メーカーのマニュアルから事実(アドレス・型・単位・倍率)だけを写してまとめた非公式の資料です。メーカーとは関係がなく、ファームウェアや形式によって異なることがあります。書き込み(運転指令・設定変更)の前に、必ず機器のマニュアルで確認してください。
通信の既定値
| プロトコル | Modbus RTU |
|---|---|
| ボーレート(出荷時) | 9600 bps — 選択肢: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200 |
| データ・パリティ・ストップ | 8 · なし · 1 |
| 局番(出荷時) | 31 (1~255) |
| 1 回の要求の最大 | レジスタ 16 個 |
| マニュアルのアドレス表記 | 通信アドレスそのまま(0 始まり) |
- Addressing: the read example (p.714) sends slave 02, FC03, start 00 20, count 00 04, CRC 45 F0 to read from 0020H (drive status 1); the write example (p.715) sends FC10 start 00 01, 2 registers, writing 0001h (forward run) to 0001H and 1770h (60.00 Hz) to 0002H. Manual address = frame address. (The write example's CRC is printed as 63 39 but computes to 6D B7; this does not affect addressing.)
- Only function codes 03H (read, up to 16 registers), 08H (loopback) and 10H (write multiple) — no 06H (p.712, p.714).
- Defaults: H5-01 address 1F (31), range 0-FF (0 = no response); H5-02 3 = 9600 bps (0-8 = 1200-115200); H5-03 0 = no parity; 8 data bits and 1 stop bit fixed, RTU only (p.703, p.707). Cycle power after changes.
- Entries where the manual prints 'ov' as 'Drive Overheat Warning (ov)' (0021H bit 1, 002AH bit 6, fault code 0008H, etc.) are left out because the name and code disagree.
レジスタ (36)
«通信アドレス» は要求フレームに載る 0 始まりのアドレスです(PortDock の «0 始まり» 表記)。値 = 生の値 × 倍率。領域: HR 保持レジスタ、IR 入力レジスタ、CO コイル、DI 入力ステータス。ファンクションコードは 16 進。
レジスタ名・説明・値の意味・注意・出典の版とページは、マニュアルの表記と照らし合わせやすいよう英語のまま載せています。
36 件
表は横にスクロールできます — 最初の列(マニュアルのアドレス)は固定です。
| マニュアル | 通信アドレス | 領域 | 名前 | 型 | 単位・倍率 | R/W | FC | 説明 |
|---|---|---|---|---|---|---|---|---|
| 0001H | 1 (0x0001) | HR | Operation commands and multi-function inputs | U16 | R/W | 03·10 | b0 Forward run (H5-12=0) / Run (H5-12=1) · b1 Reverse run (H5-12=0) / FWD-REV, 1 = reverse (H5-12=1) · b2 External fault (EF0) · b3 Fault reset · b4 Multi-function input 1 · b5 Multi-function input 2 · b6 Multi-function input 3 · b7 Multi-function input 4 · b8 Multi-function input 5 · b9 Multi-function input 6 · b10 Multi-function input 7 · b11 Multi-function input 8 p.716 | |
| 0002H | 2 (0x0002) | HR | Frequency reference | U16 | R/W | 03·10 | Unit set by o1-03 (0 = 0.01 Hz, 1 = 0.01%, 2 = r/min, 3 = user). o1-03 default depends on A1-02 (control mode). Manual FC10 example: 60.00 Hz = 1770h (p.715) p.716 | |
| 0003H | 3 (0x0003) | HR | Output voltage gain | U16 | ×0.1 % | R/W | 03·10 | 1000 (100.0%) at power-up 範囲 2 ~ 200 % p.716 |
| 0004H | 4 (0x0004) | HR | Torque reference / torque limit | S16 | ×0.1 % | R/W | 03·10 | Only when torque control is enabled p.716 |
| 0005H | 5 (0x0005) | HR | Torque compensation | S16 | ×0.1 % | R/W | 03·10 | Only when torque control is enabled p.716 |
| 0006H | 6 (0x0006) | HR | PID target | S16 | ×0.01 % | R/W | 03·10 | p.716 |
| 0009H | 9 (0x0009) | HR | Multi-function digital output settings | U16 | R/W | 03·10 | b0 Contact output 1 (M1-M2) · b1 Contact output 2 (M3-M4) · b2 Contact output 3 (M5-M6) · b6 Enables the function in bit 7 · b7 Fault contact output (MA/MB-MC) p.716 | |
| 0020H | 32 (0x0020) | HR | Drive status 1 | U16 | R | 03 | b0 During run · b1 During reverse · b2 Drive ready · b3 Fault · b4 Data setting error · b5 Multi-function contact output 1 (M1-M2) · b6 Multi-function contact output 2 (M3-M4) · b7 Multi-function contact output 3 (M5-M6) · b14 ComRef enabled · b15 ComCtrl enabled p.717 | |
