An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU, Modbus ASCII, Modbus TCP |
|---|---|
| 32-bit order | ABCD |
| Max per request | 120 registers |
| Manual address style | 1-based numbers (wire address + 1) |
- Addressing: table addresses are 1-based — saving with 0x2F03 is shown as 01 06 2F 02 00 05, menu selection 0x5000 as 01 06 4F FF and parameter value 0x5004 as 01 06 50 03 (pp.8-9). address = table address − 1. Measurement tables use the same convention and were converted the same way (the document has no numeric frame example for measurements).
- RTU, ASCII and TCP. Bytes and words big-endian (high word first) → ABCD, up to 120 registers, FC 03, 04, 06, 10 and 11 (p.1). Factory communication settings are not in this document (see DMG parameter group P07).
Registers (28)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 0x0002 | 1 (0x0001) | IR | L1 phase voltage | U32 ABCD | ×0.01 V | R | 04 | p.2 |
| 0x0004 | 3 (0x0003) | IR | L2 phase voltage | U32 ABCD | ×0.01 V | R | 04 | p.2 |
| 0x0006 | 5 (0x0005) | IR | L3 phase voltage | U32 ABCD | ×0.01 V | R | 04 | p.2 |
| 0x0008 | 7 (0x0007) | IR | L1 current | U32 ABCD | ×0.0001 A | R | 04 | p.2 |
| 0x000A | 9 (0x0009) | IR | L2 current | U32 ABCD | ×0.0001 A | R | 04 | p.2 |
| 0x000C | 11 (0x000B) | IR | L3 current | U32 ABCD | ×0.0001 A | R | 04 | p.2 |
| 0x000E | 13 (0x000D) | IR | L1-L2 voltage | U32 ABCD | ×0.01 V | R | 04 | p.3 |
| 0x0010 | 15 (0x000F) | IR | L2-L3 voltage | U32 ABCD | ×0.01 V | R | 04 | p.3 |
| 0x0012 | 17 (0x0011) | IR | L3-L1 voltage | U32 ABCD | ×0.01 V | R | 04 | p.3 |
| 0x0026 | 37 (0x0025) | IR | L1 power factor | S32 ABCD | ×0.0001 | R | 04 | p.3 |
| 0x0028 | 39 (0x0027) | IR | L2 power factor | S32 ABCD | ×0.0001 | R | 04 | p.3 |
| 0x002A | 41 (0x0029) | IR | L3 power factor | S32 ABCD | ×0.0001 | R | 04 | p.3 |
| 0x0032 | 49 (0x0031) | IR | Frequency | U32 ABCD | ×0.001 Hz | R | 04 | p.3 |
| 0x0034 | 51 (0x0033) | IR | Equivalent phase voltage | U32 ABCD | ×0.01 V | R | 04 | p.3 |
| 0x0036 | 53 (0x0035) | IR | Equivalent phase-to-phase voltage | U32 ABCD | ×0.01 V | R | 04 | p.3 |
| 0x0038 | 55 (0x0037) | IR | Equivalent current | U32 ABCD | ×0.0001 A | R | 04 | p.3 |
| 0x0040 | 63 (0x003F) | IR | Equivalent power factor | S32 ABCD | ×0.0001 | R | 04 | p.3 |
| 0x0042 | 65 (0x0041) | IR | VLL unbalance | U32 ABCD | ×0.01 % | R | 04 | p.3 |
| 0x0044 | 67 (0x0043) | IR | VLN unbalance | U32 ABCD | ×0.01 % | R | 04 | p.3 |
| 0x0046 | 69 (0x0045) | IR | Current unbalance | U32 ABCD | ×0.01 % | R | 04 | p.3 |
| 0x0054 | 83 (0x0053) | IR | THD L1 voltage | U32 ABCD | ×0.01 % | R | 04 | p.3 |
| 0x0056 | 85 (0x0055) | IR | THD L2 voltage | U32 ABCD | ×0.01 % | R | 04 | p.3 |
| 0x0058 | 87 (0x0057) | IR | THD L3 voltage | U32 ABCD | ×0.01 % | R | 04 | p.3 |
| 0x005A | 89 (0x0059) | IR | THD L1 current | U32 ABCD | ×0.01 % | R | 04 | p.3 |
| 0x005C | 91 (0x005B) | IR | THD L2 current | U32 ABCD | ×0.01 % | R | 04 | p.3 |
| 0x005E | 93 (0x005D) | IR | THD L3 current | U32 ABCD | ×0.01 % | R | 04 | p.3 |
| 0x2FF0 | 12271 (0x2FEF) | HR | Commands | U16 | W | 06 | 0 = Reset MAX-MIN · 1 = Reset MAX demand · 2 = Reset partial and tariff energy counters · 3 = Reset partial hour counters · 4 = Reset counters · 5 = Reset alarms · 6 = Reset limit thresholds · 8 = Setup to default (reboot afterwards) · 12 = Reset event list p.9 | |
| 0x2F03 | 12034 (0x2F02) | HR | Save to flash and reboot | U16 | W | 06 | Example 01 06 2F 02 00 05 E0 DD (p.9) 5 = Save and reboot (no response) p.8~9 |
Notes
- Measurement tables allow FC 03 and 04 ('FUNCTION 0x03 – 0x04', p.2). Powers (kW/100000 etc.) carry a footnote (1) whose text was not found, so they are left out. Energies are 4 words (Unsigned Long) and are not converted to PortDock types (up to u32).
- EASY BRANCH points (EXS4…) take the node numbers after the DMG (e.g. DMG 1, BRN01 2) (p.2). Pages are PDF pages (English/Polish document).
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- lovato/dmg7000.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- POWER ANALYZERS Modbus manual DMG7000-7500-8000-9000 EXS40000-EXS4001 — Lovato Electric, I676 GB PL 03 22 · Protocol specifications PDF p.1, register tables pp.2-8, parameter setup and commands pp.8-9 · checked 2026-11-01