Default communication
| Protocol | Modbus RTU, Modbus TCP |
|---|---|
| Baud (factory) | 38400 bps — options: 9600, 19200, 38400 |
| Data · parity · stop | 8 · None · 1 |
| Slave ID (factory) | 1 (1~247) |
| Max per request | 124 registers |
| Manual address style | 40001/30001 style (wire address + 1, first digit = table) |
- Map gives both REGISTER (30001/40001 style) and ADDRESS (0-based) columns; address here is the ADDRESS column (map p.1, p.6). E.g. 30001 ↔ 0, 40038 ↔ 37, coil 1 ↔ 0 (map p.15 frame examples).
- Defaults: unit 1, 38400 bps (map p.6 41008/41009, user manual p.33 Table 6). Only no parity supported, 1 start + 8 data + 1 stop (map p.12).
- Word order: Swap NO = high word first (ABCD, 100.0 → 42 C8 00 00); Swap YES = word-swapped (CDAB, 00 00 42 C8) (user manual p.42). Factory default conflicts: map p.6 (41009) says 1 (NO), user manual p.33/p.42 says YES (On). So order is left out — read 31008 high byte (1 = off, 2 = on) or check the 'S' setting.
- Ethernet (TCP) has a separate 'TCP SWAP' setting (default On) (user manual p.33, map p.6 41022). TCP port number is not stated.
- Up to 124 registers per read (03h/04h), contiguous only (map p.16).
Registers (37)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 1 | 0 (0x0000) | CO | Wh reset | BIT | W | 05 | Only ON (0xFF00) accepted (F001) map p.1 | |
| 2001 | 2000 (0x07D0) | CO | All data reset | BIT | W | 05 | Only ON (0xFF00) accepted (F001) map p.1 | |
| 30001 | 0 (0x0000) | IR | Average voltage | F32 | V | R | 04 | map p.1 |
| 30003 | 2 (0x0002) | IR | Average current | F32 | A | R | 04 | map p.1 |
| 30005 | 4 (0x0004) | IR | Phase A current | F32 | A | R | 04 | map p.1 |
| 30007 | 6 (0x0006) | IR | Phase B current | F32 | A | R | 04 | map p.1 |
| 30009 | 8 (0x0008) | IR | Phase C current | F32 | A | R | 04 | map p.1 |
| 30011 | 10 (0x000A) | IR | Voltage A-N | F32 | V | R | 04 | map p.1 |
| 30013 | 12 (0x000C) | IR | Voltage B-N | F32 | V | R | 04 | map p.1 |
| 30015 | 14 (0x000E) | IR | Voltage C-N | F32 | V | R | 04 | map p.1 |
| 30017 | 16 (0x0010) | IR | Voltage A-B | F32 | V | R | 04 | map p.1 |
| 30019 | 18 (0x0012) | IR | Voltage B-C | F32 | V | R | 04 | map p.1 |
| 30021 | 20 (0x0014) | IR | Voltage C-A | F32 | V | R | 04 | map p.1 |
| 30023 | 22 (0x0016) | IR | Power factor | F32 | R | 04 | Negative means lead map p.1 | |
| 30025 | 24 (0x0018) | IR | Total active power | F32 | W | R | 04 | map p.1 |
| 30027 | 26 (0x001A) | IR | Total reactive power | F32 | Var | R | 04 | map p.1 |
| 30029 | 28 (0x001C) | IR | Total apparent power | F32 | VA | R | 04 | map p.1 |
| 30031 | 30 (0x001E) | IR | Frequency | F32 | Hz | R | 04 | map p.1 |
| 30033 | 32 (0x0020) | IR | Active energy | F32 | Wh | R | 04 | Manual says to add the Giga counter (30531); its weight is not stated map p.1 |
| 30035 | 34 (0x0022) | IR | Reactive energy | F32 | Varh | R | 04 | Add Giga counter (30532); weight not stated map p.1 |
| 30037 | 36 (0x0024) | IR | Apparent energy | F32 | VAh | R | 04 | Add Giga counter (30533); weight not stated map p.1 |
| 30045 | 44 (0x002C) | IR | Reverse active energy | F32 | Wh | R | 04 | EX model only. Add Giga counter (30534) map p.1 |
| 30049 | 48 (0x0030) | IR | Phase A active power | F32 | W | R | 04 | EX model only map p.1 |
| 30051 | 50 (0x0032) | IR | Phase B active power | F32 | W | R | 04 | EX model only map p.1 |
| 30053 | 52 (0x0034) | IR | Phase C active power | F32 | W | R | 04 | EX model only map p.1 |
| 30079 | 78 (0x004E) | IR | Phase A power factor | F32 | R | 04 | EX model only. Negative = lead map p.2 | |
| 30081 | 80 (0x0050) | IR | Phase B power factor | F32 | R | 04 | EX model only. Negative = lead map p.2 | |
| 30083 | 82 (0x0052) | IR | Phase C power factor | F32 | R | 04 | EX model only. Negative = lead map p.2 | |
| 30111 | 110 (0x006E) | IR | Power demand | F32 | W | R | 04 | EX model only map p.2 |
| 30531 | 530 (0x0212) | IR | Active energy Giga counter | U16 | R | 04 | Range 0-999 map p.5 | |
| 30532 | 531 (0x0213) | IR | Reactive energy Giga counter | U16 | R | 04 | Range 0-999 map p.6 | |
| 30533 | 532 (0x0214) | IR | Apparent energy Giga counter | U16 | R | 04 | Range 0-999 map p.6 | |
| 31001 | 1000 (0x03E8) | IR | Wiring connection | U16 | R | 04 | 1 = 1P2W · 2 = 1P3W · 3 = 3P3W open delta · 4 = 3P3W Y · 5 = 3P4W map p.6, p.7 F219 | |
| 31008 | 1007 (0x03EF) | IR | RS-485 speed / swap | U16 | R | 04 | High byte = swap (1 disabled, 2 enabled); low byte = baud (1 9600, 2 19200, 3 38400). With swap enabled 32-bit words are exchanged map p.6, p.7 F218 | |
| 40001 | 0 (0x0000) | HR | Manufacturer name | STRING(32) | R | 03 | "LSELECTRIC". Swap not applied to 4xxxx map p.6 | |
| 40038 | 37 (0x0025) | HR | Product name | STRING(32) | R | 03 | "GIMAC1000" map p.6 | |
| 40076 | 75 (0x004B) | HR | Software version | STRING(10) | R | 03 | e.g. "01.00.00" map p.6 |
Notes
- Measurements are Float32 (F004) in engineering units after PT/CT ratio; note units are W, var, VA, Wh (not k-).
- Per-phase power/PF, demand etc. are EX model only (map Remark column).
- The map has no function-code column; FC per table (3xxxx = FC04, 4xxxx = FC03, F001 resets = FC05 ON only) follows the frame examples (map p.15-16) and F001 (p.7).
- Settings at 31001-31010 and 41001-41023 are marked R only (map p.6); writing settings over Modbus is not described.
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
Download JSON
- ls-electric/gimac1000.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please credit «PortDock device register maps» with a link. LICENSE
- Found a mistake? Please open a GitHub issue with the manual page.