| 0021H | 33 (0x0021) | HR | Fault contents 1 | U16 | R | 03 | Bit 1 is printed as 'Drive Overheat Warning (ov)' (name and code disagree), so it is left out b0 Overcurrent (oC), ground fault (GF) · b2 Drive overload (oL2) · b3 Overheat 1 (oH1), drive overheat warning (oH2) · b4 Braking transistor fault (rr), braking resistor overheat (rH) · b6 PID feedback loss (FbL/FbH) · b7 External fault EF-EF8 · b8 Hardware fault CPF (incl. oFx) · b9 Motor overload (oL1), overtorque (oL3/oL4), undertorque (UL3/UL4) · b10 PG disconnected (PGo), PG hardware fault (PGoH), overspeed (oS), speed deviation (dEv) · b11 Main circuit undervoltage (Uv) · b12 DC bus undervoltage (Uv1), control power fault (Uv2), undervoltage 3 (Uv3) · b13 Output phase loss (LF), input phase loss (PF) · b14 MEMOBUS communication error (CE), option communication error (bUS) · b15 External operator connection fault (oPr) p.717 | |
| 0022H | 34 (0x0022) | HR | Data link status | U16 | R | 03 | b0 Writing data or switching motors · b3 Upper or lower limit error · b4 Data conformity error · b5 Writing to EEPROM · b6 0 = write to EEPROM, 1 = RAM only (when H5-17 = 1) p.718 | |
| 0023H | 35 (0x0023) | HR | Frequency reference (monitor) | U16 | R | 03 | Unit set by o1-03 (p.728 note <1>) p.718 | |
| 0024H | 36 (0x0024) | HR | Output frequency | U16 | R | 03 | Unit set by o1-03 (p.728 note <1>) p.718 | |
| 0025H | 37 (0x0025) | HR | Output voltage reference | U16 | ×0.1 V | R | 03 | Units set by H5-10 (0.1 V units) p.718 |
| 0026H | 38 (0x0026) | HR | Output current | U16 | A | R | 03 | Scale by model: 2A0004-2A0040, 4A0002-4A0023 = 0.01 A; 2A0056-2A0415, 4A0031-4A0675 = 0.1 A; 4A0930, 4A1200 = 1 A p.718 |
| 0027H | 39 (0x0027) | HR | Output power | U16 | R | 03 | No unit given in the data table p.718 | |
| 0028H | 40 (0x0028) | HR | Torque reference | U16 | R | 03 | No unit given in the data table p.718 | |
| 0029H | 41 (0x0029) | HR | Fault contents 2 | U16 | R | 03 | b0 Output short circuit or IGBT fault (SC) · b1 Ground fault (GF) · b2 Input phase loss (PF) · b3 Output phase loss (LF) · b4 Braking resistor overheat (rH) · b6 Motor overheat 2, PTC input (oH4) p.718 | |
| 002AH | 42 (0x002A) | HR | Alarm contents 1 | U16 | R | 03 | Bit 6 is printed as 'Drive Overheat Warning (ov)' (name and code disagree), so it is left out b2 Forward/reverse run command input error (EF) · b3 Drive baseblock (bb) · b4 Overtorque detection 1 (oL3) · b5 Heatsink overheat (oH) · b7 Undervoltage (Uv) · b8 Internal fan fault (FAn) · b9 MEMOBUS communication error (CE) · b10 Option communication error (bUS) · b11 Undertorque detection 1/2 (UL3/UL4) · b12 Motor overheat (oH3) · b13 PID feedback loss (FbL, FbH) · b15 Serial communication transmission error (CALL) p.718 | |
| 002BH | 43 (0x002B) | HR | Input terminal status | U16 | R | 03 | b0 Terminal S1 closed · b1 Terminal S2 closed · b2 Terminal S3 closed · b3 Terminal S4 closed · b4 Terminal S5 closed · b5 Terminal S6 closed · b6 Terminal S7 closed · b7 Terminal S8 closed p.719 | |
| 002CH | 44 (0x002C) | HR | Drive status 2 | U16 | R | 03 | b0 During run · b1 Zero speed · b2 Speed agree · b3 User speed agree · b4 Frequency detection 1 · b5 Frequency detection 2 · b6 Drive ready · b7 During undervoltage · b8 During baseblock · b9 Frequency reference from operator keypad · b10 Run command from operator keypad · b11 Over/undertorque 1, 2 · b12 Frequency reference loss · b13 During fault restart · b14 Fault · b15 Communication timeout p.719 | |
| 002DH | 45 (0x002D) | HR | Output terminal status | U16 | R | 03 | b0 Multi-function contact output 1 (M1-M2) · b1 Multi-function contact output 2 (M3-M4) · b2 Multi-function contact output 3 (M5-M6) · b7 Fault contact output (MA/MB-MC) p.719 | |
| 0031H | 49 (0x0031) | HR | DC bus voltage | U16 | V | R | 03 | p.719 |
| 0032H | 50 (0x0032) | HR | Torque reference (U1-09) | U16 | % | R | 03 | p.719 |
| 0038H | 56 (0x0038) | HR | PID feedback | U16 | ×0.1 % | R | 03 | Unsigned, 100% = max. output frequency p.719 |
| 0039H | 57 (0x0039) | HR | PID input | S16 | ×0.1 % | R | 03 | 100% = max. output frequency p.719 |
