Eastron SDM120M Modbus register map

Measurements are Float input registers (FC04, two registers each); settings are holding registers (FC03 read, FC10 write). Some settings (F9xx) are single 2-byte registers. · Power meter

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)2400 bps — options: 1200, 2400, 4800, 9600
Data · parity · stop— · None · —
Slave ID (factory)1 (1~247)
Manual address style40001/30001 style (wire address + 1, first digit = table)

Registers (31)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

31

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
300010 (0x0000)IRVoltageF32VR04
PDF p.8
300076 (0x0006)IRCurrentF32AR04
PDF p.9
3001312 (0x000C)IRActive powerF32WR04
PDF p.9
3001918 (0x0012)IRApparent powerF32VAR04
PDF p.9
3002524 (0x0018)IRReactive powerF32VArR04
PDF p.9
3003130 (0x001E)IRPower factorF32R04
PDF p.9
3007170 (0x0046)IRFrequencyF32HzR04
PDF p.9
3007372 (0x0048)IRImport active energyF32kWhR04
PDF p.9
3007574 (0x004A)IRExport active energyF32kWhR04
PDF p.9
3007776 (0x004C)IRImport reactive energyF32kVArhR04
PDF p.9
3007978 (0x004E)IRExport reactive energyF32kVArhR04
PDF p.9
3008584 (0x0054)IRTotal system power demandF32WR04
PDF p.9
3008786 (0x0056)IRMaximum total system power demandF32WR04
PDF p.9
3008988 (0x0058)IRImport system power demandF32WR04
PDF p.9
3009190 (0x005A)IRMaximum import system power demandF32WR04
PDF p.9
3009392 (0x005C)IRExport system power demandF32WR04
PDF p.9
3009594 (0x005E)IRMaximum export system power demandF32WR04
PDF p.9
30259258 (0x0102)IRCurrent demandF32AR04
PDF p.9
30265264 (0x0108)IRMaximum current demandF32AR04
PDF p.9
30343342 (0x0156)IRTotal active energyF32kWhR04
PDF p.9
30345344 (0x0158)IRTotal reactive energyF32kVArhR04
PDF p.9
400032 (0x0002)HRDemand periodF32minR/W03·10
0 = 0 (shows present value) · 5 = 5 · 8 = 8 · 10 = 10 · 15 = 15 · 20 = 20 · 30 = 30 · 60 = 60 (default)
PDF p.9-10
4001312 (0x000C)HRPulse 1 widthF32msR/W03·10
60 = 60 ms (default) · 100 = 100 ms · 200 = 200 ms
PDF p.10
4001918 (0x0012)HRNetwork parity and stop bitsF32R/W03·10
Effective after restart. This cell reads as if 1 were the default, but the setup screen (PDF p.6) and specification (PDF p.3) give no parity as default
0 = 1 stop bit, no parity · 1 = 1 stop bit, even parity · 2 = 1 stop bit, odd parity · 3 = 2 stop bits, no parity
PDF p.10
4002120 (0x0014)HRMeter IDF32R/W03·10
Default 1
Range 1 ~ 247
PDF p.10
4002928 (0x001C)HRBaud rateF32R/W03·10
0 = 2400 bps (default) · 1 = 4800 bps · 2 = 9600 bps · 5 = 1200 bps
PDF p.10
4008786 (0x0056)HRPulse 1 output modeF32R/W03·10
1 = Import active energy · 2 = Total active energy (import + export) · 4 = Export active energy (default) · 5 = Import reactive energy · 6 = Total reactive energy (import + export) · 8 = Export reactive energy
PDF p.10
46145761456 (0xF010)HRReset historical dataU16W10
2-byte hex (F0 10)
0 = Reset demand info
PDF p.10
46376163760 (0xF910)HRPulse 1 output constantU16R/W03·10
2-byte hex (F9 10)
0 = 0.001 kWh/imp (default) · 1 = 0.01 kWh/imp · 2 = 0.1 kWh/imp · 3 = 1 kWh/imp
PDF p.11
46377763776 (0xF920)HRMeasurement modeU16R/W03·10
2-byte hex (F9 20)
1 = Mode 1 (total = import) · 2 = Mode 2 (total = import + export, default) · 3 = Mode 3 (total = import − export)
PDF p.11
46451564514 (0xFC02)HRMeter codeU16R03
SDM120M = 0020h
PDF p.11

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).