Carlo Gavazzi WM15 Modbus register map

96x96 panel meter. Measurements INT32 (low word first) with weights (V×10, A×1000, W×10, kWh×10). FC 03 and 04 give the same result; settings via 06 and 10. · Power meter

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)9600 bps — options: 9600, 19200, 38400, 57600, 115200
Data · parity · stop8 · None · 1
Slave ID (factory)1 (1~247)
32-bit orderCDAB
Max per request125 registers
Manual address style40001/30001 style (wire address + 1, first digit = table)

Registers (35)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

35

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
300001 (0000h)0 (0x0000)IRV L1-NS32 CDAB×0.1 VR04
p.9 Table 4.1-1
300003 (0002h)2 (0x0002)IRV L2-NS32 CDAB×0.1 VR04
p.9 Table 4.1-1
300005 (0004h)4 (0x0004)IRV L3-NS32 CDAB×0.1 VR04
p.9 Table 4.1-1
300007 (0006h)6 (0x0006)IRV L1-L2S32 CDAB×0.1 VR04
p.9 Table 4.1-1
300009 (0008h)8 (0x0008)IRV L2-L3S32 CDAB×0.1 VR04
p.9 Table 4.1-1
300011 (000Ah)10 (0x000A)IRV L3-L1S32 CDAB×0.1 VR04
p.9 Table 4.1-1
300013 (000Ch)12 (0x000C)IRA L1S32 CDAB×0.001 AR04
p.9 Table 4.1-1
300015 (000Eh)14 (0x000E)IRA L2S32 CDAB×0.001 AR04
p.9 Table 4.1-1
300017 (0010h)16 (0x0010)IRA L3S32 CDAB×0.001 AR04
p.9 Table 4.1-1
300019 (0012h)18 (0x0012)IRW L1S32 CDAB×0.1 WR04
p.9 Table 4.1-1
300021 (0014h)20 (0x0014)IRW L2S32 CDAB×0.1 WR04
p.9 Table 4.1-1
300023 (0016h)22 (0x0016)IRW L3S32 CDAB×0.1 WR04
p.9 Table 4.1-1
300037 (0024h)36 (0x0024)IRV L-N sysS32 CDAB×0.1 VR04
p.9 Table 4.1-1
300039 (0026h)38 (0x0026)IRV L-L sysS32 CDAB×0.1 VR04
p.9 Table 4.1-1
300041 (0028h)40 (0x0028)IRW sysS32 CDAB×0.1 WR04
p.9 Table 4.1-1
300043 (002Ah)42 (0x002A)IRVA sysS32 CDAB×0.1 VAR04
p.9 Table 4.1-1
300045 (002Ch)44 (0x002C)IRvar sysS32 CDAB×0.1 varR04
p.9 Table 4.1-1
300047 (002Eh)46 (0x002E)IRPF L1S16×0.001R04
p.9 Table 4.1-1
300048 (002Fh)47 (0x002F)IRPF L2S16×0.001R04
p.9 Table 4.1-1
300049 (0030h)48 (0x0030)IRPF L3S16×0.001R04
p.9 Table 4.1-1
300050 (0031h)49 (0x0031)IRPF sysS16×0.001R04
Negative = exported active power, positive = imported. Lead/lag in 0076h-0079h
p.9 Table 4.1-1
300051 (0032h)50 (0x0032)IRPhase sequenceS16R04
Meaningful only in a 3-phase system
-1 = L1-L3-L2 · 0 = L1-L2-L3
p.9 Table 4.1-1
300052 (0033h)51 (0x0033)IRHzS16×0.1 HzR04
p.9 Table 4.1-1
300053 (0034h)52 (0x0034)IRkWh (+) TOTS32 CDAB×0.1 kWhR04
p.9 Table 4.1-1
300055 (0036h)54 (0x0036)IRkvarh (+) TOTS32 CDAB×0.1 kvarhR04
p.9 Table 4.1-1
300057 (0038h)56 (0x0038)IRW sys DMDS32 CDAB×0.1 WR04
p.9 Table 4.1-1
300059 (003Ah)58 (0x003A)IRW sys DMD MAXS32 CDAB×0.1 WR04
p.9 Table 4.1-1
300079 (004Eh)78 (0x004E)IRkWh (-) TOTS32 CDAB×0.1 kWhR04
p.9 Table 4.1-1
300081 (0050h)80 (0x0050)IRkvarh (-) TOTS32 CDAB×0.1 kvarhR04
p.9 Table 4.1-1
300087 (0056h)86 (0x0056)IRkVAh TOTS32 CDAB×0.1 kVAhR04
p.9 Table 4.1-1
300091 (005Ah)90 (0x005A)IRRun hour meterS32 CDAB×0.01 hR04
p.9 Table 4.1-1
308193 (2000h)8192 (0x2000)HRRS485 instrument addressU16R/W03·06·10
Default 1
Range 1 ~ 247
p.18 Table 5.4-1
308194 (2001h)8193 (0x2001)HRRS485 baud rateU16R/W03·06·10
1 = 9.6 kbps (default) · 2 = 19.2 kbps · 3 = 38.4 kbps · 4 = 57.6 kbps · 5 = 115.2 kbps
p.18 Table 5.4-1
308195 (2002h)8194 (0x2002)HRRS485 parityU16R/W03·06·10
1 = No parity (default) · 2 = Even parity
p.18 Table 5.4-1
308196 (2003h)8195 (0x2003)HRRS485 stop bitU16R/W03·06·10
Fixed to 1 with even parity
0 = 1 stop bit (default) · 1 = 2 stop bits
p.18 Table 5.4-1

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).