メーカーのマニュアルから事実(アドレス・型・単位・倍率)だけを写してまとめた非公式の資料です。メーカーとは関係がなく、ファームウェアや形式によって異なることがあります。書き込み(運転指令・設定変更)の前に、必ず機器のマニュアルで確認してください。
通信の既定値
| プロトコル | Modbus RTU |
|---|---|
| データ・パリティ・ストップ | 8 · — · — |
| 1 回の要求の最大 | レジスタ 50 個 |
| マニュアルのアドレス表記 | 通信アドレスそのまま(0 始まり) |
- Addressing: the manual's CRC example (pp.3-22-3-23) reads 20 words from function code P02 (group P = 03h, number 02h) at station 1 with 01 03 03 02 00 14 E4 41. Wire address = group code × 256 + number (0-based, Table 3.2 p.3-5). The CRC matches calculation. The manual also writes «40000 + group × 256 + number» (J60 = 43388); unlike the usual PLC notation where 40001 is the first address, the value minus 40000 is the wire address (p.3-4).
- y04 baud 2400/4800/9600/19200/38400 bps; y06 parity 0 none (2 stop bits), 1 even, 2 odd, 3 none (1 stop bit); Modbus RTU is fixed at 8 bits (p.2-21). Set y10 (port 1) or y20 (port 2) = 0 for Modbus RTU (p.2-22). Factory settings are not in this manual and are left empty.
- FC03 reads up to 50 words at a time. Unused function codes read as 0 without an error, and one read does not cross a group (p.3-5).
レジスタ (55)
«通信アドレス» は要求フレームに載る 0 始まりのアドレスです(PortDock の «0 始まり» 表記)。値 = 生の値 × 倍率。領域: HR 保持レジスタ、IR 入力レジスタ、CO コイル、DI 入力ステータス。ファンクションコードは 16 進。
レジスタ名・説明・値の意味・注意・出典の版とページは、マニュアルの表記と照らし合わせやすいよう英語のまま載せています。
55 件
表は横にスクロールできます — 最初の列(マニュアルのアドレス)は固定です。
| マニュアル | 通信アドレス | 領域 | 名前 | 型 | 単位・倍率 | R/W | FC | 説明 |
|---|---|---|---|---|---|---|---|---|
| S01 (0701h) | 1793 (0x0701) | HR | S01 Frequency reference (p.u.) | S16 | R/W | 03·06·10 | ±20000 = maximum frequency. When S01 is not 0 it takes precedence over S05 p.5-2 Table 5.2 | |
| S05 (0705h) | 1797 (0x0705) | HR | S05 Frequency reference | U16 | ×0.01 Hz | R/W | 03·06·10 | 範囲 0 ~ 655.35 Hz p.5-2 Table 5.2 |
| S06 (0706h) | 1798 (0x0706) | HR | S06 Operation command | U16 | R/W | 03·06·10 | Format [14]. Manual example: FWD and X1 on = 0005h. To reset an alarm with bit 15, write 1 and then 0 again b0 FWD forward run command · b1 REV reverse run command · b2 X1 general-purpose input · b3 X2 general-purpose input · b4 X3 general-purpose input · b5 X4 general-purpose input · b6 X5 general-purpose input · b7 X6 general-purpose input · b8 X7 general-purpose input · b13 XF (FWD) general-purpose input · b14 XR (REV) general-purpose input · b15 RST alarm reset p.5-2 Table 5.2, p.5-67 | |
| S07 (0707h) | 1799 (0x0707) | HR | S07 Universal DO | U16 | R/W | 03·06·10 | Format [15]: drives output terminals assigned to universal DO b0 Y1 general-purpose output · b1 Y2 general-purpose output · b2 Y3 general-purpose output · b3 Y4 general-purpose output · b4 Y5 general-purpose output · b8 30 alarm output (general-purpose output) p.5-2 Table 5.2, p.5-67 | |
| S08 (0708h) | 1800 (0x0708) | HR | S08 Acceleration time (F07) | U16 | ×0.1 s | R/W | 03·06·10 | 範囲 0 ~ 3600 s p.5-2 Table 5.2 |
| S09 (0709h) | 1801 (0x0709) | HR | S09 Deceleration time (F08) | U16 | ×0.1 s | R/W | 03·06·10 | 範囲 0 ~ 3600 s p.5-2 Table 5.2 |
| S12 (070Ch) | 1804 (0x070C) | HR | S12 Universal AO | S16 | R/W | 03·06·10 | ±20000 = full scale p.5-2 Table 5.2 | |
| S13 (070Dh) | 1805 (0x070D) | HR | S13 PID command | S16 | R/W | 03·06·10 | ±20000 = ±100% p.5-2 Table 5.2 | |