| 003AH | 58 (0x003A) | HR | PID output | S16 | ×0.1 % | R | 03 | 100% = max. output frequency p.719 |
| 003DH | 61 (0x003D) | HR | Communications error contents | U16 | R | 03 | Kept until fault reset b0 CRC error · b1 Data length error · b3 Parity error · b4 Overrun error · b5 Framing error · b6 Timeout p.720 | |
| 004BH | 75 (0x004B) | HR | Drive status (U1-12) | U16 | R | 03 | b0 During run · b1 During zero speed · b2 During reverse run · b3 During fault reset signal input · b4 During speed agree · b5 Drive ready · b6 Alarm · b7 Fault · b8 During operation error (oPE) · b9 During momentary power loss · b10 Motor 2 selected · b14 ComRef / NetRef status · b15 ComCtrl / NetCtrl status p.720 | |
| 007FH | 127 (0x007F) | HR | Minor fault code | U16 | R | 03 | Code meanings: alarm register table p.731 p.720 | |
| 0080H | 128 (0x0080) | HR | Current fault (U2-01) | U16 | R | 03 | Value is a fault code (Table C.6); only some listed, 0008H left out (name and code disagree) 2 = Uv1 undervoltage · 3 = Uv2 control power supply undervoltage · 4 = Uv3 soft charge circuit fault · 6 = GF ground fault · 7 = oC overcurrent · 9 = oH heatsink overheat · 10 = oH1 heatsink overheat · 11 = oL1 motor overload · 12 = oL2 drive overload · 13 = oL3 overtorque detection 1 · 14 = oL4 overtorque detection 2 · 27 = PF input phase loss · 28 = LF output phase loss · 33 = CE MEMOBUS/Modbus communication error p.729 Table C.6 | |
| 0081H | 129 (0x0081) | HR | Previous fault (U2-02) | U16 | R | 03 | Value is a fault code (Table C.6); only some listed 2 = Uv1 undervoltage · 3 = Uv2 control power supply undervoltage · 4 = Uv3 soft charge circuit fault · 6 = GF ground fault · 7 = oC overcurrent · 9 = oH heatsink overheat · 10 = oH1 heatsink overheat · 11 = oL1 motor overload · 12 = oL2 drive overload · 13 = oL3 overtorque detection 1 · 14 = oL4 overtorque detection 2 · 27 = PF input phase loss · 28 = LF output phase loss · 33 = CE MEMOBUS/Modbus communication error p.729 Table C.6 | |
| 0098H | 152 (0x0098) | HR | Cumulative operation time (U4-01), 10 h units | U16 | ×10 h | R | 03 | For 12345 h: 0098H = 1234, 0099H = 5 p.720 |
| 0099H | 153 (0x0099) | HR | Cumulative operation time (U4-01), 1 h digit | U16 | h | R | 03 | p.720 |
| 00ABH | 171 (0x00AB) | HR | Drive rated current | U16 | A | R | 03 | Scale by model as for 0026H (p.728 note <2>) p.720 |
| 0900H | 2304 (0x0900) | HR | Enter command (save to EEPROM) | U16 | W | 10 | Write 0. Write-only p.732 | |
| 0910H | 2320 (0x0910) | HR | Enter command (RAM only) | U16 | W | 10 | Write 0. Changes are lost at power-off p.732 |
注意
- To run and set frequency by communication set b1-02 = 2 and b1-01 = 2. Depending on H5-11, parameter writes need an Enter command.
PortDock ですぐ読み出す
- 無料の PortDock Modbus Master をインストールし、機器と同じ通信設定で接続します。
- 中央の表のツールバーの «機器プロファイル…» でこの機器を選び «読み込む» — ポーリング表・セル名・型・局番が入ります(通信の既定値も合わせられます)。
- セル名に単位・倍率(例 «×0.01 Hz»)が付きます。画面の値は生の値なので、倍率を掛けて読みます。
- 機器なしで自分のプログラムを試験するには、PortDock Modbus Slave の «機器を模擬…» で同じマップ(例の値)を立ち上げます。
RS-485 の配線は 配線図作成ツール で、この機器の名前・局番・ボーレート・パリティを入れた図を描けます(端子番号はマニュアルで確認)。
JSON をダウンロード
- yaskawa/a1000.json (GitHub の原本) · このサイトのコピー · 修正履歴
- schema.json — 形式の説明(JSON Schema)。table・address(0 始まり)・type・order は PortDock の CSV と同じです。
- ライセンス: CC BY 4.0 — 使うときは出典を明記してください:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
とこのページの URL。LICENSE · データ一式・版・変更点(英語) - 誤りを見つけたら、マニュアルのページを添えて GitHub の Issue でお知らせください。
出典
- YASKAWA AC Drive-A1000 High Performance Vector Control Drive Technical Manual (SIEP C710616 41H) — YASKAWA ELECTRIC CORPORATION, SIEP C710616 41H <7>-0, PDF dated March 2022 · Appendix C MEMOBUS/Modbus pp.703-732 (data table pp.716-731) · 確認日 2026-10-23