An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 9600 bps — options: 9600, 19200, 38400, 57600, 115200 |
| Data · parity · stop | 8 · None · 1 |
| Slave ID (factory) | 1 (1~247) |
| 32-bit order | CDAB |
| Max per request | 125 registers |
| Manual address style | 40001/30001 style (wire address + 1, first digit = table) |
- The manual gives both the 'Modicom address' (300001 style) and the 'Physical address' (word address in the frame, 0000h style) (p.4). address is the physical address (= Modicom − 300001).
- FC 03 and 04 give the same result, up to 125 words per read; writes with 06 and 10 (up to 123 words) (pp.4-6). Defaults: address 1, 9600 bps, no parity, 1 stop bit (p.18).
- INT32: words LSW→MSW (p.8) → CDAB.
Registers (35)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 300001 (0000h) | 0 (0x0000) | IR | V L1-N | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 4.1-1 |
| 300003 (0002h) | 2 (0x0002) | IR | V L2-N | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 4.1-1 |
| 300005 (0004h) | 4 (0x0004) | IR | V L3-N | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 4.1-1 |
| 300007 (0006h) | 6 (0x0006) | IR | V L1-L2 | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 4.1-1 |
| 300009 (0008h) | 8 (0x0008) | IR | V L2-L3 | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 4.1-1 |
| 300011 (000Ah) | 10 (0x000A) | IR | V L3-L1 | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 4.1-1 |
| 300013 (000Ch) | 12 (0x000C) | IR | A L1 | S32 CDAB | ×0.001 A | R | 04 | p.9 Table 4.1-1 |
| 300015 (000Eh) | 14 (0x000E) | IR | A L2 | S32 CDAB | ×0.001 A | R | 04 | p.9 Table 4.1-1 |
| 300017 (0010h) | 16 (0x0010) | IR | A L3 | S32 CDAB | ×0.001 A | R | 04 | p.9 Table 4.1-1 |
| 300019 (0012h) | 18 (0x0012) | IR | W L1 | S32 CDAB | ×0.1 W | R | 04 | p.9 Table 4.1-1 |
| 300021 (0014h) | 20 (0x0014) | IR | W L2 | S32 CDAB | ×0.1 W | R | 04 | p.9 Table 4.1-1 |
| 300023 (0016h) | 22 (0x0016) | IR | W L3 | S32 CDAB | ×0.1 W | R | 04 | p.9 Table 4.1-1 |
| 300037 (0024h) | 36 (0x0024) | IR | V L-N sys | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 4.1-1 |
| 300039 (0026h) | 38 (0x0026) | IR | V L-L sys | S32 CDAB | ×0.1 V | R | 04 | p.9 Table 4.1-1 |
| 300041 (0028h) | 40 (0x0028) | IR | W sys | S32 CDAB | ×0.1 W | R | 04 | p.9 Table 4.1-1 |
| 300043 (002Ah) | 42 (0x002A) | IR | VA sys | S32 CDAB | ×0.1 VA | R | 04 | p.9 Table 4.1-1 |
| 300045 (002Ch) | 44 (0x002C) | IR | var sys | S32 CDAB | ×0.1 var | R | 04 | p.9 Table 4.1-1 |
| 300047 (002Eh) | 46 (0x002E) | IR | PF L1 | S16 | ×0.001 | R | 04 | p.9 Table 4.1-1 |
| 300048 (002Fh) | 47 (0x002F) | IR | PF L2 | S16 | ×0.001 | R | 04 | p.9 Table 4.1-1 |
| 300049 (0030h) | 48 (0x0030) | IR | PF L3 | S16 | ×0.001 | R | 04 | p.9 Table 4.1-1 |
| 300050 (0031h) | 49 (0x0031) | IR | PF sys | S16 | ×0.001 | R | 04 | Negative = exported active power, positive = imported. Lead/lag in 0076h-0079h p.9 Table 4.1-1 |
| 300051 (0032h) | 50 (0x0032) | IR | Phase sequence | S16 | R | 04 | Meaningful only in a 3-phase system -1 = L1-L3-L2 · 0 = L1-L2-L3 p.9 Table 4.1-1 | |
| 300052 (0033h) | 51 (0x0033) | IR | Hz | S16 | ×0.1 Hz | R | 04 | p.9 Table 4.1-1 |
| 300053 (0034h) | 52 (0x0034) | IR | kWh (+) TOT | S32 CDAB | ×0.1 kWh | R | 04 | p.9 Table 4.1-1 |
| 300055 (0036h) | 54 (0x0036) | IR | kvarh (+) TOT | S32 CDAB | ×0.1 kvarh | R | 04 | p.9 Table 4.1-1 |
| 300057 (0038h) | 56 (0x0038) | IR | W sys DMD | S32 CDAB | ×0.1 W | R | 04 | p.9 Table 4.1-1 |
| 300059 (003Ah) | 58 (0x003A) | IR | W sys DMD MAX | S32 CDAB | ×0.1 W | R | 04 | p.9 Table 4.1-1 |
| 300079 (004Eh) | 78 (0x004E) | IR | kWh (-) TOT | S32 CDAB | ×0.1 kWh | R | 04 | p.9 Table 4.1-1 |
| 300081 (0050h) | 80 (0x0050) | IR | kvarh (-) TOT | S32 CDAB | ×0.1 kvarh | R | 04 | p.9 Table 4.1-1 |
| 300087 (0056h) | 86 (0x0056) | IR | kVAh TOT | S32 CDAB | ×0.1 kVAh | R | 04 | p.9 Table 4.1-1 |
| 300091 (005Ah) | 90 (0x005A) | IR | Run hour meter | S32 CDAB | ×0.01 h | R | 04 | p.9 Table 4.1-1 |
| 308193 (2000h) | 8192 (0x2000) | HR | RS485 instrument address | U16 | R/W | 03·06·10 | Default 1 Range 1 ~ 247 p.18 Table 5.4-1 | |
| 308194 (2001h) | 8193 (0x2001) | HR | RS485 baud rate | U16 | R/W | 03·06·10 | 1 = 9.6 kbps (default) · 2 = 19.2 kbps · 3 = 38.4 kbps · 4 = 57.6 kbps · 5 = 115.2 kbps p.18 Table 5.4-1 | |
| 308195 (2002h) | 8194 (0x2002) | HR | RS485 parity | U16 | R/W | 03·06·10 | 1 = No parity (default) · 2 = Even parity p.18 Table 5.4-1 | |
| 308196 (2003h) | 8195 (0x2003) | HR | RS485 stop bit | U16 | R/W | 03·06·10 | Fixed to 1 with even parity 0 = 1 stop bit (default) · 1 = 2 stop bits p.18 Table 5.4-1 |
Notes
- Models without serial RS485 (OX/OXPF) do not have the serial configuration registers (p.18).
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- carlo-gavazzi/wm15.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.