| S14 (070Eh) | 1806 (0x070E) | HR | S14 Alarm reset command | U16 | R/W | 03·06·10 | Writing 1 resets the alarm. Always reads 0 0 = None · 1 = Alarm reset p.5-2 Table 5.2, p.5-5 | |
| S19 (0713h) | 1811 (0x0713) | HR | S19 Speed command | S16 | r/min | R/W | 03·06·10 | p.5-2 Table 5.2 |
| M01 (0801h) | 2049 (0x0801) | HR | M01 Frequency reference (p.u.) (final command) | S16 | R | 03 | ±20000 = maximum frequency p.5-11 Table 5.8 | |
| M05 (0805h) | 2053 (0x0805) | HR | M05 Frequency reference (final command) | U16 | ×0.01 Hz | R | 03 | p.5-11 Table 5.8 |
| M06 (0806h) | 2054 (0x0806) | HR | M06 Output frequency 1 (p.u.) | S16 | R | 03 | ±20000 = maximum frequency, before slip compensation p.5-11 Table 5.8 | |
| M07 (0807h) | 2055 (0x0807) | HR | M07 Torque real value | S16 | ×0.01 % | R | 03 | 100% = motor rated torque p.5-11 Table 5.8 |
| M09 (0809h) | 2057 (0x0809) | HR | M09 Output frequency | U16 | ×0.01 Hz | R | 03 | Modbus RTU uses format [22] (0.00-655.35 Hz, unsigned) p.5-11 Table 5.8 |
| M10 (080Ah) | 2058 (0x080A) | HR | M10 Input power | U16 | ×0.01 % | R | 03 | 100% = nominal applicable motor output p.5-11 Table 5.8 |
| M11 (080Bh) | 2059 (0x080B) | HR | M11 Output current effective value | U16 | ×0.01 % | R | 03 | 100% = inverter rated current p.5-11 Table 5.8 |
| M12 (080Ch) | 2060 (0x080C) | HR | M12 Output voltage effective value | U16 | ×0.1 V | R | 03 | Format [3] (0.1 units) but there is no fractional part (changes in 1.0 V steps) p.5-11 Table 5.8 |
| M13 (080Dh) | 2061 (0x080D) | HR | M13 Operation command (final command) | U16 | R | 03 | Format [14]: final command from keypad, terminals and communications b0 FWD forward run command · b1 REV reverse run command · b2 X1 general-purpose input · b3 X2 general-purpose input · b4 X3 general-purpose input · b5 X4 general-purpose input · b6 X5 general-purpose input · b7 X6 general-purpose input · b8 X7 general-purpose input · b13 XF (FWD) general-purpose input · b14 XR (REV) general-purpose input · b15 RST alarm reset p.5-12 Table 5.9, p.5-67 | |
| M14 (080Eh) | 2062 (0x080E) | HR | M14 Operation status | U16 | R | 03 | Format [16] b0 FWD running forward · b1 REV running in reverse · b2 EXT DC braking (or pre-exciting) · b3 INT inverter shut down · b4 BRK braking · b5 NUV DC link voltage established (0 = undervoltage) · b7 VL voltage limiting · b8 IL current limiting · b9 ACC accelerating · b10 DEC decelerating · b11 ALM alarm relay (any fault) · b12 RL communications effective · b15 BUSY writing function code data p.5-12 Table 5.9, p.5-67 | |
| M15 (080Fh) | 2063 (0x080F) | HR | M15 General-purpose output terminal information | U16 | R | 03 | Format [15] b0 Y1 general-purpose output · b1 Y2 general-purpose output · b2 Y3 general-purpose output · b3 Y4 general-purpose output · b4 Y5 general-purpose output · b8 30 alarm output (general-purpose output) p.5-12 Table 5.9, p.5-67 | |
| M16 (0810h) | 2064 (0x0810) | HR | M16 Latest alarm contents | U16 | R | 03 | Alarm code (format [10], p.5-65) p.5-12 Table 5.9 | |
| M17 (0811h) | 2065 (0x0811) | HR | M17 Last alarm contents | U16 | R | 03 | Alarm code (format [10], p.5-65) p.5-12 Table 5.9 | |
| M18 (0812h) | 2066 (0x0812) | HR | M18 Second last alarm contents | U16 | R | 03 | Alarm code (format [10], p.5-65) p.5-12 Table 5.9 | |
