Reading an MC protocol 3E binary frame — header, command, device, end code

An MC protocol (SLMP) 3E binary request and reply, byte by byte: subheader, station fields, length, timer, command, device, end code; how 4E and ASCII differ.

Tools for this guidePLC Simulator Windows program · freeMC Protocol (SLMP) Frame Decoder web · no installInteger & Base Converter web · no install

An MC protocol (SLMP) 3E frame starts with «subheader + station fields + data length». A request then carries the monitoring timer, command, subcommand and command data; a reply carries the end code and response data. Binary code sends any number of two or more bytes low byte first (little-endian). Below is a request that reads three words from D100, and its reply.

Request: batch read D100–D102

50 00 00 FF FF 03 00 0C 00 10 00 01 04 00 00 64 00 00 A8 03 00
BytesFieldMeaning
50 00Subheader3E request
00Network No.00
FFPC No.FF
FF 03Request destination module I/O No.03FF (low byte first)
00Request destination module station No.00 — 00, FF, 03FF, 00 together mean the connected station itself
0C 00Request data length12 bytes — from the monitoring timer to the end
10 00Monitoring timer0x0010 = 16 × 0.25 s = 4 s
01 04Command0401 Read (batch)
00 00Subcommand0000 word units
64 00 00Head device number100 (3 bytes)
A8Device codeD data register
03 00Number of device points3 words

The length of 12 is timer 2 + command 2 + subcommand 2 + device 4 + points 2 bytes. If it does not match, the receiver cannot cut the frame correctly, and PortDock PLC Simulator answers C057.

Reply: values 0x1995, 0x1202, 0x1130

D0 00 00 FF FF 03 00 08 00 00 00 95 19 02 12 30 11
BytesFieldMeaning
D0 00Subheader3E reply
00 FF FF 03 00Station fieldsechoed from the request
08 00Response data length8 bytes — from the end code to the end
00 00End code0000 completed
95 19D1000x1995 = 6549
02 12D1010x1202 = 4610
30 11D1020x1130 = 4400

The reply carries no device numbers; which device each value belongs to comes from the matching request.

Error reply

D0 00 00 FF FF 03 00 0B 00 59 C0 00 FF FF 03 00 01 01 00 00

End code «59 C0» is C059. The next 9 bytes are error information: the request's network, PC, I/O and station numbers (00 FF FF 03 00), command «01 01» (0101) and subcommand «00 00». Length 0B 00 = end code 2 + error information 9. A program that sends several requests can tell from these fields which one was refused. «MC protocol end codes: what to check» goes through each code.

Reading in bit units (subcommand 0001)

Reading the 8 points M100–M107 in bit units uses command data «01 04 01 00 64 00 00 90 08 00», and the reply data is «00 01 00 11». Each point takes 4 bits and the earlier point sits in the upper 4 bits, so M100=0, M101=0, M102=0, M103=1, M104=0, M105=0, M106=1, M107=1. With an odd number of points the lower 4 bits of the last byte are 0.

Bit devices in word units (subcommand 0000)

Reading 2 words from M100 in word units returns M100–M131, 32 points. One word holds 16 points, and the lowest number is bit 0. The reply «34 12 02 00» means M100–M115 = 0x1234 and M116–M131 = 0x0002; the set bits 2, 4, 5, 9 and 12 of 0x1234 mean M102, M104, M105, M109 and M112 are ON.

How 4E and ASCII differ

To decode bytes you received, paste them into the web tool «MC Protocol (SLMP) Frame Decoder». Add the matching request with a reply and each value is labelled with its device.

This guide is based on Mitsubishi Electric's public manuals (SLMP and MC protocol); it is not affiliated with Mitsubishi Electric.