Modbus RTU. Measurements are INT32 (low word first) with weights (V×10, A×1000, W×10, kWh×10). FC 03 and 04 give the same result; writes use FC 06, one word at a time. Up to 11 words per request. · Power meter

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Data · parity · stop— · None · 1
32-bit orderCDAB
Max per request11 registers
Manual address style40001/30001 style (wire address + 1, first digit = table)

Registers (41)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

41

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
300001 (0000h)0 (0x0000)IRV L1-NS32 CDAB×0.1 VR04
p.8
300003 (0002h)2 (0x0002)IRV L2-NS32 CDAB×0.1 VR04
p.8
300005 (0004h)4 (0x0004)IRV L3-NS32 CDAB×0.1 VR04
p.8
300007 (0006h)6 (0x0006)IRV L1-L2S32 CDAB×0.1 VR04
p.8
300009 (0008h)8 (0x0008)IRV L2-L3S32 CDAB×0.1 VR04
p.8
300011 (000Ah)10 (0x000A)IRV L3-L1S32 CDAB×0.1 VR04
p.8
300013 (000Ch)12 (0x000C)IRA L1S32 CDAB×0.001 AR04
p.8
300015 (000Eh)14 (0x000E)IRA L2S32 CDAB×0.001 AR04
p.8
300017 (0010h)16 (0x0010)IRA L3S32 CDAB×0.001 AR04
p.8
300019 (0012h)18 (0x0012)IRW L1S32 CDAB×0.1 WR04
p.8
300021 (0014h)20 (0x0014)IRW L2S32 CDAB×0.1 WR04
p.8
300023 (0016h)22 (0x0016)IRW L3S32 CDAB×0.1 WR04
p.8
300041 (0028h)40 (0x0028)IRW (system)S32 CDAB×0.1 WR04
p.8
300043 (002Ah)42 (0x002A)IRVA (system)S32 CDAB×0.1 VAR04
p.8
300045 (002Ch)44 (0x002C)IRvar (system)S32 CDAB×0.1 varR04
p.8
300047 (002Eh)46 (0x002E)IRDMD WS32 CDAB×0.1 WR04
p.8
300051 (0032h)50 (0x0032)IRPF L1S16×0.001R04
Negative = lead (C), positive = lag (L)
p.8
300054 (0035h)53 (0x0035)IRPF (system)S16×0.001R04
Negative = lead (C), positive = lag (L)
p.8
300055 (0036h)54 (0x0036)IRPhase sequenceS16R04
-1 = L1-L3-L2 · 0 = L1-L2-L3
p.8
300056 (0037h)55 (0x0037)IRHzS16×0.1 HzR04
p.8
300057 (0038h)56 (0x0038)IRDMD W maxS32 CDAB×0.1 WR04
p.8
300063 (003Eh)62 (0x003E)IRkWh(+) TOTS32 CDAB×0.1 kWhR04
p.8
300065 (0040h)64 (0x0040)IRkvarh(+) TOTS32 CDAB×0.1 kvarhR04
p.8
300067 (0042h)66 (0x0042)IRkWh(+) PARS32 CDAB×0.1 kWhR04
p.8
300093 (005Ch)92 (0x005C)IRkWh(-) TOTS32 CDAB×0.1 kWhR04
p.8
300095 (005Eh)94 (0x005E)IRkvarh(-) TOTS32 CDAB×0.1 kvarhR04
p.8
300097 (0060h)96 (0x0060)IRHourS32 CDAB×0.01 hR04
p.8
300769 (0300h)768 (0x0300)IRDigital input statusU16R04
b0 Input 1 (0 closed, 1 open) · b1 Input 2 · b2 Input 3
p.8
300770 (0301h)769 (0x0301)IRCurrent tariffU16R04
0 = Tariff 1 · 1 = Tariff 2 · 2 = Tariff 3 · 3 = Tariff 4
p.9
300771 (0302h)770 (0x0302)IRVersion code (model)U16R04
PFA 0-10; PFB adds 128, X adds 64 (model table in the manual)
p.9
304353 (1100h)4352 (0x1100)HRPasswordU16R/W03·06
Range 0 ~ 9999
p.10
304354 (1101h)4353 (0x1101)HRType of applicationU16R/W03·06
0 = 'A' · 1 = 'B' · 2 = 'C' · 3 = 'D' · 4 = 'E' · 5 = 'F' · 6 = 'G' · 7 = 'H'
p.10
304355 (1102h)4354 (0x1102)HRMeasuring systemU16R/W03·06
PFA and PFB support 3Pn only
0 = 3Pn · 1 = 3P1 · 2 = 2P · 3 = 1P · 4 = 3P
p.10
304356 (1103h)4355 (0x1103)HRDMD interval timeU16minR/W03·06
Range 1 ~ 30 min
p.10
304363 (110Ah)4362 (0x110A)HRRS485 instrument addressU16R/W03·06
Range 1 ~ 247
p.11
304364 (110Bh)4363 (0x110B)HRRS485 baud rateU16R/W03·06
0 = 4800 bps · 1 = 9600 bps
p.11
304397 (112Ch)4396 (0x112C)HRCurrent transformer ratioU32 CDAB×0.1R03
Range 1 ~ 60000
p.13
304399 (112Eh)4398 (0x112E)HRVoltage transformer ratioU32 CDAB×0.1R03
Range 1 ~ 6000
p.13
312289 (3000h)12288 (0x3000)HRReset all meters (hour counter excluded)U16W06
1 = Execute
p.13
312291 (3002h)12290 (0x3002)HRReset partial metersU16W06
1 = Execute
p.13
312294 (3005h)12293 (0x3005)HRReset dmd maxU16W06
1 = Execute
p.13

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).