| M19 (0813h) | 2067 (0x0813) | HR | M19 Third last alarm contents | U16 | R | 03 | Alarm code (format [10], p.5-65) p.5-12 Table 5.9 | |
| M20 (0814h) | 2068 (0x0814) | HR | M20 Cumulative operation time | U16 | h | R | 03 | p.5-12 Table 5.9 |
| M21 (0815h) | 2069 (0x0815) | HR | M21 DC link circuit voltage | U16 | V | R | 03 | p.5-12 Table 5.9 |
| M23 (0817h) | 2071 (0x0817) | HR | M23 Model code | U16 | R | 03 | Series, generation, model and voltage series as four hex digits (format [17]) p.5-12 Table 5.9 | |
| M24 (0818h) | 2072 (0x0818) | HR | M24 Capacity code | U16 | R | 03 | Format [11] p.5-12 Table 5.9 | |
| M25 (0819h) | 2073 (0x0819) | HR | M25 ROM version | U16 | R | 03 | p.5-12 Table 5.9 | |
| M26 (081Ah) | 2074 (0x081A) | HR | M26 Transmission error transaction code | U16 | R | 03 | RS-485 communications error code (format [20]) p.5-12 Table 5.9 | |
| M27 (081Bh) | 2075 (0x081B) | HR | M27 Frequency reference on alarm (p.u.) | S16 | R | 03 | ±20000 = maximum frequency p.5-12 Table 5.9 | |
| M31 (081Fh) | 2079 (0x081F) | HR | M31 Frequency reference on alarm | U16 | ×0.01 Hz | R | 03 | p.5-13 Table 5.10 |
| M32 (0820h) | 2080 (0x0820) | HR | M32 Output frequency 1 on alarm (p.u.) | S16 | R | 03 | ±20000 = maximum frequency p.5-13 Table 5.10 | |
| M33 (0821h) | 2081 (0x0821) | HR | M33 Torque real value on alarm | S16 | ×0.01 % | R | 03 | p.5-13 Table 5.10 |
| M35 (0823h) | 2083 (0x0823) | HR | M35 Output frequency on alarm | U16 | ×0.01 Hz | R | 03 | p.5-13 Table 5.10 |
| M36 (0824h) | 2084 (0x0824) | HR | M36 Input power on alarm | U16 | ×0.01 % | R | 03 | p.5-13 Table 5.10 |
| M37 (0825h) | 2085 (0x0825) | HR | M37 Output current effective value on alarm | U16 | ×0.01 % | R | 03 | p.5-13 Table 5.10 |
| M39 (0827h) | 2087 (0x0827) | HR | M39 Operation command on alarm | U16 | R | 03 | b0 FWD forward run command · b1 REV reverse run command · b2 X1 general-purpose input · b3 X2 general-purpose input · b4 X3 general-purpose input · b5 X4 general-purpose input · b6 X5 general-purpose input · b7 X6 general-purpose input · b8 X7 general-purpose input · b13 XF (FWD) general-purpose input · b14 XR (REV) general-purpose input · b15 RST alarm reset p.5-13 Table 5.10, p.5-67 | |
| M40 (0828h) | 2088 (0x0828) | HR | M40 Operation status on alarm | U16 | R | 03 | b0 FWD running forward · b1 REV running in reverse · b2 EXT DC braking (or pre-exciting) · b3 INT inverter shut down · b4 BRK braking · b5 NUV DC link voltage established (0 = undervoltage) · b7 VL voltage limiting · b8 IL current limiting · b9 ACC accelerating · b10 DEC decelerating · b11 ALM alarm relay (any fault) · b12 RL communications effective · b15 BUSY writing function code data p.5-13 Table 5.10, p.5-67 | |
| M41 (0829h) | 2089 (0x0829) | HR | M41 Output terminal information on alarm | U16 | R | 03 | b0 Y1 general-purpose output · b1 Y2 general-purpose output · b2 Y3 general-purpose output · b3 Y4 general-purpose output · b4 Y5 general-purpose output · b8 30 alarm output (general-purpose output) p.5-13 Table 5.10, p.5-67 | |
| M42 (082Ah) | 2090 (0x082A) | HR | M42 Cumulative operation time on alarm | U16 | h | R | 03 | p.5-13 Table 5.10 |
| M43 (082Bh) | 2091 (0x082B) | HR | M43 DC link circuit voltage on alarm | U16 | V | R | 03 | p.5-13 Table 5.10 |
