An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Data · parity · stop | 8 · — · 1 |
| 32-bit order | CDAB |
| Max per request | 18 registers |
| Manual address style | 40001/30001 style (wire address + 1, first digit = table) |
- The manual gives both the 'Modicom address' (300001 style) and the 'Physical address' (word address in the frame) (p.3). address is the physical address (= Modicom − 300001).
- FC 03 and 04 give the same result, up to 18 words per request; settings use FC 06 (pp.3-4). 1 stop bit fixed (p.12). Factory baud and address are not in this document.
- INT32: words LSW→MSW (p.7) → CDAB.
Registers (27)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 300001 (0000h) | 0 (0x0000) | IR | V L1-N | S32 CDAB | ×0.1 V | R | 04 | p.8 Table 2.3-1 |
| 300003 (0002h) | 2 (0x0002) | IR | V L2-N | S32 CDAB | ×0.1 V | R | 04 | p.8 Table 2.3-1 |
| 300005 (0004h) | 4 (0x0004) | IR | V L3-N | S32 CDAB | ×0.1 V | R | 04 | p.8 Table 2.3-1 |
| 300007 (0006h) | 6 (0x0006) | IR | V L1-L2 | S32 CDAB | ×0.1 V | R | 04 | p.8 Table 2.3-1 |
| 300009 (0008h) | 8 (0x0008) | IR | V L2-L3 | S32 CDAB | ×0.1 V | R | 04 | p.8 Table 2.3-1 |
| 300011 (000Ah) | 10 (0x000A) | IR | V L3-L1 | S32 CDAB | ×0.1 V | R | 04 | p.8 Table 2.3-1 |
| 300013 (000Ch) | 12 (0x000C) | IR | A L1 Σ | S32 CDAB | ×0.001 A | R | 04 | p.8 Table 2.3-1 |
| 300015 (000Eh) | 14 (0x000E) | IR | A L2 Σ | S32 CDAB | ×0.001 A | R | 04 | p.8 Table 2.3-1 |
| 300017 (0010h) | 16 (0x0010) | IR | A L3 Σ | S32 CDAB | ×0.001 A | R | 04 | p.8 Table 2.3-1 |
| 300019 (0012h) | 18 (0x0012) | IR | W Σ | S32 CDAB | ×0.1 W | R | 04 | p.8 Table 2.3-1 |
| 300021 (0014h) | 20 (0x0014) | IR | VA Σ | S32 CDAB | ×0.1 VA | R | 04 | p.8 Table 2.3-1 |
| 300023 (0016h) | 22 (0x0016) | IR | var Σ | S32 CDAB | ×0.1 var | R | 04 | p.8 Table 2.3-1 |
| 300025 (0018h) | 24 (0x0018) | IR | kWh (+) TOT Σ | S32 CDAB | ×0.1 kWh | R | 04 | p.8 Table 2.3-1 |
| 300027 (001Ah) | 26 (0x001A) | IR | kvarh (+) TOT Σ | S32 CDAB | ×0.1 kvarh | R | 04 | p.8 Table 2.3-1 |
| 300029 (001Ch) | 28 (0x001C) | IR | W DMD Σ | S32 CDAB | ×0.1 W | R | 04 | p.8 Table 2.3-1 |
| 300033 (0020h) | 32 (0x0020) | IR | W MAXDMD Σ | S32 CDAB | ×0.1 W | R | 04 | p.8 Table 2.3-1 |
| 300037 (0024h) | 36 (0x0024) | IR | PF Σ | S32 CDAB | ×0.001 | R | 04 | Sign as in section 2.1.1 p.8 Table 2.3-1 |
| 300269 (010Ch) | 268 (0x010C) | IR | A L1 TCDA1 | S32 CDAB | ×0.001 A | R | 04 | p.8 Table 2.3-1 |
| 300271 (010Eh) | 270 (0x010E) | IR | A L2 TCDA1 | S32 CDAB | ×0.001 A | R | 04 | p.8 Table 2.3-1 |
| 300273 (0110h) | 272 (0x0110) | IR | A L3 TCDA1 | S32 CDAB | ×0.001 A | R | 04 | p.8 Table 2.3-1 |
| 300281 (0118h) | 280 (0x0118) | IR | W TOT TCDA1 | S32 CDAB | ×0.1 W | R | 04 | p.8 Table 2.3-1 |
| 300287 (011Eh) | 286 (0x011E) | IR | kWh (+) TCDA1 TOT | S32 CDAB | ×0.1 kWh | R | 04 | p.8 Table 2.3-1 |
| 308193 (2000h) | 8192 (0x2000) | HR | RS485 instrument address | U16 | R/W | 03·06 | Range 1 ~ 247 p.12 Table 2.7-10 | |
| 308194 (2001h) | 8193 (0x2001) | HR | RS485 baud rate | U16 | R/W | 03·06 | 0 = 9.6 kbps · 1 = 19.2 kbps · 2 = 38.4 kbps p.12 Table 2.7-10 | |
| 308195 (2002h) | 8194 (0x2002) | HR | RS485 parity | U16 | R/W | 03·06 | 0 = No parity · 1 = Even parity p.12 Table 2.7-10 | |
| 316385 (4000h) | 16384 (0x4000) | HR | Reset partial meters and demand | U16 | W | 06 | 1 = Execute p.12 Table 2.7-11 | |
| 316386 (4001h) | 16385 (0x4001) | HR | Reset total energy meters | U16 | W | 06 | 1 = Execute p.12 Table 2.7-11 |
Notes
- EM271 measures two current-transformer groups (TCD): Σ is the sum, TCDA1 the first group. Values not handled by the measuring system return MSB 7FFDh (p.8). Availability differs per system column (Table 2.3-1).
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- carlo-gavazzi/em271.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- EM271 Communication Protocol — Carlo Gavazzi, Version 1 Revision 2 (2018-01-29) · 1.2 Modbus functions pp.3-5, 2.1 data format p.7, Table 2.3-1 p.8, Tables 2.7-10 and 2.7-11 p.12 · checked 2026-11-01