (F0 10)
3 = Reset resettable energy
PDF p.12
46451564514 (0xFC02)HRMeter codeU16R03
SDM72D-M-1 = 0084h
PDF p.12
46464564644 (0xFC84)HRSoftware versionU16R03
Display XX.YY: first byte XX, second byte YY
PDF p.13

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).