| M44 (082Ch) | 2092 (0x082C) | HR | M44 Inverter internal air temperature on alarm | U16 | ℃ | R | 03 | p.5-13 Table 5.10 |
| M45 (082Dh) | 2093 (0x082D) | HR | M45 Heat sink temperature on alarm | U16 | ℃ | R | 03 | p.5-13 Table 5.10 |
| M46 (082Eh) | 2094 (0x082E) | HR | M46 Life of main circuit capacitor | U16 | ×0.1 % | R | 03 | 100% = capacity at shipment p.5-13 Table 5.10 |
| M49 (0831h) | 2097 (0x0831) | HR | M49 Input terminal [12] voltage (p.u.) | S16 | R | 03 | -20000 = -10 V, 20000 = 10 V p.5-14 Table 5.11 | |
| M50 (0832h) | 2098 (0x0832) | HR | M50 Input terminal [C1] current (p.u.) | U16 | R | 03 | 0 = 0 mA, 20000 = 20 mA p.5-14 Table 5.11 | |
| M52 (0834h) | 2100 (0x0834) | HR | M52 Input terminal [32] voltage (p.u.) | S16 | R | 03 | -20000 = -10 V, 20000 = 10 V p.5-14 Table 5.11 | |
| M54 (0836h) | 2102 (0x0836) | HR | M54 Input terminal [V2] voltage (p.u.) | S16 | R | 03 | -20000 = -10 V, 20000 = 10 V p.5-14 Table 5.11 | |
| M61 (083Dh) | 2109 (0x083D) | HR | M61 Inverter internal air temperature | U16 | ℃ | R | 03 | p.5-14 Table 5.11 |
| M62 (083Eh) | 2110 (0x083E) | HR | M62 Heat sink temperature | U16 | ℃ | R | 03 | p.5-14 Table 5.11 |
| M63 (083Fh) | 2111 (0x083F) | HR | M63 Load factor | S16 | ×0.01 % | R | 03 | 100% = motor rating p.5-14 Table 5.11 |
| M64 (0840h) | 2112 (0x0840) | HR | M64 Motor output | S16 | ×0.01 % | R | 03 | 100% = motor rated output (kW) p.5-14 Table 5.11 |
| M68 (0844h) | 2116 (0x0844) | HR | M68 PID final command | S16 | R | 03 | ±20000 = ±100% p.5-14 Table 5.11 |
注意
- Only S and M codes supported by both HVAC and AQUA whose meaning and unit are in the manual tables are included. M38 is left out (step 1.0 vs format [3] = 0.1), M47/M48 (life) because Table 5.10 (10 h) could not be matched with format [74], M69 (rated current) because its scale changes with capacity, and M53 because Table 5.11 calls it input terminal [C2] current while format Table 5.28 says voltage.
- Bit 6 of format [16] (operation status) is 0 (unused) in the bit diagram but TL (torque limiting) in the table below it, so it is left out (p.5-67).
- To run the drive and give the frequency reference over communications, set H30 (link function) and y98/y99 to communications (pp.2-17-2-19). Reading (M codes) works as is.
PortDock ですぐ読み出す
- 無料の PortDock Modbus Master をインストールし、機器と同じ通信設定で接続します。
- 中央の表のツールバーの «機器プロファイル…» でこの機器を選び «読み込む» — ポーリング表・セル名・型・局番が入ります(通信の既定値も合わせられます)。
- セル名に単位・倍率(例 «×0.01 Hz»)が付きます。画面の値は生の値なので、倍率を掛けて読みます。
- 機器なしで自分のプログラムを試験するには、PortDock Modbus Slave の «機器を模擬…» で同じマップ(例の値)を立ち上げます。
RS-485 の配線は 配線図作成ツール で、この機器の名前・局番・ボーレート・パリティを入れた図を描けます(端子番号はマニュアルで確認)。
JSON をダウンロード
- fuji-electric/frenic-hvac.json (GitHub の原本) · このサイトのコピー · 修正履歴
- schema.json — 形式の説明(JSON Schema)。table・address(0 始まり)・type・order は PortDock の CSV と同じです。
- ライセンス: CC BY 4.0 — 使うときは出典を明記してください:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
とこのページの URL。LICENSE · データ一式・版・変更点(英語) - 誤りを見つけたら、マニュアルのページを添えて GitHub の Issue でお知らせください。
出典
- RS-485 Communication User's Manual (FRENIC-HVAC, FRENIC-AQUA) — Fuji Electric, 24A7-E-0021b 3rd edition May 2015 · RS-485 settings pp.2-20-2-22, Modbus RTU messages pp.3-4-3-5, CRC example pp.3-22-3-23, command data p.5-2, monitor data pp.5-11-5-14, format numbers pp.5-51-5-52, format specifications pp.5-63-5-71 · 確認日 2026-10-24